DOB01/15/2021V-DOB VIOLATION - ACTIVE
DOB01/15/2021V-DOB VIOLATION - ACTIVE
DOB01/28/2020V-DOB VIOLATION - ACTIVE
DOB01/28/2020V-DOB VIOLATION - ACTIVE
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB01/15/2019V-DOB VIOLATION - ACTIVE
DOB01/15/2019V-DOB VIOLATION - ACTIVE
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/27/2016V-DOB VIOLATION - ACTIVE
DOB01/27/2016V-DOB VIOLATION - ACTIVE
DOB01/13/1997V-DOB VIOLATION - ACTIVE
DOB08/22/1990VW-VIOLATION WORK WITHOUT PERMIT - ACTIVE
DOB06/29/19901
ECB06/01/2026WEIL MCLAIN BOILER MODEL # 588WAS NEVER SIGNED OFF UNDER PERMIT #520358675. GET PERMIT SIGNED OFFNothing owed — awaiting certificate of correction
ECB06/01/2026ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN THE KITCHEN ELECTRICAL CLOSET THE INSTALLATION OF TWO NEW 8-16 CIRCUIT PANEL BOXES WITH NEW BX CABLES LEAVING TO FEED MICROWAVE AND OVEN AND OTHER LOCATIONS. CHECKENothing owed — awaiting certificate of correction
ECB06/01/2026UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERVED IN THE KIDS PLAY RM EXPOSED WIRES FROM REMOVAL OF FIXTURE ALSO THRU OUT BUILDING RECEPTACLES ARE INSTNothing owed — awaiting certificate of correction
ECB06/01/2026FAILURE TO INSTALL GROUND-FAULT CIRCUIT INTERRUPTER (GFCI) PROTECTION AS REQUIRED. OBSERVED THRU OUT THE MEN AND WOMEN BATH RM NO GFCI COVERAGE LOCATED AT SINKS. ALSO IN THE MECHANICAL RMS NO GFCI IS NOT PROVIDNothing owed — awaiting certificate of correction
ECB06/30/2025XLASS 1: FILE CERTIFCATE OF CORRECTION FOR EXPIRED CATEGORY 1 INSPECTIONS. CLASS 2: UPON INSPECTION FOUND DEVICE TO BE OUT OF SERVICE. THIS PRESENTS A SAFETY HAZZARD TO SPECIAL NEEDS RESIDENTS & FIRST RESPONDERNothing owed — awaiting certificate of correction
ECB06/30/2025WEIL MCLAIN BOILER MODEL # 588, WAS NEVER SIGNED OFF UNDER PERMIT # 520358675. GET SIGNED OFF.Nothing owed — awaiting certificate of correction
ECB06/30/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8 (2014 CODE); 27-371; BC 1008.1.9 (2014 CODE); BC 1010.1.8 (2022 CODE); BC 1010.1.9 (2022 CODE). OBSENothing owed — awaiting certificate of correction
ECB06/30/2025UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. OBSERVED STORAGE ROOM UNDERNEATH STAIRCASE AT CELLAR LEVEL, WHICH IS PROHIBITED. POTENTIAL HAZARD., MAINTAIN STORAGE IN COMPLIANCE WITH FIRE CODENothing owed — awaiting certificate of correction
ECB06/17/2025CLASS 1: FILE CERTIFICATE OF CORRECTION FOR EXPIRED CATEGORY 1 INSPECTIONS.Nothing owed — awaiting certificate of correction
ECB10/18/2024FOUND ONE GAS FIRED WEIL MCLAIN BOILER MODEL 588 1358000 BTU UNREGISTERED. PERMIT # 520358675 IS NOT SIGNED OFF. CORRECT ALL VIOLATING CONDITIONSNothing owed — awaiting certificate of correction
