ECB03/20/2026ONLY ELEVATOR IN A MULTIPLE DWELLING OUT OF SERVICE. THIS CONDITION AFFECTS NUMEROUS TENANTS, INCLUDING THOSE WITH SPECIAL NEEDS, THEREBY CREATING A CONDITION DANGEROUS TO HUMAN LIFE.$6K due
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB09/23/2024VIOLATION ISSUED-FAILURE TO FILE 2023 EXTERNAL LOW PRESSURE INSPECTION
ECB04/12/2024FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. TOP OF THE CAR DIRTY, CLEAN. PIT DIRTY, CLEAN. IN CAR COMMUNICATION INOPERATIVE, REPAIR. DOOR GIBS WORN, REPLACE WHERE NECESSARY. LIGHT MISSING ON TOP OF T$6K due
ECB08/18/20232:X:10; IN-CAR COMMUNICATION NOT WORKING, NEED TO REPAIR. 8:V:1; CAR SADDLE TO FLOOR SILLS OFF LEVEL, NEED TO ADJUST. 32:H:10; CAR SHOES ARE WORN. ELEVATOR CAB SHIFTS ABOUT 2 INCHES SIDE TO SIDE, THEY NEED TO B$6K due
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
ECB07/21/2022PROVIDE IN-CASE OF FIRE SIGNS ON ALL FLOORS., REPAIR IN-CAR EMERGENCY PHONE., PROVIDE IN-CAR LIGHT GUARDS., RESTORE SERVICE TO BASEMENT., CLEAN OR REPLACE HOIST-WAY ROPES. REMOVE ITEMS BLOCKING ELEVATOR ENTRANC$625 due
ECB05/21/2021FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER AT THE TIME OF MY INSPECTION THE ENTIRE ROOF AREA AT REAR WAS OBSERVED UNCOVERED LEAVING WOODEN STRUTCURAL MEMBERS EXPOSED RESIDENTIAL UNITS ARE LOCATED$6K due
DOB05/13/2021FTM BLDG SAFE CONDN:FIRE ESC @EXP3 WAS IN DISREPR W/MISSING PORTNS OF ENCLOSURE PEELING PAINT,PERSONAL EFFECTS & DEBRIS OBSTRUCTING EGRESS, DOOR TO STREET.ROOF BULKHEAD DOOR MISSING LATCH/HARDWARE.RAILING ARUND ROOF UNSTBL.OWNR RETN NYS LIC PE&DOB REG CONTR TO EVAL ENTRE BLDG &RPR UNDR PRMT.FILE APPL BY 7/15/21.BEGN WRK BY 8/15/21.CMPLT WRK BY 1/1/22
DOB05/04/2021V-DOB VIOLATION - ACTIVE
HPD03/30/2021§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE WOOD STAIR STRINGER PULLING AWAY FROM WEST WALL AT 2ND TO 3RD STORY AT PUBLIC HALL STAIRS, 2nd STORY
ECB03/17/2021DEBRIS IN BOILER ROOM, LOOSE WIRES,NO WORKING LIGHT & NO CHIMNEY CLEAN OUT. CORRECT VIOLATING CONDITIONS&SUBMIT A CERTIFICATE OF CORRECTION.$3K due
ECB01/19/2021FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#39030427X ISSUED ON 10/23/20 AND TO FILE A CERIFICATE OF CORRECTION PURSUANT TO 28-201.01 AND 1RCNY 102-01.FAILURE TO MAINTAIN BUIL$6K due
ECB12/24/2020CLASS 1 : NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. FILE APPLICATION, INSTALL DLM$1K due
ECB10/23/2020AT TIME OF INSPECTION OBSERVED ENTIRE STAIRWELL WALL INSTATE OF DISREPAIR CONDITION WITH HORIZONTAL/VERTICAL CRACKS, DETERIORATED WITH SHEETROCK WALL SLIGHTLY BUCKLING / BULGING AND SECTION OF BULKHEAD CEILING$6K due
ECB09/28/2020FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT EXPOSURE#1,THE FACADE HAS RUNNING STEP CRACKS THROUGHOUT THE PARAPET WALLS HAS SECTIONS WITH MISSING BRICKS AND MORTAR.THE RIGHT CORNER OF THE PARA$6K due
HPD09/18/2020§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES AIR CONDITIONER PROTRUDING BEYOND THE WINDOW SILL AT BALCONY AT FRONT BUILDING AT 1st FIRE ESCAPE FROM EAST, 3rd STORY
HPD09/18/2020§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING AT PUBLIC HALL, 1st STORY
HPD09/18/2020§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING BULKHEAD TO ROOF
HPD09/18/2020§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTER AT CEILING AND WALLS TROUGHOUT ALL STORIES AT PUBLIC HALL
HPD09/18/2020§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE DOOR FRAME AT ENTRANCE BULKHEAD DOOR TO ROOF
HPD09/18/2020§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT CEILING AND WALLS TROUGHTOUT ALL STORIES AT PUBLIC HALL
