ECB09/03/2026FAILURE TO COMPLY WITH COMMISSIONER'S ORDER FOR ECB 39114847Y IN CONNECTION WITH 052024CAH02JK/376905., COMPLY WITH COMMISSIONER'S ORDER$2K due
ECB08/01/2025BC 3301.2 FAILURE TO MAINTAIN SAFETY MEASURES TO SECURE PUBLIC. AT TIME OF INSPECTION OBSERVED AT ROOF LEVEL DETERIORATE TRANSPARENT PLASTIC COVERING DISLODGE HANGING OF ROOF LEVEL IN RISK OF FALLING TOWARDS TH$10K due
DOB05/21/2024FAILURE TO MAINTAIN BLDG IN A SAFE CONDITION.THE BLDG SUFFRD FRM FAILURE TO MAINTAIN CONDITIONS@ALL EXPOSURES&ROOF.VARIOUS CRCKS OBSRVD PN EXT&INT OF ALL EXP FLR JOISTS,GIRDERS,POSTS HAD VARIOUS CRCKS&WERE STRCTRLLY COMPROMISED.OWNR TO IMMED RTAIN NYSPE TO EVAL ENT BLDG, DETERMNE STRCTRL STBILITY,&PREPARE/FILE RPAIR DWGS.BLDG TO BE RPAIRD
DOB05/20/2024FAILURE TO MAITAIN BUILDING IN CODE COMPLIAANT MANNER . EXTERIOR, INTE RIOR CRACKS THROUGHOUT BUILDING ALLOWING WATER TO SEEP IN CAUSING WAT ER DAMAGE . DUE TO FAILURE TO MAINTAIN THIS 5 STORY BUILDIGN , THE PA RAPET HAS PARTIALLY COLLAPSED COMPROMISING STRUCTURAL STABILITY + SEC ONDARY MEANS OF EGRESS
DOB05/20/2024EMERGENCY WORK ORDER.ON 5/19/24,THE PARAPET ALONG EXP4 HAD PARTIALLY CLLPSD DMGNG DELAMINGLE LEANING OUTWRD.LOOSE BRCKS MISSNG MOTOR JOINTS BRCKS THE SDWALK SHED&ADJCNT VEHICLES ON THE STREET.OWNR TO IMMED RTAIN NYSPE&DOB REG HC TO 1.IMMED PRVDE TEMP SHORNG&BRACNG INSIDE THE BLDG TO STABILIZE EXP4 WALL
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB04/25/2023VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
DOB04/25/2023VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
DOB04/25/2023VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
DOB04/25/2023VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
DOB04/25/2023VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
DOB04/25/2023VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
DOB04/25/2023VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
ECB08/18/2022NOTE: AT THE TIME OF INSPECTION I OBSERVED A 5 STORY BUILDING WITH A SIDEWALK SHED IN PLACE AT EXP#1 NOT PROPERLY MAINTAINED. I OBSERVED THE WOODEN MUDSILLS BENEATH THE VERTICAL MEMBERS, IN SOME AREAS BROKEN AN$2K due
DOB12/17/2021FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB12/17/2021FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB12/17/2021FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB12/17/2021FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB09/15/2017VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2016 INSPECTION/TEST
DOB09/15/2017VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2016 INSPECTION/TEST
DOB09/15/2017VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2016 INSPECTION/TEST
DOB09/15/2017VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2016 INSPECTION/TEST
DOB09/12/2017V-DOB VIOLATION - ACTIVE
DOB09/12/2017V-DOB VIOLATION - ACTIVE
DOB09/12/2017V-DOB VIOLATION - ACTIVE
DOB09/12/2017V-DOB VIOLATION - ACTIVE
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB11/01/2012FAILURE TO MAINTAIN BUILDING DUE TO STORM
DOB01/15/2009OBTAIN PERMITS OR RESTORE TO PRIOR LEGAL CONDITION
