DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
ECB05/05/2026REISSUE ON ECB #35720957J. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: DUE TO DEFECTIVE ROOFING MATERIAL CAUSING PENETRATION TO TRAVEL TO CLASSROOM 302C 3RD FLOOR, TEACHERS LOUNGE 1ST FLOOR ANNothing owed — awaiting certificate of correction
ECB05/05/2026EXIT DOOR NOT SELF-CLOSING. NOTED: EMERGENCY EXTERIOR EXIT DOOR NOT SELF-CLOSING DUE TO BINDING MISSING AND/OR FAULTY HARDWARE ON EXTERIOR EXIT DOOR AT EXIT 7 1ST FL AND EXIT 10 1ST FL OBSERVED UPON INSPECTION.Nothing owed — awaiting certificate of correction
ECB05/05/2026REISSUE ON ECB #35688781H. FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES. NOTED: FOUNDATION WALL AT BASEMENT BOILER ROOM HAS BECOME POROUS ALLOWING WATER PENETRATION AT VARIOUS LOCATIONS OBSERVED UPON INSNothing owed — awaiting certificate of correction
ECB05/05/2026REISSUE ON ECB #35688780K. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDOSR PER BC 1006,1; 27-381. NOTED: EMERGENCY ILLUMINATED DISCHARGE EXITNothing owed — awaiting certificate of correction
ECB05/05/2026REISSUE ON ECB #356688782J. FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES. NOTED: VARIOUS STEP AND VERTICAL CRACKS WITH MISSING MORTARAT ALL EXPOSURES 1, 2, 3, 4, OF THE OCCUPIED BUILDING WITH SIDEWALK SHNothing owed — awaiting certificate of correction
ECB05/05/2026REISSUE ON ECB #35720958L. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: FIRE RATED CLASSROOMS AND SMOKE DOORS NOT SELF-CLOSING DUE TO BINDING, MISSING, AND ON FAULTY HARDWARE ON CLASSROOMS, 302Nothing owed — awaiting certificate of correction
ECB07/16/2025REISSUE#35688785P FAILURE TO MAITAIN BUILDING IN CODE COMPLIANT MANNER3RD FLOOR STORY AT 2ND FLOOR RM 213 NEXT TO 202.ALL HAVE BROKEN DOOR CLOSER.REM:COMPLY WITH CODE.Nothing owed — awaiting certificate of correction
ECB07/16/202528-301.1 REISSUE#35688783L FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.CEILING LEAK AT 3RD FLOOR CLASS 302C, 1ST FLOOR CAFETERIA AND TEACHERS CHANGE ALL THESE ROOM HAVE WATER DAMAGE.REM:COMPLY WITH CONothing owed — awaiting certificate of correction
ECB09/24/2024REISSUE#35672272N FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCESNOTED:AT CELLAR FOUNDATION WALLS HAS BECOME POROUS ALLOWING THE WATER INTO THE BOILER ROOM AT VARIOUS LOCATIONS.REM:MAINTAIN EXTERIOR WALL.Nothing owed — awaiting certificate of correction
ECB09/24/2024REISSUE #35672270J. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: CEILING LEAK AT 3RD FLOOR CLASS ROOM #302C, FIRST FLOOR CAFETERIA, AND TEACHER LOUNGE AREA DUE TO DEFECTIVE ROOF. REMEDY: MAKE NNothing owed — awaiting certificate of correction
ECB09/24/2024REISSUE#35672271L FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCESNOTED:AT EXP#1 BRICK FACADE WITH VERTICAL CRACK AT THE CORNER BY MAIN ENTRANCE AND FLAG POLE,STEP CRACK UNDER FIRST FLOOR WINDOW BY EXIT#1,MNothing owed — awaiting certificate of correction
ECB09/24/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AR 3RD FLOOR, STAIR "A" WITH BROKEN DOOR CLOSER, SECOND FLOOR CORRIDOR DOOR NEXT TO ROOM #213, AND NEXT TO ROOM #202, ALL HAS BROKEN DOOR CLOSERS. RNothing owed — awaiting certificate of correction
ECB09/24/2024REISSUE#35672273P FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:AT GYM 2 EMERGENCY EXIT LIGHTING,AT CAFETERIA 3 LIGNothing owed — awaiting certificate of correction
ECB06/22/2023REISSUE#35663145X FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER: ILLUMINATION FOR EXITS, EXIT DISCHARGES, AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED: OBSERVED AT VARIOUS LOCATIONS OF THE 1ST FLNothing owed — awaiting certificate of correction
