ECB08/06/2021Missing manual reset low water cut off asper FGC631.1/asme csd-failure to provide pipe insul.on heating/hw pipes per code mc 1204 ,remote control shutoff must be located outside boiler room doors mc 1006.8.1; fNothing owed — awaiting certificate of correction
ECB05/26/2021Missing remote control switch outside boiler room MC1006.8.1 missing clean out opening at base of chimney MC801.13 hydronic system piping shall be insulated MC1204.1; mc misc., comply with notice of violationNothing owed — awaiting certificate of correction
ECB07/08/2016B265,15,19B,32,38,4A,16,24B,36,34. As per class 2 (B265) 28-303.7 failure to file a complete boiler inspection report as per DOB records;50ANO discharge on relief valve; 50B-storage around boiler.submit a curreNothing owed — awaiting certificate of correction
Old · issued 3+ years ago and still listed by DOB; nothing on the city's records either way
DOB04/25/2023Violation issued-failure to file 2022 external low pressure inspectionIssued 2023; DOB's record still lists it as active2 identical filings
DOB01/17/2020Violation issued for failure to file annual boiler 2017 inspection reportIssued 2020; DOB's record still lists it as active2 identical filings