DOB01/15/2009DISCONTINUE ILLEGAL USE AND/OR AMEND C/O
DOB11/28/2006CERTIFICATE OF OCCUPANCY#201390 INDICATES GRND FLR CELLAR) TO 4TH FLR( ACTUALLY -5TH FL LEVEL) TO BE OCCUPIED AS FACTORY SPACE. 2 RESTAURANT/ CAFE'S WERE OCCUPIED AT NORTH & SOUTH ELEVATIONS OF GRND FLR. W/O FIRS T OBTAINING A C.O. SHOWING AMENDED USE.AT 4TH & 5TH FLR LEVELS RESIDEN TIAL UNITS WERE OBSERVED. AT 5TH FLR. A S BEDRM,W/3PC BATYH &* FULL KI
DOB10/31/2006DISPLACED BRICK AT 3RD FL.LINEL IN DANGER OF FALLING ONTO WEST ELEVATI ON SIDEWAL.NUMEROUS SEPARATIONS & CRACKS AT ALL ELEVATIONS-N/ELEV. BUL GING LOOSE BRICK WORK AT PARAPET W/CRACK ACROSS LINTELS & BRICK SHELF S/W CRNR W/VERTICAL CRACK 3RD-4FL.E/ELEV.PARAPET W/DETERIORATED MORTAR JOINTS.UNSUPPORTED WINDOW MOUNTED A/C'S AT ALL ELEVATIONS W/ONE HEATE
DOB06/03/2003V-DOB VIOLATION - ACTIVE
DOB06/03/2003V-DOB VIOLATION - ACTIVE
DOB03/27/20023F4070
DOB01/13/1997V-DOB VIOLATION - ACTIVE
DOB08/16/1993V-DOB VIOLATION - ACTIVE
ECB05/02/2025FAILURE TO AVOID INTERFERENCE. AS NOTED: AT TIME INSPECTION, OBSERVED A SIDEWALK SHED INSTALLED ALONG EXPOSURE 1 AND 2 OF 143 ROEBLING STREET. AT NE SIDE OF ROEBLING STREET AROUND HOPE STREET THE SIDEWALK SHEDNothing owed — awaiting certificate of correction
ECB05/20/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. BUILDING IS STRUCTURALLY COMPROMISED WITH INTERIOR AND EXTERIOR ALLOWING WATER TO ENTER BUILDING AND CAUSE WATER DAMAGE. FAILURE TO MAINTAIN THE BUILDING HNothing owed — awaiting certificate of correction
ECB05/20/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. BUILDING IS STRUCTURALLY COMPROMISED WITH INTERIOR AND EXTERIOR CRACKS, ALLOWING WATER TO ENTER BUILDING AND CAUSE WATER DAMAGE. FAILURE TO MAINTAIN THE BUNothing owed — awaiting certificate of correction
ECB05/20/2024FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER EXTERIOR AND INTERIOR CRACKS THROUGHOUT BUILDING ALLOWING WATER TO SEEP IN AND CAUSE WATER DAMAGE CAUSING THE 6-STORY BUILDING TO BECOME STRUCTURALLY COMPRONothing owed — awaiting certificate of correction
ECB05/19/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER-EXPOSURE(4) HOPESTREET PARAPET HALL COLLAPSED ONTO THE FIRE ESCAPE SIDE HACK SID DAMAGING SEVERAL VEHICLES AND COLLAPSING THE OVERHEAD PROTECTION. APPROX-75Nothing owed — awaiting certificate of correction
ECB03/13/2023FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:OBSERVED CRACKING OF STUCCO DAMAGED MORTAR JOINTS MISSING WINDOW SILL BRACKET FAILED COATING AT WINDOW LINTEL & SILL & DAMAGED AT FRONT STEP.REMEDY:MAINTAINNothing owed — awaiting certificate of correction
ECB03/14/2022STRUCTURE RENDERED NON-COMPLIANT DUE TO PARAPET WALL IN STATE OF DISREPAIR. AT THE TIME OF INSPECTION IT WAS OBSERVED THAT SECTION OF PARAPET WALL DISLODGE AND FALLEN ONTO SIDEWALK AT EXPOSURE 2 SIDE OF THE BUINothing owed — awaiting certificate of correction
ECB10/03/201767X10,12Q3,39P7,20M7,70P7,42I10-67X10)REPAIR EMERGENCY PHONE IN CAR. 39P7)PROVIDE ACCESS TO THE CAR TOP.(ALL FLOORS ARE BLOCKED(LOCKED)). 700P7)PROVIDE ACCESS TO THE PIT AND "B" FLOOR. 20M7)B FLOOR. 42I10)REPAINothing owed — awaiting certificate of correction