ECB06/22/2023REISSUE #35663149NFAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED:OBSERVED AT ROOF LEVEL OF THE OCCUPIED SCHOOL BUILDING, ROOFING MATERIALHAS BECOME POROUS ALLOWING WATER TO PENETRATE DOWN INTO 3 FNothing owed — awaiting certificate of correction
ECB06/22/2023REISSUE#35665350YFAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTE:OBSERVED AT 3RD FL CLASSROOM #302C AND AT 1ST FL CAFETERIA, AND TEACHERS LOUNGE, CEILING IN STATE OF DISREPAIR DUE TO WATER PENETRATIONothing owed — awaiting certificate of correction
ECB06/22/2023REISSUE#35663146H FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTE: OBSERVED AT CELLAR LEVEL, BOILER ROOM FOUNDATION WALLS HAVE BECOME POROUS AND ALLOWING WATER TO PENETRATE AT VARIOUS LOCATIONS INTONothing owed — awaiting certificate of correction
ECB06/22/2023REISSUE #35663147J FAILURE TO MAINTAIN BUILDING WALL (S) OR APPURTENANCES. NOTE: OBSERVED AT VARIOUS LOCATIONS THROUGHOUT ALL 4 EXPOSURES OF THE OCCUPIED SCHOOL BUILDING, NUMEROUS STEP CRACKS, MISSING MORTAR BENothing owed — awaiting certificate of correction
ECB07/01/2022REISSUED#35577423X FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:OBSERVED EXISTING EMERGENCY LIGHTS LABELED#16,BY RNothing owed — awaiting certificate of correction
ECB07/01/2022REISSUED#35502401Z FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES:NOTED:OBSERVED AT EXPOSURE#1,AT EXIT#1,SPALLING CEMENT AT ENTRANCE DOOR OVERHANG,DIAGONAL CRACKS BY EXIT#1 RIGHT SIDE UNDER 1ST FLR WINDOWNothing owed — awaiting certificate of correction
ECB07/01/2022FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:NOTED:OBSERVED AT 3RD FLOOR,ROOM 302C,CEILINGS PLASTER IS DAMAGED DUE TO WATER PENETRATION,WATER BEING CAUGHT IN A WASTE BIN.REM:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB07/01/2022FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:NOTED:OBSERVED, ROOFING MATERIAL HAS BECOME POROUS ALLOWING WATER TO ENTER THE BUILDING INTO CLASSROOM#302C.REM:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB07/01/2022REISSUED#35577422Y FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES:NOTED OBSERVED FOUNDATION WALLS HAVE BECOME POROUS ALLOWING WATER TOPENETRATE INTO THE BOILER ROOM AREA AT VARIOUS LOCATIONS.REM:MAINTAINNothing owed — awaiting certificate of correction
ECB07/21/2021REISSUE#35501059H FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: DURING INSPECTION OBSERVED AT EXP#1-LIMESTONE OVER MAIN ENTRANCE EXIT#1 HAS CRACKS BETWEEN SLAB JOINTS DUE TO MISSING SEALENT,DIAGONALNothing owed — awaiting certificate of correction
ECB07/21/2021RE-ISSUE#35501063K FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. BOTED: DURING INSPECTION OBSERVED AT CELLAR LEVEL-BOILER ROOM FOUNDATIONWALL HAS STARTED TO BECOME POROUS AT SEVERAL LOCATIONS ALLOWING WATERNothing owed — awaiting certificate of correction
ECB07/21/2021REISSUE#35501062Z FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDOR PER BC1006.1;27-381. NOTED: DURING INSPECTION OBSERVED EXISTING EMERGENCY LIGHTS ATNothing owed — awaiting certificate of correction
ECB06/30/2020FAILURE TO MAINTAIN BUIDLING WALL(S) OR APPURTENANCES NOTED FOUNDATION WALLS HAVE BECOME POROUS ALLOWING WATER TO ENTER INTO THE BOILER ROOM AREA MAINTIN EXTRRIO BUILDING WALLNothing owed — awaiting certificate of correction
ECB06/30/2020FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES NOTED OBSERVED AT EXPOSURE 1, BRICK RETAINING WALL HAS VERTICAL CRACKS AT THE CORNERS BY MAIN ENTRANCE AND FLAG POLE FRAGONAL CRACKS UNDER FIRST FLOOR WINDONothing owed — awaiting certificate of correction
ECB06/30/2020FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDOR PER BC 1006.1;27-381 NOTED OBSERVED EXISTING EMERGENCY LIGHST AT STAIR"A" EXIT 9 AT EXIT 8 , EXINothing owed — awaiting certificate of correction