DOB08/31/2026FAILURE TO MAINTAIN BLDG. OBSERVED @ EXP 1, LONG VERTICAL CRACK ON COLUMN & MISSING MORTAR JOINTS. AT EXP 2, MISSING GLASS PANEL & SPALLING STUCCO @ PARAPET. AT EXP 3, LOOSE BRICK ON FIRST FLOOR WITH DAMAGED MORTAR JOINTS & SPALLING BRICKS. AT EXP 4, DAMAGED WINDOW SILL & SPALLING BRICK & LOOSE ROOF PANEL. REMEDY:REPAIR AND/OR REPLACE
ECB07/15/2026UNLAWFUL ACTS. FAILURE TO COMPLY WITH COMMISSIONER'S ORDER. AS NOTED RESPONDENT FAILURE TO COMPLY WITH PREVIOUSLY WRITTEN VIOLATION #35730079Y ON 04/30/2026, WHICH REQUIRES RESPONDENT TO PROVIDE ADEQUATE SAFETY$2K due
ECB04/30/2026FAILURE TO MAINTAIN PARKING STRUCTURE IN SAFE CONDITION. AT TIME OF INSPECTION ON AN OCCUPIED PARKING STRUCTURE CONSISTING OF 1 LEVEL BELOW BUILDING CELLAR LEVEL, OBSERVED CRACKED CONCRETE COLUMN/SPALLING BEAM$6K due
ECB11/21/2025UNLAWFUL ACTS. FAILURE TO COMPLY WITH COMMISSIONER'S ORDER FOR VIO 23-01716 DATED 04/26/2023. PREVIOUS SUMMONS 37025560J ISSUED FOR SAME CONDITIONS., COMPLY WITH COMMISSIONER'S ORDER$6K due
ECB11/21/2025FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MATTER. NOTED: IN GARAGE, CELLAR LEVEL LOAD BEARING BRICK AND MORTAR WALL IS MISSING JOINT MORTAR AND WATER LEAKS THROUGHOUT., REPAIR AND/REPLACE$3K due
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB11/10/2025FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. EXPOSURE 1 DEFLATED WINDOW LINTEL,CRACK COLUMN ON FIRST FLOOR. OPEN MORTAR JOINTS & CRACK CORNER OF EXP1&EXP4. EXP2 MISSING GLASS PANEL, CRACK AT PARAPET. EXP3, LOOSE BRICKS ON FIRST FLOOR EXIT. EXP4 LOOSE ROOF PANEL AND DAMAGED WINDOW SILLS. REMEDY: REPAIR AND/OR REPLACE
DOB03/05/2025FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
ECB12/05/2024FAILURE TO SUBMIT THE REQUIRED PARKING STRUCTURE INITIAL OBSERVATION REPORT FOR AN EXISTING PARKING STRUCTURE OR A PERIODIC INSPECTION OF A PARKING STRUCTURE(PIPS) REPORT DOCUMENTING THE CONDITIONS OF PSID#B000$2K due
DOB09/23/2024VIOLATION ISSUED-FAILURE TO FILE 2023 EXTERNAL LOW PRESSURE INSPECTION
DOB09/23/2024VIOLATION ISSUED-FAILURE TO FILE 2023 EXTERNAL LOW PRESSURE INSPECTION
DOB09/23/2024VIOLATION ISSUED-FAILURE TO FILE 2023 EXTERNAL LOW PRESSURE INSPECTION
ECB12/21/2023FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER IN DOB VIOLATION VIO23-01716,DATED 4/26/2023.RESPONDENT WAS REQUIRED TO SUBMIT AN ENGINEER'SREPORT CONCERNING STRUCTURALLY DEFICIENT CONDITIONS.AS OF 10/11/2023,A$12K due
DOB10/04/2023FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION
ECB06/29/2023SPALLING CONCRETE AT CELLAR WITH EXPOSED REBARS AT VARIOUS AREAS OF THE GARAGE. RUSTED METAL BEAMS,MISSING MORTAR BETWEEN BRICK JOINTS, PLUMBING LEAK THROUGHOUT THE PARKING GARAGE., REPAIR AND/REPLACE; MAKE NEC$6K due
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