ECB05/06/2017FAILURE TO MAINTAIN BUILDING WALLS(S) OR APPURTENANCES NOTED,AT EXP #1 ON HOPE STREET,FRONT FACADE IS IN A SERIOUS STATE OF DISREPAIR,A PIECE OF REINFORCED CONRETE UNDER 5TH FLOOR WINDOW HAS FALLEN AND VERTICALNothing owed — awaiting certificate of correction
ECB08/12/2014OCCUP CONTRARY TO DEP RECORDS,4 FL REAR BLDG NOT PROTECTED UNDER LOFT LAW CONVERTED W/MULTI SROS W/NO REGISTRATION FOR THAT LVL.RESPONDANT HAS A HISTORY OF NON COMPLIANCE W/DOB.REM:DISCONTINUE ILLEGAL USE.Nothing owed — awaiting certificate of correction
ECB06/25/2010FAILURE TO COMPLY W/COMMISSIONER'S ORDER TO VACATE. COMMISSIONER'S ORDER 29368 ISSUED 12.8.08 TO VACATE CELLAR IS NOT COMPLIED W/AT PREMISES. AT TIME OF INSPECTION CELLAR AREA HAS NO NATURAL LIGHT, AIR ORNothing owed — awaiting certificate of correction
ECB04/03/2009FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER LACK OF EMERGENCY LIGHTING FOR EXITS. EXIT DISCHARGES & PUBLIC CORRIDORS PER BC 1006.1/27-542 NOTED EMERGENCY LIGHTING IN STAIRWELL NOT OPERATIONAL.Nothing owed — awaiting certificate of correction
ECB04/03/2009SEC. BC1001.3 27-361 FAILURE TO MAINTAIN EGRESS CLEAR & UNOBSTRUCTED. NOTED LANDING AT 1ST FLR STAIR HAS APPROX 5' 6" CLEARANCE IN HEIGHT. LANDINGS TO ALL FLRS ARE APPROX (2' 6") WIDE. DOES NOT MEET MINIMUM REQNothing owed — awaiting certificate of correction
ECB04/03/2009FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER NOTED BULK HEAD HAS CRACKS IN CEILING,WALLS HAVE LOOSE BRICKS WITH STEP CRACKS 4TH FLR HAS SECTION OF WOOD FLOORING LOOSE & BUCKLING. REMEDY: REPAIR ALL DEFNothing owed — awaiting certificate of correction
ECB04/02/2009OCCUPANCY CONTRARY TO THAT ALLOWED BY C OF O OR BLDG DEPT RECORDS.NOTED:FACTORY BLDG DEPT RECORDS CONVERTED TO RESIDENTIAL ON 4FL.RESPONDENTHAS HISTORY OF NON COMPLIANCE FOR THIS VIOLATING CONDITION.REMEDY:DISCNothing owed — awaiting certificate of correction
ECB03/16/2009OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERT OF OCCUPANCY NOTED 5STY BLDG ALTERED TO BE OCCUPIED AS CLASS A APT AND OFFICES CONTRARY TO CERT OF OCCUPANCY #201390 INDICATE BLDG TO BE USED AND OCCUPIED AS FACTONothing owed — awaiting certificate of correction
ECB01/20/2009FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER RE: INSTALLATION/MAINTENANCE OF PLUMBING MATERIALS/EQUIPMENTS PER PC 102.3; 27-902. FOUND ON 5TH FLR 2 HANGING HEATERS AND 2 HOT WATER HEATERS HOOKED UP W/ GASNothing owed — awaiting certificate of correction
ECB01/16/2009UNLAWFULLY CONTINUED WORK WHILE ON NOTICE OF A STOP WORK ORDER. NOTED:OBSERVED CONTINUED WORK OF INSTALLATION OF NEW BATHROOM & WALL AT 2ND FL & ERECTION OF PARTITIONS AT CELLAR, CONTRARY TO SWO ISSUED 12.8.08Nothing owed — awaiting certificate of correction
ECB12/10/2008OCCUPANCY CONTRARY TO THAT ALLOWED BY C/O NOTED: C/O #201390 INDICATES LEGAL OCCUPANCY OF CELLAR FACTORY USE,BUILDING DEPT RECORDS INDICATE BUILDING SERVICES & STORAGE ILLEGAL OCCUPANCY OBSERVED 2 ROOMS USED ASNothing owed — awaiting certificate of correction
