DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB02/01/1995V-DOB VIOLATION - ACTIVE
DOB02/01/1995V-DOB VIOLATION - ACTIVE
DOB02/01/1995V-DOB VIOLATION - ACTIVE
ECB05/26/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:MISSING CHUNKS OF CONCRETE ON RISER STEPS AND MISSING NON SLIP DIAMOND TREAD PLATES ON EXTERIOR WALKWAY STEPS OBSERVED CONED OFF UPON INSPECTION.REM:RNothing owed — awaiting certificate of correction
ECB05/26/2026REISSUE ON ECB#35725404M FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE);FSC APPENDIX E(E4)(2014 CODE).NOTED:AT CELLAR LEVEL AT GAS METER ROOM REMAINS WITHOUT VENTILATION OR FRESH AIR INTNothing owed — awaiting certificate of correction
ECB05/26/2026REISSUED ON ECB#35725403K FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:FIRE RATED CLASSROOMS AND SMOKE DOORS NOT SELF-CLOSINGDUE TO BINDING,MISSING AND OR FAULTY HARDWARE ON CLASSROOMS 501,502,30Nothing owed — awaiting certificate of correction
ECB05/26/2026REISSUE ON ECB#35725405Y FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT KITCHEN WITH COMMERCIAL GAS STOVE WITHOUT AN ANSUL OR A FIRE SUPPRESSION SYSTEM OBSERVED UPON INSPECTION.REM:REPAIR AND/ORNothing owed — awaiting certificate of correction
ECB05/26/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NO FIRESTOPPING PER BC 712.3;27-345.NOTED:MISSING FIRESTOPPING IN GAS METER ROOM ON ONE LARGE SECTION OF CMU BLOCK ABOVE ENTRANCE APPROXIMATELY 2FT X 3FT OBNothing owed — awaiting certificate of correction
ECB10/23/202528-301.1. REISSUE #35692557P DATE OF ISSUE: 10-24-2024. FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE) FGC APPENDIX E(E4)(2014 CODE) . AT THE TIME OF INSPECTION OBSERVED AND NOTED AT CELNothing owed — awaiting certificate of correction
ECB10/23/2025REISSUE #35692556N DATE OF ISSUE: 10-14-2024. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AND OBSERVED AT KITCHEN HAS A COMMERCIAL GAS STOVE IN THAT PLACE WITHOUT AN ANSUL SYSTEM. REMEDY: REPAINothing owed — awaiting certificate of correction
ECB10/23/2025REISSUE #35692558R DATE OF ISSUE: 10-24-2024. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED, DEFECTIVE HARDWARE ON INTERIOR FPSC DOORS MISSING DOOR CLOSURENothing owed — awaiting certificate of correction
ECB10/20/2025FEDERAL BOILER HAS #3 KING VALVE LEAKING WATER ONTO OIL BURNER+VAC SYSTEM PUMP+FLOAT SWITCH BOTH LEAKING WATER+OIL SHUTOFF VALVE IS MISSING@TOP OF OIL TANK;CORRECT VIOLATION+SUBMIT CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB10/24/2024REISSUE #35663488H. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: KITCHEN HAS A COMMERCIAL GAS STOVE IN PLACE WITHOUT AN ANSUL SYSTEM. REMEDY: REPAIR/REPLACE. PROVIDE ANSUL SYSTEM.Nothing owed — awaiting certificate of correction
ECB10/24/202428-301.1 REISSUE #35663487X. FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE), FGC APPENDIX E(E4)(2014 CODE). NOTED ATCELLAR LEVEL GASMETER ROOM, NO FRESH AIR VENTILATION PROVIDED. REMEDY:Nothing owed — awaiting certificate of correction
ECB10/24/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: INTERIORFPSC DOORS MISSING CLOSURES OR RACHED AT RM #303B, 303C, 313C, 313E, 313G, 309 SMOKE DOOR, 309B, 309C, 200X, 203A, 203C. MENTIONED DOORS ARNothing owed — awaiting certificate of correction
