ECB08/13/2026AT THE TIME OF INSPECTION OBSERVED ON THE ROOF ON THE COOLING TOWER UNIT A CRACKED VALVE ALSO PIPE CONNECTION MADE WITH FERNCO COUPLES . MC 908.1 - COOLING TOWERS: COOLING TOWERS SHALL BE INSTALLED IN ACCORDANC$2K due
ECB08/13/2026ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN THE BASEMENT 4 NEW 200 AMP DISCONNECT SW AND 1 1600 AMP DISTRIBUTION INSTALLED WITH BX RISERS. ALSO IN LOBBY AND BASEMENT HUNG ELECTRIC HEATERS INSTALLED WITH BX AN$2K due
ECB08/13/2026UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERVED IN THE MAIN LOBBY AND BACK STORAGE AREA EXPOSED BX AND SJ CORD FEEDING HUNG HEATERS SJ COR$2K due
ECB08/13/2026UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES. OBSERVED THRU OUT HALLWAYS AND CHILDREN PLAY ROOM NO INSTALLATION OF TAMPER RESISTANT RECEPTACLES AND IN THE MECHANICAL RMS NO G$2K due
ECB08/13/2026AT THE TIME OF INSPECTION OBSERVED THROUGHOUT THE BUILDING, MULTIPLE AUTOMATIC SPRINKLER HEADS WERE OBSERVED OBSTRUCTED. MULTIPLE SPRINKLER HEADS WERE OBSERVED WITH THEIR ESCUTCHEONS/CAPS PAINTED AND OR MISSING$2K due
ECB08/13/2026CLASS 1: 1. DLM MALFUNCTIONING AND NOT PROVIDING REQUIRED DOOR LOCK MONITORING. AS PER ASME A17.1 2.12. REMEDY: REPAIR DLM TO RESTORE PROPER MONITORING. CLASS 2: 2. CAR PRODUCES WHISTLING NOISE WHILE TRAVELING.$1K due
ECB08/13/2026CLASS 1 C/U: 1. COMPENSATION CHAIN DRAGGING ON PIT FLOOR, CREATING HAZARDOUS INTERFERENCE WITH PIT EQUIPMENT. AS PER ASME A17.1 2.2. REMEDY: ADJUST AND SECURE COMPENSATION CHAIN TO MAINTAIN COMPLIANT FLOOR CLEA$1K due
HPD04/29/2026(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
HPD11/17/2025§27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID REGISTRATION STATEMENT IS FILED.
ECB08/05/2025FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH SECTION. OBSERVED NO SECONDARY GROUNDING ELECTRODE. LOCATED IN WATERMAIN ROOM AND THROUGHOUT ELECTRIAL ROOMS., PROPERLY INSTALL GROUND ELECTRO$12K due
HPD01/12/2024§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF SCALDING HOT WATER EXCEEDING THE MAXIMUM ALLOW TEMPERATURE OF 130 DEGREES IN THE ENTIRE APARTMENT LOCATED AT APT 1521, 15th STORY, 2nd APARTMENT FROM EAST AT SOUTH
HPD11/29/2023§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF HOT WATER TEMPERATURE OF 158 DEGREES; EXCEEDING THE MAXIMUM ALLOWABLE TEMPERATURE OF 130 DEGREES IN THE ENTIRE APARTMENT LOCATED AT APT 1208, 12th STORY, 1st APARTMENT FROM EAST AT SOUTH
HPD11/08/2023§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF HOT WATER EXCEEDING THE MAXIMUM TEMPERATURE OF TEMPERATURE 130 DEGREES AT PLUMBING FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 1607, 16th STORY, 1st APARTMENT FROM WEST AT NORTH
DOB02/22/2022FAILED TO FILE FISP CYCLE 9A TECHNICAL REPORT BY 02/21/2022
DOB02/17/2017V-DOB VIOLATION - ACTIVE
DOB01/31/2013FAILED TO FILE FISP CYCLE 7A TECHNICAL REPORT BY 02/21/2012
DOB09/12/1997VP-VIOLATION UNSERVED ECB-ACTIVE