HPD09/18/2020§ 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING. AT PUBLIC HALL, 1st STORY
HPD09/18/2020§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD. AT PUBLIC HALL, 1st STORY
HPD09/18/2020§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED
HPD09/18/2020§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSEHOLD ITEMS AT PUBLIC HALL, 4th STORY
HPD09/18/2020§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSEHOLD ITEMS AT PUBLIC HALL, 3rd STORY
HPD09/18/2020§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING APPROX 10 SQ.FT AT PUBLIC HALL, 4th STORY ORIGINAL VIOLATION 13819923 ISSUED 18-SEP-20 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
HPD09/18/2020§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY
HPD09/18/2020§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX MISSING AT PUBLIC HALL, 1st STORY
HPD09/18/2020§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED ELECTRICAL WIRING AT CEILING LIGHT FIXTURE AT PUBLIC HALL, 3rd STORY
HPD09/03/2020§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF AIR CONDITION UNITS, FURNITURE, AND OTHER HOUSEHOLD EFFECTS, ALL STORIES AT PUBLIC HALL
HPD09/03/2020§ 27-2010, 2011, 2012 ADM CODE CLEANSE AND DISINFECT TO THE SATISFACTION OF THIS DEPARTMENT AFTER REMOVING THE RUBBISH, ALL STORIES AT PUBLIC HALL
HPD09/03/2020§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED ELECTRICAL WIRE AT CEILING AT PUBLIC HALL, 3rd STORY
HPD09/03/2020§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING, NORTH, SOUTH, EAST AND WEST WALLS, TOTAL 25 SQ FT AT PUBLIC HALL, 3rd STORY
HPD09/03/2020§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING AT PUBLIC HALL, 4th STORY
HPD09/03/2020§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE AT CEILING, NORTH, SOUTH, EAST AND WEST WALLS, TOTAL 15 SQ FT AT PUBLIC HALL, 2nd STORY
HPD09/03/2020§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING, NORTH, SOUTH EAST AND WEST WALLS AT PUBLIC HALL, 2nd STORY
HPD09/03/2020§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING, NORTH, SOUTH, EAST AND WEST WALLS AT PUBLIC HALL, 3rd STORY
HPD09/03/2020§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING, NORTH, SOUTH, EAST AND WEST WALLS, TOTAL 50 FT AT PUBLIC HALL, 4th STORY
HPD09/03/2020§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING, NORTH, SOUTH, EAST AND WEST WALLS AT PUBLIC HALL, 4th STORY
ECB07/14/2020FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. EXP#2 PARAPET & CHIMNEY LEANING IN OVER BLDG. SEVERAL LOCATIONS AT EXP#1 FACADE W/MISSING BRICKS &/OR MORTAR. OBSERVED PARAPET CRACKING AT CONNECTION TO EXP#4 WA$6K due
DOB04/16/2020V-DOB VIOLATION - ACTIVE
HPD12/18/2019§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX .. AT PUBLIC HALL, 1st STORY
HPD12/18/2019§ 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING. AT PUBLIC HALL, 1st STORY
HPD12/18/2019§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD. AT PUBLIC HALL, 1st STORY
HPD12/18/2019§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY
HPD12/18/2019§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED AT BOILER ROOM AT BASEMENT
HPD12/18/2019§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED
HPD11/11/2019§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING AT PUBLIC HALL STAIRS
HPD11/11/2019§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING LOCATED AT APT 3F, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
HPD11/11/2019§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING LOCATED AT APT 3F, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