ECB08/15/2023REISSUE: 35655436X FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. COMMERCIAL GAS STOVE IN PLACE WITHOUT AN ANSUL SYSTEM. REMEDY: REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB08/15/2023REISSUE: 35655437H MISCELLANEOUS VIOLATIONS CELLAR LEVEL GAS METER ROOM NO FRESH AIR INTAKE VENT. REMEDY: COMPLY WITH CODENothing owed — awaiting certificate of correction
ECB06/09/2022REISSUE#35561264L FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:OBSERVED IN 1ST FLR KITCHEN,COMMERCIAL GAS STOVE IN PLACE WITHOUT A ANSUL SYSTEM.REM:REPAIR AND/OR REPLACE,INSTALL ANSUL SYSTEM.Nothing owed — awaiting certificate of correction
ECB06/09/202228-301.1 REISSUE#35561262H FAILURE TO PROVIDE VENTILATION TO GAS METERROOM PER P115.6(1968 CODE),FGC APPENDIX E(E4)(2014 CODE).NOTED:OBSERVED AT BASEMENT LEVEL-GAS METER ROOM DOES NOT HAVE MECHANICAL OR NATURALNothing owed — awaiting certificate of correction
ECB12/13/2021MISSING BOLTS & DOGS ON FRONT & REAR DOORS ON BOILER,OIL LEAK AT BURNER,MISSING WISKA SWITCH FOR COMBUSTION AIR,VACUUM PUMP LEAKINGNothing owed — awaiting certificate of correction
ECB11/17/2021MISSING BOLTS & DOGS ON FRONT & REAR DOORS OF BOILER,OIL LEAK AT BURNER,MISSING WISKA SWITCH FOR COMBUSTION AIR LOUVER,VACUUM PUMP LEAKINGNothing owed — awaiting certificate of correction
ECB05/11/2021SEC. 28-301.1 REISSUE#35495211P FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE),F6C APPENDIX E (E4)(2014 CODE)OBSERVED: AT BASEMENT,GAS METER ROOM DOES NOT HAVE MECHANICAL OR NATURAL VENTNothing owed — awaiting certificate of correction
ECB05/11/2021VIOLATION REISSUE#35495212R FAILURE TO MAINTAIN BLDG IN CODE COMPLIANTMANNER: OBSERVED: 1ST FL KITCHEN AREA COMMERCIAL GAS STOVE W/O ANSUAL SYSTEM. REMEDY: REPAIR &/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB05/26/2020FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: AT KITCHEN AREA,COMMERCIAL GAS STOVE W/NO ANSUL SYSTEM. REMEDY: PROVIDE ANSUL SYSTEM TO COMMERCIAL GAS STOVE.Nothing owed — awaiting certificate of correction
ECB05/26/2020SEC. 28-301.1 RESSIE#35433665X FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER PH5.5(1968 CODE);FGC APPENDIX E(E4)2014 CODE. NOTED: AT GAS METER ROOM NO FRESH AIR VENTILATION PROVIDED. REMEDY: COMPLY WITHNothing owed — awaiting certificate of correction
ECB06/20/2019SEC. 28-301.1 FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER 115.6 FGC APPENDIX E(E4)NOTED: AT CELLAR GAS METER ROOM W/NO FRESH AIR INTAKE/VENTILATION SYSTEM. REMEDY: COMPLY W/NOTICE OF VIOLATION.Nothing owed — awaiting certificate of correction
ECB01/11/2016BC3307.6.5 FAILURE TO MAINTAIN SIDEWALK SHED AS REQUIRED BY CODE.NOTEDSIDEWALK SHED ERECTED AS PER JOB#402892553 ALONG EXP1 HAS INOPERABLE 4BULBS RENDERING AFFECTED AREA VISIBLY DARK CREATING POTENTIAL RISK REMNothing owed — awaiting certificate of correction
ECB07/30/2015REISSUE 35028670L FAILURE TO PROVIDE FRESH AIR INLET PER 27-766.NOTED @ CELLAR GAS METER ROOM,NO FRESH AIR INLET.REM COMPLY W/ NOVNothing owed — awaiting certificate of correction
ECB07/29/201327-766 - REISSUE 34981448K NO FRESH AIR INTAKE AT CELLAR GAS METER ROOM. RMDY: PROVIDE FRESH AIR INTAKE.Nothing owed — awaiting certificate of correction
ECB06/27/201227-766 REISSUE #34921937R NO FRESH AIR INLET AT CELLAR GAS METER ROOM NO FRESH AIR INLET REM: FRESH AIR INLET REM: PROVIDE FRESH AIR INLETNothing owed — awaiting certificate of correction
ECB07/29/2011THE GAS METER ROOM IS LACKING FRESH AIR VENTILATION IN THE CELLAR LEVEL. REMEDY: PROVIDE/MAINTAIN FRESH AIR VENTILATION.Nothing owed — awaiting certificate of correction