ECB09/04/2026AT THE TIME OF INSPECTION OF THE 12-STORY BUILDING, I OBSERVED THE SIDEWALK SHED WAS NOT PROPERLY MAINTAINED. EXPOSED SHARP EDGES WERE PRESENT ALONG THE SHED, CREATING A CUT HAZARD TO PASSING PEDESTRIANS, CONTR$2K due
DOB03/18/2026FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER.AT THE TIME OF INSPECTION,OBSERVED DEFECTIVE CONDITIONS.EXP1,CRACK/BROKEN WINDOW PANE CRACK AND SPALLING STONE.EXP2 SPOILED ON FLAKING OF PAINT.EXP3 BOW WIN DOW LINTEL,CRACK WATER TABLE.REMEDY:REPAIR AND/OR REPLACE
DOB09/02/2025FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED SPALLED STONE ON EXPOSURE 1 SOUTH ELEVATION, CRACKED WORK ON EXPOSURE 2 WEST ELEVATION AND DAMAGED MORTAR ON ALL EXPOSURES IN MULTIPLE LOCATIONS. REMEDY: REPAIR AND/OR REPLACE
DOB09/02/2025FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER. OBSERVED SPALLED STONE ON EXPOSURE 1 SOUTH ELEVATION, CRACKED STONE WORT ON EXPOSURE 2 WEST ELEVATION AND DAMAGED MORTAR JOINTS ON ALL EXPOSURES IN MULTIPLE LOCATIONS. REMEDY: REPAIR AND/OR REPLACE
DOB06/17/2024CYCLE 9C UNSAFE REPORT FILED
DOB06/17/2024CYCLE 9C UNSAFE REPORT FILED
DOB06/17/2024CYCLE 9C UNSAFE REPORT FILED
DOB02/22/2024FAILED TO FILE FISP CYCLE 9C TECHNICAL REPORT BY 2/21/2024
DOB02/22/2024FAILED TO FILE FISP CYCLE 9C TECHNICAL REPORT BY 2/21/2024
DOB02/22/2024FAILED TO FILE FISP CYCLE 9C TECHNICAL REPORT BY 2/21/2024
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB05/20/2019FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB05/20/2019FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB05/20/2019FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB02/22/2019V-DOB VIOLATION - ACTIVE
DOB02/22/2019V-DOB VIOLATION - ACTIVE
DOB02/21/2019V-DOB VIOLATION - ACTIVE
DOB02/21/2019V-DOB VIOLATION - ACTIVE
DOB02/20/2019V-DOB VIOLATION - ACTIVE
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB01/23/2014V-DOB VIOLATION - ACTIVE
DOB08/05/2011V-DOB VIOLATION - ACTIVE
DOB04/25/19916
DOB07/02/1990V-DOB VIOLATION - ACTIVE
DOB07/02/1990V-DOB VIOLATION - ACTIVE
DOB06/29/19901
DOB05/23/1990(74) PROVIDE PROPER CLEARANCE BETWEEN THE CLUT AND THE SUFFER
DOB04/25/1990DEPARTMENT RECORDS INDICATE FAILURE TO COMPLETE INSTALLATION OF FIREMA N'S SERVICE AS REQUIRED BY SEC. 27.996.02
DOB12/13/1989V-DOB VIOLATION - ACTIVE
DOB12/12/1989V-DOB VIOLATION - ACTIVE
DOB10/12/198910
DOB02/15/1989V-DOB VIOLATION - ACTIVE
DOB02/15/1989V-DOB VIOLATION - ACTIVE
DOB02/15/1989V-DOB VIOLATION - ACTIVE
DOB02/15/1989V-DOB VIOLATION - ACTIVE
ECB02/12/2024FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8C REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FACADES REPORT REQUIRED BY 28-302.5 FOR CONTROL #802863. REMEDY: FILE ACCEPTABLE REPORT.Nothing owed — awaiting certificate of correction
ECB02/12/2024FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8C REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FACADES REPORT REQUIRED BY 28-302.5 FOR CONTROL #802862. REMEDY: FILE ACCEPTABLE REPORT.Nothing owed — awaiting certificate of correction
ECB01/16/2024FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8C REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FACADES REPORT REQUIRED BY 28-302.5 FOR CONTROL #802864. REMEDY: FILE ACCEPTABLE REPORT.Nothing owed — awaiting certificate of correction
ECB03/24/2022CEASE USE OF FEDERAL FST-300 BOILER. EVIDENCE OF BOILER RUNNING WITHOUT WATER. FIRE CHAMBER BULGED AND FULL OF WATER. DO NOT OPERATE BOILER UNTIL ALL HAZARDOUS CONDITIONS ARE IMMEDIATELY CORRECTED AND DOB IS NONothing owed — awaiting certificate of correction
ECB04/11/2016FAILURE TO FILE AN ACCEPTABLE AMENDED CYCLE 7 REPORT TO THIS DEPARTMENT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL LOCAL LAW FISP REPORT.RMDY:FILE AN AMENDED REPORT FOLLOWING REMEDIAL REPAINothing owed — awaiting certificate of correction
ECB06/18/2013FAILURE TO MAINTAIN BLDG WALLS & APPURTENANCES.NOTED:SPALLED & CRACKEDBRICKWORK AT A-NORTH ELEVN (EXPOUSRE1) AT FLOORS 3&4 AT MIDST & WEST SECTION;B-EAST ELEVN (EXP2) A-AT 12/F AND 1/F AT SHELF ANGLES BETW FLRSNothing owed — awaiting certificate of correction
ECB08/03/1988ALTERED BUILDING OCCUPIED WITHOUT A VALID C OF O. REMEDY: OBTAIN A VALID CERTIFICATE OF OCCUPANCY OR DISCONTINUE ILLEGAL USE.Nothing owed — awaiting certificate of correction