HPD11/08/2019§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AT PUBLIC HALL STAIRS, 2nd STORY
HPD11/08/2019§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING LOCATED AT APT 2, 3rd STORY, APARTMENT AT NORTH
HPD11/08/2019§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES AC PROTRUDING AT 3RD STORY BALCONY, FIRE ESCAPE AT BUILDING FRONT
HPD11/08/2019§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES CONSISTING OF HOUSEHOLD ITEMS 4TH STORY BALCONY FIRESCAPE AT BUILDING FRONT
HPD11/08/2019§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING LOCATED AT APT 2, 3rd STORY, APARTMENT AT NORTH
HPD11/08/2019§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AT PUBLIC HALL, 1st STORY
HPD11/08/2019HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 2, 3rd STORY, APARTMENT AT NORTH
HPD11/08/2019§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL STAIRS, 2nd STORY
HPD11/08/2019§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WITH FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 1st STORY
DOB04/12/2019V-DOB VIOLATION - ACTIVE
DOB02/24/2017VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2015 INSPECTION REPORT
HPD09/22/2016§ 27-2040 ADM CODE PROVIDE ADEQUATE LIGHTING AT OR NEAR THE OUTSIDE OF THE FRONT ENTRANCEWAY OF THE BUILDING AND KEEP SAME BURNING FROM SUNSET EVERY DAY TO SUNRISE ON THE DAY FOLLOWING 100 WATTS MINIMUM REQUIRED, LIGHT FIXTURE PRESENT
HPD09/17/2016§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF CONSISTING OF HOUSEHOLD ARTICLES AND BICYCLES THROUGHOUT AT PUBLIC HALL STAIRS
HPD09/17/2016§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES AT CEILING AT 1ST, 2ND AND 4TH STORIES AT PUBLIC HALL STAIRS
HPD09/17/2016§ 27-2021 ADM CODE PROVIDE SUFFICIENT, PROPER AND SEPARATE METAL RECEPTACLES FOR THE DEPOSIT OF GARBAGE, RUBBISH AND OTHER WASTE MATERIAL AND ARRANGE FOR COLLECTION AND DISPOSAL OF SUCH MATERIAL.
HPD11/14/2015§ 27-2040 ADM CODE PROVIDE ADEQUATE LIGHTING AT OR NEAR THE OUTSIDE OF THE FRONT ENTRANCEWAY OF THE BUILDING AND KEEP SAME BURNING FROM SUNSET EVERY DAY TO SUNRISE ON THE DAY FOLLOWING 100 WATTS MINIMUM REQUIRED , LIGHT FIXTURE PRESENT
DOB10/01/2015VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2014 INSPECTION REPORT
DOB03/03/2015VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2013 INSPECTION REPORT
HPD11/14/2014§ 53, 187, 231 M/D LAW AND DEPARTMENT RULES AND REGULATIONS. PROVIDE A SHOE PROPERLY SECURED TO BOTTOM OF STRING OF DROPLADDER AT BUILDING FRONT AT FIRE ESCAPE
DOB05/15/2014VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2012 INSPECTION REPORT
DOB03/01/2013VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2011 INSPECTION REPORT
DOB12/13/2011VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2010 INSPECTION REPORT
DOB12/31/2009V-DOB VIOLATION - ACTIVE
HPD10/07/2003§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 1R, 1st STORY, APARTMENT AT NORTH
HPD10/07/2003§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM LOCK DOOR 1ST. STY. PUBLIC HALL TO , CELLAR
HPD10/02/2003§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 2L, 3rd STORY, APARTMENT AT NORTH
HPD10/02/2003§ 27-2005, 2007 ADM CODE FIRE EGRESS DEFECTIVE. REMOVE OBSTRUCTING BARS OR UNLAWFUL GATES FROM WINDOW TO FIRE ESCAPE OR PROVIDE APPROVED TYPE GATE ... IN THE ENTIRE APARTMENT LOCATED AT APT 2L, 3rd STORY, APARTMENT AT NORTH
DOB03/19/2003V-DOB VIOLATION - ACTIVE
DOB03/26/2002V-DOB VIOLATION - ACTIVE
DOB01/13/1997V-DOB VIOLATION - ACTIVE
DOB08/16/1993V-DOB VIOLATION - ACTIVE
DOB09/05/1990V-DOB VIOLATION - ACTIVE