ECB03/03/2026Work without a permit. Noted: at(basement) electric meter rm B7 with/installed of temp power/light lines under jon #M00721899-11-el exp 12/19/2024. Remedy: obtain permit.Nothing owed — awaiting certificate of correction
ECB03/03/2026Failure to maintain building in code-compliant manner. Lack of emergency lighting for exits, exit discharges and public corridors per bc 1006.1; 27-542. Noted: at(2ND fl) library rm 217 without provided/installNothing owed — awaiting certificate of correction
ECB03/03/2026Reissue ECB #35717451P. Exit door not self-closing noted: at(1ST fl) xxit 7 and 6, stair c hallway smoke door near rm 106, auditorium(2ND fl) stair a and b, hallway smoke door near rm's 208 and 232(3RD fl) staiNothing owed — awaiting certificate of correction
ECB03/03/2026Reissue ECB #35717450N. Failure to maintain building in code-compliantmanner. Illumination for exits, exits discharges and public corridors per bc 10061,; 27-381. Noted: at(1ST fl) cafeteria, auditorium(2ND fl)Nothing owed — awaiting certificate of correction
ECB03/03/2026Failure to maintain building in code-compliant manner. Noted: at(basement) gas meter rm B2 and electric meter rm 7 both rooms with multiple items of storage with desk, chairs, bags, etc... Remedy: comply with cNothing owed — awaiting certificate of correction
ECB03/03/202628-301.1. Reissue ECB #35717452R. Failure to provide ventilation to gas meter rm per P115.6(1968 code) fgc appendix e(E4)(2014 code). Noted:at(basement) rm B2 with no ventilation installed/provided. Remedy: comNothing owed — awaiting certificate of correction
ECB04/16/202528-301.1 failure to provide ventilation to gas meter room per P115.6(1968 code)fgc appendix e(E4)(2014 code).at the time of inspection observed & noted that no ventilation inside gas meter room need to provideNothing owed — awaiting certificate of correction
ECB04/16/2025Exit door not self closing properly at the time of inspection when tested.at the time of inspection i observed & noted at 1ST floor exit 5 outside two exit door and 1ST fl auditorium neer stage one exit door anNothing owed — awaiting certificate of correction
ECB04/16/2025Faiure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.at thetime of inspection observed and noted at 1ST floor auditorium 5 emergeNothing owed — awaiting certificate of correction
Likely answered · the city's own records show a filing, but DOB's feed still lists these as active
DOB09/23/2024Violation issued-failure to file 2023 external low pressure inspectionThe owner has filed since: boiler inspection reports are on file for later years (latest 2024). This one is not shown as answered2 identical filings