DOB06/12/2023EXPSD&CORRDD CONC SLAB REINFORCMNT.W SPALLED CONC CVR ON ROOF.20'X40' APPROXIMTY,IN.FRONT SPRINKLR RM,EXPSD&CORRDD BEAMS,GIRDERS,MISSNG CONC ENCASMNT,WATER ISSUE CAUSED DAMAGES OBSERVD.PREVIOUS REPAIR,TEMP TARPS FAILED.REMEDY:IMMEDITE SHORE DOWN2CELLAR STRCTRLY COMPRO ELEMNTS UNDER NYS PE.SUBMIT S/S RPT W PHOTOS BY 5/15.ENSURE EGRESS PROTCTD.OVRHEAD
DOB05/24/2023EXPSD&CORRDD CONC SLAB W SPALLED CONC CVR ON ROOF,APPROXIMTY20'X40' IN FRONT SPRINKLR RM,BEAMS,GIRDERS,COLUMNS EXPSD,CORRDD.MISSNG CONC ENCASMNT,CRACKS,WATER ISSUE,REPAIRS&TEMP MEASURES FAILING RETAIN NYS RDP 2 PREPARE REPAIR PLAN 4 ALL DAMAGE.&STRUCTRL FILE RPR BY 7/28 & RPR WRK TO START BY PERMIT BY 8/25/23
DOB05/12/2023V-DOB VIOLATION - ACTIVE
DOB04/26/2023SPALLING CONCRETE AT CELLAR WITH EXPOSED REBARS AT VARIOUS AREAS OF THE GARAGE. RUSTED METAL BEAMS,MISSING MORTAR BETWEEN JOINTS,PLUMBING LEAK THROUGHOUT THE GARAGE.
DOB04/25/2023VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
DOB04/25/2023VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
DOB04/25/2023VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
DOB06/09/2021FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB11/08/2019VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
DOB11/08/2019VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
DOB11/08/2019VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
DOB04/30/2019FAILED TO FILE FISP CYCLE 8C TECHNICAL REPORT BY 02/21/2019
DOB04/06/2018VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2016 INSPECTION REPORT
DOB04/06/2018VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2016 INSPECTION REPORT
DOB04/06/2018VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2016 INSPECTION REPORT
ECB11/08/2017FAILURE TO FILE ANNUAL CERTIFICATION THAT COOLING TOWER 1000004843 HAS BEEN INSPECTED, TESTED & DISINFECTED & THAT A MAINTENANCE PLAN HAS BEEN DEVELOPED & IMPLEMENTED BY 11/1/2016. REM: FILE ANNUAL CERTIFICATIO$-216 due
ECB06/17/2017EXIT DOOR NOT SELF CLOSING. EXIT DOOR TO COMMON HALL. NOTED: FPSC DOOR NOT SELF CLOSING. REM: COMPLY W/ CODE.$-37 due
DOB02/24/2017VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2015 INSPECTION REPORT
DOB02/24/2017VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2015 INSPECTION REPORT
DOB02/24/2017VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2015 INSPECTION REPORT
DOB12/01/2016VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2015 INSPECTION/TEST
DOB12/01/2016VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2015 INSPECTION/TEST
DOB12/01/2016VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2015 INSPECTION/TEST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB08/05/2016V-DOB VIOLATION - ACTIVE
DOB05/30/2014VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
DOB05/30/2014VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
DOB05/30/2014VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