ECB07/26/2024ENTIRE DEVICE IS SHUT DOWN. NEED TO REPAIR AND RE-INSPECTION REQUIRED. CAT 1 TEST TAG IS EXPIRED, 10/2021, NEED TO PERFORM TEST AND FILE WITH NYC DOB. CAT 5 TEST TAG IS EXPIRED, 12/2018, NEED TO PERFORM TEST ANNothing owed — awaiting certificate of correction
ECB05/17/2024CLASS 1: UPON INSPECTION FOUND DEVICE TO BE OUT OF SERVICE. THIS IS A SAFETY HAZZARD TO RESIDENTS & FIRST RESPONDERS. RESTORE TO SERVICE REPAIR IMMEDIATELY AS PER 1RCNY 11-02. WHEN SERVICE RESTORED CONTACT NYCDNothing owed — awaiting certificate of correction
ECB01/02/2024DOOR LOCK MONITORING NOT INSTALLED AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE NYCBC. THIS SAFETY DEVICE ENSURES PASSENGER SAFETY. AS PER 304.7 OF THE NYC ADMIN CODE ALL PASSENGER CARS MUST HAVE A CONTRACT WITNothing owed — awaiting certificate of correction
ECB06/21/2023WEIL MCLAIN/MODEL# 588. BOILER NOT REGISTERED. REGISTER BOILER.Hearing held — result not yet published
ECB06/21/2023OBSERVED IN THE KITCHEN LOCATED ON THE FIRST FLOOR COMMERCIAL QUICK DISCONNECT INSTALLED ON COMMERCIAL COOKING EQUIPMENT THAT IS NOT ON CASTERS. AS PER 411.1.1 COMMERCIAL COOKING APPLIANCES. COMMERCIAL COOKINGHearing held — result not yet published
ECB06/21/2023EMERGENCY DOOR DOES NOT SELF CLOSE, LOCATED BTWEEN FIRST & CELLAR LEVEL, EXPOSURE #4., REPAIR/REPLACE DOOR; REPAIR AND/OR REPLACEHearing held — result not yet published
ECB03/27/2023AN ELEVATOR IN SECTION OF BUILDING OR BUILDING IS OUT-OF-SERVICE. UPON INSPECTION THE DEVICE IS FOUND TO BE OUT-OF-SERVICE CREATING A HAZARDOUS CONDITION AS PER 1RCNY 11-02. RESTORE TO SERVICE IMMEDIATELY AND NNothing owed — awaiting certificate of correction
ECB01/11/2023CLASS 1: RESTORE TO SERVICE REPAIR IMMEDIATELY AS PER 1RCNY 11-02. CALL NYCDOB FOR INSPECTON.Nothing owed — awaiting certificate of correction
ECB01/11/2023CLASS 1: 97.X.10 RESTORE TO SERVICE REPAIR IMMEDIATELY AS PER 1RCNY 11-02. CALL NYCDOB FOR INSPECTION.Nothing owed — awaiting certificate of correction
ECB10/31/202297X17,40P07,100M07:UPON INSPECTION DEVICE#5P56 IS FOUND TO BE OUT OF SERVICE CREATING A HAZARDOUS CONDITION AS PER 1RCNY 11-02. REMEDY RESTORE TO SERVICE IMMEDIATELY&NOTIFY NYCDOB THE DEVICE HAS BEEN RETURNED TNothing owed — awaiting certificate of correction
ECB10/31/202297X17,40P07,100M07:UPON INSPECTION DEVICE#5P55 IS FOUND TO BE OUT OF SERVICE CREATING A HAZARDOUS CONDITION AS PER 1RCNY 11-02. REMEDY RESTORE TO SERVICE IMMEDIATELY&NOTIFY NYCDOB THE DEVICE HAS BEEN RETURNED TNothing owed — awaiting certificate of correction
ECB05/11/2022ELECTRICAL PANEL ROOM THROUGHOUT THE BUILDING, FROM THE 6TH FLOOR TO THE FIRST FLOOR SEVERAL OPENINGS DUE PIPES/CABLES PENETRATION WITHOUT FIRE STOPPING PROVIDED., PROVIDE/MAINTAIN FIRE STOPPINGNothing owed — awaiting certificate of correction
