HPD01/22/2022§ 27-2005, 2007, 204.1 HMC CODE: ARRANGE AND MAKE SELF-CLOSING THE DOORS AT BUILDING ENTRANCE AT PUBLIC HALL, 1st STORY
HPD01/22/2022§ 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING.
HPD01/22/2022§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 1, APARTMENT AT WEST
HPD01/22/2022§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 4th ROOM FROM NORTH AT WEST LOCATED AT APT 1, APARTMENT AT WEST
HPD01/22/2022§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE AT THE ENTRANCE LOCATED AT BSMT-APT 1, BSMT-APT AT WEST
HPD01/22/2022§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE 4th ROOM FROM NORTH AT WEST LOCATED AT BSMT-APT 1, BSMT-APT AT WEST
HPD01/22/2022§ 185, 240 M/D LAW PROPERLY FIRE RETARD IN ACCORDANCE WITH THE RULES AND REGULATIONS OF THIS DEPARTMENT THE CELLAR CEILING
HPD01/22/2022§ 27-2050 ADM CODE SEAL IN OPEN POSITION THE O.S.Y. VALVE OF THE SPRINKLER SYSTEM IN ACCORDANCE WITH THE RULES AND REGULATIONS OF THIS DEPARTMENT AT CELLAR FRONT
HPD01/22/2022§ 27-2050 ADM CODE PROVIDE 3 EXTRA SPRINKLER HEADS AND SUITABLE WRENCH FOR EMERGENCY PURPOSES AT O.S.Y. VALVE OF SPRINKLER IN ACCORDANCE WITH THE RULES AND REGULATIONS OF THIS DEPARTMENT AT CELLAR
HPD01/22/2022§ 27-2005 ADM CODE REFIT ENTRANCE DOOR AT BOILER ROOM, CELLAR
HPD01/22/2022§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT SOFFIT ABOVE PUBLIC HALL STAIRS, CELLAR
HPD01/22/2022§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD. AT PUBLIC HALL, 1st STORY
HPD01/22/2022§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR (MISSING) AT PUBLIC HALL, 1st STORY
HPD01/22/2022§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX (MISSING) AT PUBLIC HALL, 1st STORY
HPD01/22/2022§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY
HPD01/22/2022§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE BATHROOM LOCATED AT BSMT-APT 1, BSMT-APT AT WEST
HPD01/22/2022§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF ELECTRICAL WIRES AND BOX CABLES AT CEILING, THROUGH-OUT CELLAR
HPD11/04/2018§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CEILING IN THE 4th ROOM FROM NORTH LOCATED AT BSMT-APT 1
HPD11/04/2018§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE BATHROOM LOCATED AT BSMT-APT 1
HPD11/04/2018§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT BSMT-APT 1
HPD11/04/2018§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING, WEST WALL, NORTH WALL AND AROUND WEST WINDOW CASING IN THE 4th ROOM FROM NORTH LOCATED AT BSMT-APT 1
HPD11/04/2018§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT BSMT-APT 1
HPD11/04/2018§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CEILING IN THE BATHROOM LOCATED AT BSMT-APT 1
HPD06/12/2006SECTION 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT .... NORTH WALL IN THE BATHROOM LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD06/12/2006SECTION 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD06/12/2006SECTION 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY ?11-06(B)(2) 1st WINDOW FRAME FROM WEST AT NORTH WALL, 2nd WINDOW FRAME FROM WEST AT NORTH WALL, 3rd WINDOW FRAME FROM WEST AT NORTH WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD06/12/2006SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ... CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD06/12/2006SECTION 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ... 1st DOOR FRAME FROM EAST AT SOUTH WALL IN THE 4th ROOM FROM NORTH LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD06/12/2006SECTION 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT .... NORTH WALL IN THE FOYER LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD04/04/2005SECTION 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 3FL, 3rd STORY
HPD04/04/2005SECTION 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE PAVING BUILDING ENTRANCE YARD YARD
HPD04/20/2004SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE FOYER LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD04/20/2004SECTION 27-2005 ADM CODE REPLACE WITH NEW THE MISSING LOCKING DEVICE AT DOOR TO THE BALCONY IN THE 2nd ROOM FROM NORTH LOCATED AT APT 3, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD04/20/2004SECTION 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CEMENT FLOOR IN THE 2nd ROOM FROM NORTH LOCATED AT APT 3, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD04/20/2004SECTION 27-2018 ADM CODE ABATE THE NUISANCE CONSISTING OF VERMIN ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD04/20/2004SECTION 27-2018 ADM CODE ABATE THE NUISANCE CONSISTING OF VERMIN MICE IN THE ENTIRE APARTMENT LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD04/20/2004SECTION 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE WOOD FRAME AT NORTH WINDOWS IN THE 1st ROOM FROM NORTH LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD10/14/2003SECTION 27-2050 ADM CODE PROVIDE A PIECE OF GARDEN HOSE 10 FEET IN LENGTH WITH FEMALE COUPLING AND A 10 QUART PAIL ON PREMISES TO TEST SPRINKLER SYSTEM. AT PUBLIC HALL, 4th STORY
HPD10/14/2003SECTION 27-2050 ADM CODE SEAL IN OPEN POSITION THE O.S.Y. VALVE OF THE SPRINKLER SYSTEM IN ACCORDANCE WITH THE RULES AND REGULATIONS OF THIS DEPARTMENT .. AT OPEN SPACE, CELLAR
HPD10/14/2003SECTION 27-2005 ADM CODE REPLACE WITH NEW THE MISSING BANISTER AND BALUSTERS MISSING 4TH STORY BESIDE SCUTTLE LADDER
HPD10/14/2003SECTION 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE BALCONY DOOR IN THE 1st ROOM FROM NORTH LOCATED AT APT 3, 3rd STORY, APARTMENT AT WEST
HPD10/14/2003SECTION 27-2005 ADM CODE REPLACE WITH NEW THE MISSING WINDOW LOCKS IN THE ENTIRE APARTMENT LOCATED AT APT 3, 3rd STORY, APARTMENT AT WEST
HPD10/14/2003SECTION 27-2018 ADM CODE ABATE THE NUISANCE CONSISTING OF VERMIN MICE IN THE ENTIRE APARTMENT LOCATED AT APT 3, 3rd STORY, APARTMENT AT WEST
HPD10/14/2003SECTION 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING KEY OPERATED DOUBLE CYLINDER LOCK TO STREET ENTRANCE DOOR TO VESTIBULE 1STORY
HPD10/14/2003SECTION 27-2005, 2007 ADM CODE FIRE EGRESS DEFECTIVE. MAKE STATIONARY THE IRON LADDER LEADING TO SCUTTLE OPENING IN ROOF ... AT PUBLIC HALL
HPD10/14/2003SECTION 27-2050 ADM CODE PROVIDE 3 EXTRA SPRINKLER HEADS AND SUITABLE WRENCH FOR EMERGENCY PURPOSES AT O.S.Y. VALVE OF SPRINKLER IN ACCORDANCE WITH THE RULES AND REGULATIONS OF THIS DEPARTMENT .. AT OPEN SPACE, BASEMENT