ECB07/07/2026FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR. OBSERVED IN THE MAIN ELECTRICAL RM NO ELECTRODE GROUND ROD NOT INSTALLED THIS IS A SECOND MEANS OF GROUNDING FOR SERVICE EQUIPMENT. POTENTINAL SHOCK HAZARDS NECHearing held — result not yet published
ECB07/07/2026ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN THE REAR/ PARKING LOT A/C SPILT UNIT COMPRESSOR INSTALLED WITH ALUMINUM PIPE AND DISCONNECT SW. CHECKED BIS / DOB NOW NO PERMIT ON FILE. ALL WORK MUST BE FILLED BYNothing owed — awaiting certificate of correction
ECB07/07/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED STORAGE IN SPRINKLER ROOM. COMBUSTIBLE ITEMS (TV, COMPUTER, WOOD DESK) POTENTIAL HAZRDS., REPAIR AND/OR REPLACEHearing held — result not yet published
ECB07/07/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ATOI OBSERVED THROUGH OUT BUILDING OBSTRUCTED SPRINKLER HEADS AND IN BASEMENT THE USE OF PVC AND PEX PIPING CONTRARY TO BC 903.3.3, PC 605.9 & PC 1101.10 AHearing held — result not yet published$2K proposed
ECB07/07/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED WOOD PANELS AS WALLS, WHICH ARE NOT FIRE RATED INSIDE OF THE SPRINKLER ROOM. POTENTIAL FIRE HAZARD., REPAIR AND/REPLACEHearing held — result not yet published$2K proposed
ECB07/07/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. EXIT DOOR HAS ILLEGAL HARDWARE, PREVENT PERSONAL FROM OPENING DOOR BOTH WAYS. POTENTIAL HAZARD., REPAIR AND/REPLACEHearing held — result not yet published$2K proposed
ECB07/07/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED CONVEYOR BELT OBSTRUCTING STAIRCASE LEADING FROM BASEMENT. POTENTIAL HAZARD., REPAIR AND/REPLACEHearing held — result not yet published$2K proposed