ECB03/19/2026Exit door not self-closing. Noted exit door #6 not self-closing. Remedy: repair/replace door.Nothing owed — awaiting certificate of correction
ECB03/19/2026Reissue ECB #35725536Y. Failure to maintain building in code-compliantmanner. Noted smoke doors not self-closing at: stair c-5TH floor, exit#7, 7TH floor, classrooms: 321, 331, 336, 225, 213, 329, 201. Remedy:Nothing owed — awaiting certificate of correction
ECB03/19/2026Reissue ECB #35725535M. Failure to maintain building in code-compliantmanner. Illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. Noted emrgency lights at gym not working. RemedyNothing owed — awaiting certificate of correction
ECB10/27/2025Re-issue ECB #35678935M. Failure to maintain building in code-compliant manner. Illumination for exits, exit discharges and public corridorsper bc 1006.1; 27-381. Noted: emergency lights not functioning upon teNothing owed — awaiting certificate of correction
ECB10/27/2025Failure to maintain building in code-compliant manner. Noted: smoke doors not self-closing due to hardware or binding stair c 5TH fl exit 7 1ST fl, classrooms 321, 331, 336, 225, 219, 329 library and 201 danceNothing owed — awaiting certificate of correction
ECB02/04/2024Reissue#35671736H failure to maintain building in code compliant manner.illumiation for exits,exit discharges and public corridors per bc 1006.1;27-381.noted 2ND floor gym,emergency light not operative tested.rNothing owed — awaiting certificate of correction
ECB03/16/2023Reissue: fail to maintain bldg in code compliant manner:2ND fl gym emergency lights not working.remedy:comply with code.Nothing owed — awaiting certificate of correction
ECB04/11/2019Found kewanee boiler mdl# 7L284 with violating conditions. Water column leaking water. Safety valves leaking. Combustion air interlock bypassed. Vacuum tank pump leaking water. Correct violating conditions andNothing owed — awaiting certificate of correction
ECB04/11/2019Found kewanee boiler mdl# 7L284 with violating conditions. Combustion air interlock bypassed. Vacuum tank pump leaking water. Correct violating conditions and submit a certificate of correction.Nothing owed — awaiting certificate of correction