ECB04/22/2026Class 1 - cease use violation: failure to maintain elevator device in a safe condition. Door zone restrictor found defective/inoperative, failing to restrict hoistway door opening outside the door zone. In addi$5K due
DOB03/27/2026Borough commissioner has ordered all work stopped underpermit# B00911674-I1 on 3/26/26.
ECB05/19/2026Electrical closet not dedicated to electrical distribution equipment only. Observed on the 6TH fl that the electrical closet is not dedicated the installation of internet/ camera equipment in the same closet asNothing owed — awaiting certificate of correction
ECB05/19/2026Laars boiler#3 has a outside combustion air inlet louver with a striped backdraft damper locking screw+ao smith hwh has incorrect safety discharge pipe;correct violation+submit certificate of correctionNothing owed — awaiting certificate of correction
ECB05/19/2026Electrical work without a permit. Observed in the basement laundry rm the new installation of emt pipes and 30 amp receptacles, breakers in panel for new electric dryers. 27-3018(b) checked BIS / DOB now no perNothing owed — awaiting certificate of correction
ECB05/19/2026Laars boiler#1 has threaded end on safety discharge pipe+broken tri gauge on hw storage tank#2+bypass around backflow preventer;correct violation+submit certificate of correctionNothing owed — awaiting certificate of correction
ECB05/21/2025Exit door not self-closing. Observed non self closing doors at exits and mechanical/utility rooms throughout building. Potential hazard., repair/replace doorNothing owed — awaiting certificate of correction
ECB05/21/2025Failure to maintain building in code-compliant manner. Observed unpermitted flex hose on exhausted of commercial dryer smooth interior. (mechanical code 504.8.1), repair and/or replaceNothing owed — awaiting certificate of correction
ECB02/13/2025Failure to comply with commissioner's order contained in summons #39097465R issued on 10/19/2023, and failure to file a certificate of correction pursuant to 28.201.1 and 1 rcny 102-01(d)(2). An acceptable certNothing owed — awaiting certificate of correction
ECB10/19/2023Back flow preventer for domestic hot water boiler leaking., maintain boiler; correct violating condition and submit a certificate of correction.Nothing owed — awaiting certificate of correction