ECB12/10/2008OPERATION OF A P.A. W/O A CURRENT CERTIFICATE OF OPERATION. NOTED: OPERATION OF RESTAURANT,(KITCHEN)AS "ROEBLING TEA ROOM" UNDER APPL. #301913231 WITH SEATING FOR 66 PERSONS + STAFF,APPROX PLANS 9/26/05 HOW OPENothing owed — awaiting certificate of correction
ECB12/10/2008OCCUPANCY CONTRARY TO THAT ALLOWED BY C/O NOTED: C/O #201390 INDICATES LEGAL USE FLRS 1-5 IS THAT OF CLOTHING FACTORY. ENTIRE BUILDING ILLEGALLY CONVERTED TO COMMERCIAL & RESIDENTIAL/STUDIO SPACES & OFFICES W/ONothing owed — awaiting certificate of correction
ECB12/10/2008WORK W/O PERMITS NOTED: BUILDING LEGAL USE FACTORY ILLEGALLY CONVERTED THROUGHOUT FLRS CELLAR-5 PARTITIONS ERECTED WITH ASSOC. LIGHTING & ELECTRIC,WATER ,WASTE AND GAS LINES TO CREATE RESIDENTIAL KITCHENS,3 & 2Nothing owed — awaiting certificate of correction
ECB04/05/2007WORK W/O A PERMIT.NOTED:6 WINDOWS AT FRONT WEST SIDE APPROX 3FT WIDE X6FT HIGH.EACH 2 ON 2ND FL, 2 ON 3RD FL & 2 ON 4TH FL ARE SEALED W/BRICK WALL W/O A VALID PERMIT.REMEDY:OBTAIN PERMIT IF FEASIBLE OR TONothing owed — awaiting certificate of correction
ECB01/28/2007WORK W/O A PERMIT IN MANUFACTURING M1-6 FOR RESIDENTIAL USE.WORK NOTEDFOURTH FLOOR FRONT BLDG ERECTED FULL HEIGHT PARTITION WALLS TO CREATE 3 SRO'S,1 KITCHEN COMPLETE W/GAS STOVE,3 PIECE BATHROOM(TOILET,SINKNothing owed — awaiting certificate of correction
ECB01/24/2007OCCUPANCY IN MANUFACTURING DISTRICT M1-6 INCONSISTANT W/ THAT ALLOWED BY C OF O OR DOB RECORDS ILLEGAL OCCUPANCY NOTED:SIXTH FLR FRONT BLDG MANUFACTURING NOW CONVERTED TO TWO CLASS A APTS,EACH WITH ONE SINKNothing owed — awaiting certificate of correction
ECB01/24/2007WORK W/O PERMIT IN MANUFACTURING M1-6 FOR RESIDENTIAL USE WORK NOTED: SIXTH FLOOR FRONT BLDG ERECTED FULL HEIGHT PARTITION WALLS TO CREATE 2CLASS A APARTMENTS EACH W/ A KITCHEN AND BATHROOM.REMEDY:DISCONTINUENothing owed — awaiting certificate of correction
ECB01/24/2007PLUMBING WORK W/O A PERMIT IN MANUFACTURING DISTRICT M 1-6 FOR RESIDENTIAL USE. WORK NOTED:6TH DL FRONT BLDG INSTALLED WATER & WASTE LINES FOR 2 KITCHEN SINKS,2 SHOWER,2 TOILETS,2 BATHROOM SINKS.ALSO INSTALL 1Nothing owed — awaiting certificate of correction
ECB01/24/2007OCCUPANCY IN MANUFACTURING DISTRICT M1-6 INCONSISTANT WITH THAT ALLOW ED.BY C OF O OR DOB RECORDS.ILLEGAL OCCUPANCY NOTED:1ST FLR REAR BLDG MANUFACTURING NOW CONVERTED TO CLASS A APARTMENTS WITH ONE KITCHENNothing owed — awaiting certificate of correction
ECB01/24/2007WORK W/O A PERMIT IN MANUFACTURING M1-6 FOR RESIDENTAL USE WORK NOTED:1ST FLOOR REAR BLDG ERECTED FULL HEIGHT PARTITION WALLS TO CREATE A CLASS A APT W/ A KITCHEN COMPLETE W/ 1 GAS STOVE & 1 RESIDENTIAL SINKNothing owed — awaiting certificate of correction
ECB01/24/2007ILLEGAL USE IN MANUFACTURING DISTRICT NOTED 4FL FRONT BLDG INSTALLED AKITCHEN W/A RESIDENTIAL SINK,3PC BATHROOM(SINK,TOILET,TUB,SHOWER)REMEDY:DISCONTINUE ILLEGAL USENothing owed — awaiting certificate of correction