DOB10/01/2012VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2011 INSPECTION/TEST
DOB08/15/2012VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2010 CAT 1 INSP/TST
DOB03/21/2008V-DOB VIOLATION - ACTIVE
DOB10/01/2005V-DOB VIOLATION - ACTIVE
DOB11/19/2004V-DOB VIOLATION - ACTIVE
DOB02/19/2002V-DOB VIOLATION - ACTIVE
DOB03/08/2001V-DOB VIOLATION - ACTIVE
DOB03/10/2000V-DOB VIOLATION - ACTIVE
DOB01/20/1999V-DOB VIOLATION - ACTIVE
DOB07/25/1994V-DOB VIOLATION - ACTIVE
DOB07/25/1994V-DOB VIOLATION - ACTIVE
DOB05/31/1994V-DOB VIOLATION - ACTIVE
ECB05/11/2023FAILURE TO MAINTAIN BUILDING WALL(S)IN CODE COMPLIANT MANNER.NOTE:AT THE TIME OF INSPECTION OBSERVED AT EXPOSURE#1 NORTH ELEVATION AND EXPO#4 WEST ELEVATION(NEW YORK AVE)DETERIORATING MORTAR JOINT AT SEVERAL LONothing owed — awaiting certificate of correction
ECB05/07/2021FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.NOTED:ATOI I OBSERVEDON EXP1,3,4 CRACKS,DAMAGED MORTAR JOINTS;SPALLING BRICKS&MORTAR JOINTS.EXP3,SPALLING COPING;SPALLING BRICK&MORTAR JOINTS ON 5FL&SEVERAL OTHENothing owed — awaiting certificate of correction
ECB05/15/2017ALTERED/CHANGED BLDG OCCUPIED W/O A VALID COFO AS PER 28-118.3.1;28-118.3.2 OBSERVED DAYCARE CENTER IN OPERATION ON HERKIMER ST ENTRANCE AT 1ST FL.W/APPROX 20 STUDENTS AND 5 STAFF W/O VALID COFO#301925843T01THearing held — result not yet published
ECB07/21/2014FAIL TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.@ BASEMENT @ PUBLIC PARKING GARAGE,THERE IS A LARGE PILE OF RUBBLE @ CONST DEBRIS @ THE REAR OF GARAGE @ SUB CELLAR.REM:REMOVE DEBRIS.Nothing owed — awaiting certificate of correction
ECB12/20/2011ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY AS PER 28-118.3.1 & 28-118.3.2.NOTED: TCO#301925843T008 EXPIRED 09/10/11 & HAS NOT BEEN RENEWED. BUILDING IS FULLY OCCUPIED. REMEDY OBTNothing owed — awaiting certificate of correction
ECB12/04/2009FAIL TO MAINTAIN ILLUMINATION FOR EXITS SIGNS DEFECTIVE.REM:REPAIR/REPLACE EXIT SIGNSNothing owed — awaiting certificate of correction
ECB05/06/2008FAILED TO NOTIFY THE DOB PRIOR TO THE USE OR INSTALLATION OF "C" HOOKS OR OUTRIGGER BEAMS IN CONNECTION W/SUSPENDED SCAFFOLDS.Nothing owed — awaiting certificate of correction
ECB04/03/2008ALTERED BLDG OCCUPIED W/O A VALID C OF O. NOTE: JOB #301925843, ALT 1 HAS OBTAINED TEMPORARY C OF O #301925843T003, BLDG NOW OCCUPIED W/TCO EXPIRED 3/5/07 (TCO #301925843T003). REMEDY: OBTAIN VALID C OF O.Nothing owed — awaiting certificate of correction
ECB02/22/1995FAILURE TO FILE A REPORT OF COMPLIANCE WITH LOCAL LAW 16/84-CERTIFYINGTO THE INSTALLATION OF REQUIRED FIRE PROTECTIO SYSTEM. REMEDY-FILE REPORT.Nothing owed — awaiting certificate of correction
ECB10/31/1988OCCUPIED CONTRARY TO DEPT OF BUILDING RECORDS. FROM RESTAURANT TO BANK. REMEDY: FILE REQUIRED PLAN AND APPLICATION TO LEGALIZE PRESENT USE.Nothing owed — awaiting certificate of correction