ECB04/28/2026REISSUE#35717408J AT THE TIME OF INSPECTION,THE FOLLOWING ELECTRICAL METER ROOM HAS OPENING AT CEILING/WALL WERE THE CLUSTER OF PIPES ARE THGAS METER ROOM HAD PENETRATION OPEN AT CEILING.BOTH ELECTRICAL METER RNothing owed — awaiting certificate of correction
ECB04/28/2026REISSUE#35072839P AT THE TIME OF INSPECTION,THE FOLLOWING DOORS WERE NOT SELF-CLOSING CORRIDOR DOORS NEXT STAIRCASE H ON 4TH FLOOR,457,401,409,351,333,CORRIDOR DOOR NEXT TO 248,253,209 DOOR FROM 2ND FLOOR GYM SNothing owed — awaiting certificate of correction
ECB04/28/202628-301.1 UNLAWFUL DISPLAY OF ARTWORK IN CORRIDORS GREATER THAN 20% PERFDNY 2008 CODE;FC 803.3.2.AT THE TIME OF INSPECTION,6TH FLOOR CORRIDORNEAR ROOM 443 HAD EXCESSIVE ARTWORK IN EXCESS OF 20% AS PERMITTED.REM:Nothing owed — awaiting certificate of correction
ECB04/28/2026REISSUE#35717407H AT THE TIME OF INSPECTION,THE FOLLOWING EMERGENCY LIGHTS WERE INOPERABLE LIGHT IN STAIRWELL H BY 3RD FLOOR LIGHTS IN STAIRWELL A ON 3RD/2ND FLOOR LIGHT IN STAIRWELL 4 ON 2ND FLOOR ALL EMERGENCNothing owed — awaiting certificate of correction
ECB04/28/2026REISSUE#35717409L AT THE TIME OF INSPECTION CRACKS WERE ON CORRIDOR WALL AT ROOM 315,THERE WAS EFFLORESCENCE IN STAIRCASE H ON 4TH FLOOR ROOM 301 HAS WATER STAIN IN CEILING ROOM 259 HAD BROKEN GLASS PANEL 2ND,3Nothing owed — awaiting certificate of correction
ECB04/28/2026REISSUE#35717410Z AT THE TIME OF INSPECTION,THE FOLLOWING EXIT DISCHARGE DOORS WERE NOT SELF-CLOSING #9,#5 FRAME WAS FALLING OFF.REM:REPAIR/REPLACE DOOR.Nothing owed — awaiting certificate of correction
ECB06/02/2025REISSUE #35672837L: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE-STOPPING FOR BC 712.3; 27-543. AT ELECTRICAL ROOM IN CELLAR LEVEL REAR ENTRANCE DOOR LARGE OPENING SURROUNDING CONDUIT PIPES WINothing owed — awaiting certificate of correction
ECB06/02/2025REISSUE #35677520X: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER 1006,1; 27-381. EXISTING EMERGENCY LIGHT(S) ARE NOT OPERATIONAL WHEN TNothing owed — awaiting certificate of correction
ECB06/02/2025REISSUE #35672840M: EXIT DOOR NOT SELF-CLOSING AT MAIN EXIT 7, EXIT 8(KITCHEN) NOT CLOSE PROPERLY WHEN TESTED. REMEDY: REPAIR AND/OR REPLACEDOOR(S).Nothing owed — awaiting certificate of correction
ECB06/02/2025REISSUE #35672843H; FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: AT 3RD FLOOR LESS OF ROOM HORIZONTAL CRACKS WITH LOOSE/MISSING MORTAR ARE GLAZE SURFACE CMU INTERIOR BLOCK WALLS. REMEDY: REPAIR AND/ORNothing owed — awaiting certificate of correction
ECB05/03/2024REISSUE#35672841Y FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.AT TIME OF MY INSPECTION I OBSERVED AT 3RD FLOOR STAIRWELNothing owed — awaiting certificate of correction
ECB03/14/2023FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.ILLUMINATION FOR EXIT,EXIT DISCHARGES & PUBLIC CORRIDORS PER BC 1006.1; 27-381.NOTED:AT 3RD FL STAIRWELL A, 2ND FL GYNASIUM,STAIRWELL B, H, 1ST FL STAIRWELLNothing owed — awaiting certificate of correction
ECB03/14/2023EXIT DOOR NOT SELF-CLOSING.NOTED:EXTERIOR DOOR AT MAIN ENTRANCE TO BUILDING EXIT 7, & KITCHEN EXIT 8 NOT WORKING PROPERLY.REMEDY:REPAIR/REPLACE DOORNothing owed — awaiting certificate of correction