ECB01/24/2007PLUMBING WORK W/O A PERMIT MANUFACTURING DISTRICT M 1-6 FOR RESIDENTIAL USE. WORK NOTED:1ST FL REAR BLDG INSTALLED WATER & WASTE LINES FOR A KITCHEN W/ A RESIDENTIAL SINK,& 3 PC BATHROOM(SINK,TOILET,TUB/SHOWER)Nothing owed — awaiting certificate of correction
ECB01/24/2007OCCUPANCY IN MANUFACTURING DISTRICT M1-6 INCONSISTANT WITH THAT ALLOW ED BY C OF O OR DOB RECORDS.ILLEGAL OCCUPANCY NOTED:5TH FLR FRONT BLDGMANUFACTURING NOW CONVERTED TO 27 SRO'S WITH ONE KITCHEN AREANothing owed — awaiting certificate of correction
ECB01/24/2007PLUMBING WORK W/O A PERMIT IN MANUFACTURING DISTRICT M 1-6 FOR RESIDENTIAL USE,WORK NOTED 2ND FL FRONT BLDG INSTALLED WATER & WASTE LINES FOR 4 TOILETS,4 RESIDENTIAL BATHROOM,SINKS,5 SHOWERS,& 1 KITCHEN SINKNothing owed — awaiting certificate of correction
ECB01/24/2007ILLEGAL USE IN MANUFACTURING DISTRICT.NOTED:6FL HAS 2 CLASS A APT EACHW/IT'S OWN KITCHEN(RESIDENTIAL SINK,STORE,REFRIGERATOR)& BATHROOM(SINK,TOILET,SHOWER)LIVING AREA & BEDROOMS.REMEDY:DISCONTINUE ILLEGAL USENothing owed — awaiting certificate of correction
ECB01/24/2007WORK W/O A PERMIT IN MANUFACTURING M1-6 FOR RESIDENTIAL USE. WORK NOTED:SECOND FLR ERECTED FULL HIEGHT PARTITION WALLS TO CREATE 8 SRO'S1 KITCHEN COMPLETE WITH ELECTRIC STOVE,3 PIECE BATHROOM(TOILET,SINK,Nothing owed — awaiting certificate of correction
ECB01/24/2007OCCUPANCY IN MANUFACTURING DISTRICT M1-6 INCONSISTANT WITH THAT ALLOW ED BY C OF O OR DOB RECORDS.ILLEGAL OCCUPANCY NOTED:SECOND FLOOR FRONTBUILDING MANUFACTURING NOW CONVERTED TO AN APARTMENT WITH 8 SRO'S.Nothing owed — awaiting certificate of correction
ECB01/24/2007PLUMBING WORK W/O A PERMIT IN A MANUFACTURING DISTRICT R1-6 FOR RESIDENTIAL USE.WORK NOTED 2ND FL FRONT BLDG INSTALLED WATER & WASTE LINES FOR 3 PC BATHROOM(TOILET, SINK,TUB/SHOWER)REMEDY:OBTAIN PERMIT IF FEASINothing owed — awaiting certificate of correction
ECB01/24/2007ILLEGAL USE IN MANUFACTURING DISTRICT.NOTED 2FL HAS A KITCHEN W/A RESIDENTIAL SITE,3PC BATHROOM(SINK,TOILET,TUB/SHOWER).REMEDY:DISCONTINUE ILLEGAL USENothing owed — awaiting certificate of correction
ECB01/24/2007OCCUPANCY IN MANUFACTURING DISTRICT M1-6 INCONSISTANT WITH THAT ALLOW ED BY C OF O OR DOB RECORDS.ILLEGAL OCCUPANCY NOTED:4TH FLR FRONT BLDGMANUFACTURING NOW CONVERTED TO 3 SRO'S WITH ONE KITCHEN COMPLETE W/GASNothing owed — awaiting certificate of correction
ECB01/24/2007PLUMBING WORK W/O A PERMIT IN MANUFACTURING DISTRICT M1-6 FOR RESIDENTIAL USE.WORK NOTED:4TH FL FRONT BLDG INSTALLED WATER & WASTE LINE FOR 3 PC BATHROOM(TOILET,SINK,TUB/SHOWER)REMEDY:OBTAIN PERMIT IF FEASIBLENothing owed — awaiting certificate of correction
ECB01/24/2007ILLEGAL USE IN MANUFACTURING DISTRICT.NOTED:5FL HAS A KITHCEN W/A RESIDENTIAL SINK,BATHROOM W/4 TOILETS & 4 SINKS,BATHROOM W/5 SHOWERS.REMEDY:DISCONTINUE ILLEGAL USE.Nothing owed — awaiting certificate of correction
ECB01/19/2007ILLEGAL USE IN MANUFACTURING DISTRICT.NOTED:1FL REAR BLDG 1 CLASS A APT W/IT'S OWN KITCHEN(STOVE,REFRIGERATOR,RESIDENTIAL SINK)& BATHROOM(SINK,TOILET,TUB/SHOWER)LIVING AREA,BEDROOM.REMEDY:DISCONTINUE ILLEGAL USNothing owed — awaiting certificate of correction