ECB05/11/2022AT EXPOSURE # 2, ABOVE EXIT ROUTE, FIVE (5) WINDOW A/C UNITS WITHOUT SUPPORTS, REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB05/11/2022AT STAIR B FROM 1ST FL TO 6TH FL EXIT DOORS, AT 6TH FL LADIES RM DOOR, AND MAIN ENTRANCE DOOR ILLEGAL HARDWARE. DOORS DO NOT MEET TECHNICAL AND SAFETY STANDARDS WHEN WERE INSPECTED, REPAIR/REPLACE DOORNothing owed — awaiting certificate of correction
ECB05/11/2022ELECTRICAL PANEL ROOM THROUGHOUT THE BUILDING, FROM THE 6TH FL TO THE FIRST FL, ACOUSTIC CEILING, MISSING PANEL AND GENERAL DANAGES, REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB01/12/2022NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. FILE APPLICATION INSTALL DLM AND PERFORNothing owed — awaiting certificate of correction
ECB01/12/2022NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. FILE APPLICATION INSTALL DLM AND PERFORNothing owed — awaiting certificate of correction
ECB12/15/2021FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.I OBSERVED COMMERCIAL COOKING APPLIANCE NOT ON CASTER INSTALLED WITH COMMERCIAL GAS FLEK.FREE STANDING GAS APPLIANCE SHALL BE HARD PIPED ACCORDING TO THE FGNothing owed — awaiting certificate of correction
ECB10/15/2021BOILER NOT REGISTERED. REGISTER BOILERNothing owed — awaiting certificate of correction
ECB04/08/2020NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY; FILE APPLICATION, INSTALL DLM ANothing owed — awaiting certificate of correction
ECB04/08/2020NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY; FILE APPLICATION, INSTALL DLM ANothing owed — awaiting certificate of correction
ECB03/16/2020WORK WITHOUT A PERMIT. GET PERMITNothing owed — awaiting certificate of correction
ECB01/23/2020NOTED: EXTERIOR EXIT DOOR AT CELLAR STAR "A" REMAINS OPEN WHEN RELEASED AND DO NOT SELF CLOSE., REPAIR/REPLACE DOORNothing owed — awaiting certificate of correction
ECB01/23/2020I OBSERVED ON 01/21/20 AT THE ABOVE ADDRESS COMMERCIAL COOKING EQUIPMENT INSTALLED WITH COMMERCIAL GAS FLEX AND NOT CASTERS, AS MUST BE INSTALLED WITH RIGID PIPE PER FGC411.1., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB01/23/2020I OBSERVED AT THE ABOVE ADDRESS NEW SPRINKLER PIPING INSTALLED THROUGHOUT BUILDING FOR THE DRAIN DOWN RISER WITHOUT HAVING ANY PERMITS ON FILE AT THE DOB, OBTAIN ALL PERMITSNothing owed — awaiting certificate of correction
ECB10/22/2019(59BB10/42H11/64M7/56Y2/56Y13)(59)EXPIRED BRAKE MAINT TAG(44)FIX CONTACT ON DOOR OPEN AND BRAKE REPLACE(64)NYCID MISSING ON CONTROLLER AND HOIST MACHINE(56)HOIST MACHINE OIL LEAK,CLEAN AND SEAL.Nothing owed — awaiting certificate of correction
ECB10/22/2019(59BB10/42G7/42H11/58H10/64M7)59-EXPIRED BRAKE MAINT TAG.42-PROPERLY FUSE CONTROLLER(42)FIX CONTACTS ON DOOR OPEN AND BRAKE REPLACE(58)PLUGSIN(THRUST)BEARINGS(64)NYCID MISSING ON HOIST MACHINE.Nothing owed — awaiting certificate of correction