ECB03/14/2023FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT 4TH FL CORRIDOR BY STAIR H,ROOM 449, 3RD FL CORRIDOR BY STAIR F,G & H, ROOM 307,309,322(LIBRARY)ENTRANCE,RIGHT ROOM INSIDE 322,2ND FL ROOM 205,209Nothing owed — awaiting certificate of correction
ECB03/14/2023FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT RIGHT SIDE OF EXP #2 NEAR 3RD FL LEVEL HAS LOOSE & MISSING MORTAR IN VARIOUS AREAS THROUGHOUT.BRICK MISSING AT GROUND LEVEL OUTSIDE EXIT 4.REMEDY:RNothing owed — awaiting certificate of correction
ECB03/14/2023REISSUE #35650744P NOTED:AT CELLAR LEVEL ELECTRICAL METER ROOM,LARGE HOLES ABOVE ENTRANCE DOOR FROM CONDUITS IN VARIOUS AREAS.REMEDY:PROVIDE/MAINATAIN FIRE STOPPING.Nothing owed — awaiting certificate of correction
ECB03/14/2023REISSUE #35650743N NOTED:AT 3RD FL CORRIDOR BY RM 315, RIGHT SIDE OF STAIR H & 2ND FL ADJACENT TO RM 228*(WHITE CMU BLOCKWALL) ALL HAVE CRACKS AND/OR STEP CRACKS IN VARIOUS AREAS.REMEDY:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB04/14/2022REISSUE#35557930M 4/12/2021.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NO FIRE STOPPING PRE BC712.3;27-345 AT ELECTRICAL ROOM IN BASEMENT EMERGENCY LIGHT CONDUIT PENETRATED WALL WITH NO FIRE STOPPINGNothing owed — awaiting certificate of correction
ECB04/14/2022REISSUE#35557931Y 4/12/2021.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.AT 3RD FLOOR CORRIDOR BY ROOM 315,4TH FLOOR BY ROOM 424 LARGE STEP PATTERN CRACKS ON CMU BLOCK WALLS.REMEDY:COMPLY WITH CODE.Nothing owed — awaiting certificate of correction
ECB04/12/2021REISSUE#35486745P FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER MISSING EMERGENCY LIGHTING AT 1ST FL EXITS ALSO PIPE PENTRATION AT BASEMENT ELECTRICAL ROOM DOES NOT HAVE ADEQUATE FIRE STOPPING.Nothing owed — awaiting certificate of correction
ECB04/12/2021REISSUE#35486744N FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. AT TIME OF INSPECTION NOTED: AT 3RD FL CORRIDOR OUTSIDE OF ROOM#315,12 FOOT STEP CRACK IN C.M.U. BLOCK WALL. REMEDY: COMPLY WITH CODE.Nothing owed — awaiting certificate of correction
ECB03/27/2020REISSUE#35235629L FAILURE TO MAINTAIN BUILDING WALLS/OR APPURETNANCES RM 315 HORIZONTAL CRACK ON WALL CORRIDOR MAINTAIN BUILDING WALLSNothing owed — awaiting certificate of correction
ECB03/27/2020FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER LACK OF EMERGENCY LIGHTING FOR EXITS ,EXIT DISCHARGES AND PUBLCI CORRIDOR PER BC 7.2.3;27-345 ELECTRICAL HAS PIPES PENETRATUBF WALL WITH NO FIRESTOPPING REPNothing owed — awaiting certificate of correction
ECB03/08/2018REISSUE#35235629L FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: STEPS CRACK IN THE WALL AT 3RD FL OUTSIDE RM#315 & AT 4TH FL ADJACENT TO RM#424 AT CORRIDOR. REMEDY: COMPLY W/CODE/REPAIR THE WALLS.Nothing owed — awaiting certificate of correction
ECB04/05/2017FAILURE TO MAINTAIN BUUILDING WLLS OR APPURTENANCES.NOTED AT 3RD FLR REAR OF ROOM 315 HORIZONTAL CRACK ON WALL 1/4"GAP.REM:MAINTAIN BUILDINGWALLS(EXTERIOR-INTERIOR).Nothing owed — awaiting certificate of correction