ECB03/29/2019FAILURE TO HAVE OR ALTERED PLUMBING SYSTEM TESTED. OBSERVED IN GAS METER ROOM WORK PERFORMED ON GAS SERVICE TO REPAIR LEAK THAT WAS NOT TESTED ON DOB RECORDS DO NOT SHOW ANY TEST HAVING BEEN PERFORMEDNothing owed — awaiting certificate of correction
ECB01/23/2019FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES NOTED: OBSERVED AT EXPOSURE ONE FRONT FACADE (RIGHT SIDE OF ENTRANCE)VERTICAL CRACKS THROUGH STONES FROM AROUND FLOOR UP TO THIRD FLOOR ALSO THE EXTERIORNothing owed — awaiting certificate of correction
ECB01/23/2019ALTERED/CHANGED BUILDING OCCUPIED W/O A VALID C OF O AS PER 28-118.3.1/28-118.3.2. NOTED:BUILDING OCCUPIED AS A HOMELESS SHELTER UNDER AN EXPIRED TEMPORARY C OF O, T.C.O#5P0003060 EXPIRED ON 12/26/97. REMEDY:OBNothing owed — awaiting certificate of correction
ECB03/29/2018WORK W/O PERMIT. OBSEVED IN STAIRWELLS PRESSURE GAUGES INSTALLED AT THE FLOOR CONTROL VALVES W/O A PERMIT. RMDY: OBTAIN ALL REQUIRED PERMITSPHOTOS TAKEN.Nothing owed — awaiting certificate of correction
ECB11/11/201797O2,17H11,10H11,56O2,56Y13,11L10,42T7. (97O)CAR DOWN ENTER DEVICE. (17H)REPLACE ALL HATCH DOOR GIBBS. (10H)REPLACE ALL CAR DOOR GIBBS. (56O)CLEAN OIL ON MACHINE. (56Y)SEAL OIL LEAK ON MACHINE. (71L)REPAIR LIGHNothing owed — awaiting certificate of correction
ECB11/11/201742T7,11L10,56Y13,56O2,10H11,17H11,97O2. (42T)PROVIDE COMPANY STICKERS & REMOVE OLD ONES. (11L)REPAIR LIGHTS ON CAR STATION BUTTONS. (56Y)SEAL OIL TANK ON MACHINE. (56O)CLEAN OIL ON MACHINE. (10H)REPLACE CAR DOONothing owed — awaiting certificate of correction
ECB09/11/2017FAIL TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.RE:INSTALLTATION/MAINTENANCE OF PLUMBING MATERIAL/EQUIPMENT PER PC 102.3;27-902.OBSERVED ON 9/11/17 AT ABOVE ADSDRESS BLACK MALLEABLE FITTINGS USED ON 1 INCHNothing owed — awaiting certificate of correction
ECB04/19/2017FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON EVERY FLOOR NO PRESSURE GAUGE INSTALLED ON INDIVIDUAL FLOOR ISOLATION MAINS ON THE AUTOMATIC FIRE SPRINKLER SYSTEM AS REQUIRED. RMDY:REPAIR AND/ORNothing owed — awaiting certificate of correction
ECB04/19/2017UNAPPROVED,UNSAFE,UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE. OBSERVED THROUGHOUT FACILITY: WATER FOUNTAIN RECEPTACLES THAT PROVIDE ELECTRICAL POWER TO UNITS ARE NOTNothing owed — awaiting certificate of correction
ECB10/24/2016ALTERED/CHANGED BLDG OCCUPIED W/O A VALID C OF O AS PER 28-118.3.1;28-118.3.2. NOTE: PREMISES OCCUPIED UNDER TEMPORARY C OF O #5P0003060 EXPIRED ON 11/18/17. REMEDY: OBTAIN VALID C OF O OR DISCONTINUE ILLEGALNothing owed — awaiting certificate of correction