HPD05/07/2026(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
HPD11/17/2025§27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID REGISTRATION STATEMENT IS FILED.
HPD06/12/2025(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
ECB01/08/2025FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS #39071098Z ISSUED ON 09/29/2022, AND FAILURE TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28.201.1 AND 1 RCNY 102-01(D)(2). AN ACCEPTABLE CERT$6K due
DOB12/01/2024FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
HPD11/22/2024§27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID REGISTRATION STATEMENT IS FILED.
DOB08/02/2024FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB05/02/2024FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
HPD04/16/2024(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
DOB02/22/2024FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
HPD11/15/2023§27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID REGISTRATION STATEMENT IS FILED.
DOB11/02/2023FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB08/02/2023FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB05/02/2023FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
HPD03/29/2023(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
HPD02/26/2023§ 27-2026 ADM CODE RESET, SO AS TO SECURE A PROPER AND TIGHT CONNECTION, THE WATER CLOSET BOWL ... IN THE BATHROOM LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
DOB12/01/2022FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
ECB09/29/2022I OBSERVED IN THE REAR COURTYARD AREA THE BOILER ROOM WITH NO REMOTE SHUT-DOWN AT THE EXTERIOR POINT OF EGRESS AS REQUIRED UNDER MC 1006.8.1; MC 1006.8.1, COMPLY WITH CODE; SUPPLY REMOTE SHUT-OFF AT EXTERIOR PO$1K due
ECB09/29/2022AT ROOF LEVEL, BULKHEADS (A&B) FACADE WALLS CRACKED MORTAR IN VARIOUS LOCATIONS. ALSO, PARAPET WALLS,EXTERIOR SIDE , CRACKED MORTAR (EXP # 1,2,3&4).PREVIOUS ECB VIOLATION NUMBER: 39060462M., MAINTAIN EXTERIOR B$3K due
ECB09/29/2022I OBSERVED ON ALL FLOORS THE INSTALLATION OF PORCELAIN TYPE FIXTURES IN THE STORAGE CLOSETS AND THE REPLAIR OR REPLACEMENT OF THE INOPERABLE FIXTURES ON THE FLOORS. NO PERMIT ON FILE FOR THIS WORK AS REQUIRED F$800 due
ECB09/29/2022AT EXPOSURE # 1, RAMP / STAIRS / RAILINGS, OF MAIN ACCESS WITH METAL (COLUMNS AND BEAMS) AND CONCRETE STRUCTURE WAS BUILT WITHOUT A PERMIT, OBTAIN ALL PERMITS$1K due
ECB09/29/2022OBSERVED ACTIVE WATER LEAK IN THE CORRIDOR AT CELLAR LEVEL. AS PER THE 2014 PC 102.3 INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHALL BE MAINTAINED IN PROPER OPERATING CONDITION IN ACCORDANCE WITH$625 due
ECB09/29/2022AT CELLAR LEVEL, UTILITIES ROOMS, SEVERAL OPENING DUE PIPES/CABLES PENETRATION WITHOUT FIRE STOPPING PROVIDED., PROVIDE/MAINTAIN FIRE STOPPING$1K due
ECB09/29/2022AS PER ONE LAARS PENNANT. AIR PROVING SWITCH DEFECTIVE-COMPOUND GAGE DEFECTIVE-AIR INTAKE FILTERS DIRTY.$625 due
ECB09/29/2022AT FIRST FLOOR, EXP # 1, EXIT DOOR (LEFT SIDE ) STAIR B EXIT DOOR, AT CELLAR LEVEL, EXP # 1, EXIT DOORS (3 UND),DOORS DO NOT CLOSE PROPERLY, DUE TO DAMAGE TO THE LEAVES, FRAMES, SELF-CLOSING SYSTEM AND OTHER FA$2K due
ECB09/29/2022AT BACK YARD FACADE, VERTICAL CRACK BETWEEN WINDOWS FROM THE FIRST FLOOR TO THE ROOF. PREVIOUS ECB VIOLATION NUMBER: 39051287J, MAINTAIN EXTERIOR BUILDING WALL$3K due
ECB09/29/2022AT CELLAR LEVEL, EXP # 4, HALLWAY/EXIT TO BACK YARD/HEATER ROOM, DAMAGED CEILING, NO LIGHTING/DARK HALLWAY. PREVIOUS ECB VIOLATION NUMBER: 39051289N., REPAIR AND/OR REPLACE$2K due
ECB04/18/2022NOTED: OBSERVED VERTICAL AND HORIZONTAL CRACKS ON EXTERIOR OF STAIR "A" AND "B" BULKHEADS, WEST ROOF'S PARAPET, MID BUILDINGS' SHAFTWAY, AT REAR OF BOTH EAST AND WEST BUILDINGS HAVE VERTICAL CRACKS UNDER WINDOW$3K due
DOB12/01/2021FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
ECB11/17/2021NOTED: OBSERVED AT REAR VERTICAL CRACKS UNDER WINDOWS FROM FIRST FLOOR UP TO THE FIFTH FLOOR, CORNER NEAR PARAPET (WEST ROOF), AND INTERIOR MID BUILDING SHAFTWAYS, STEP CRACKS ON EXTERIOR OF BOTH BULKHEAD., MAI$3K due
ECB11/17/2021I OBSERVED ON ALL FLOORS IN THE HALLS AND THE STORAGE CLOSETS DEFECTIVE/INOPERABLE LIGHTS AND EXPOSED CONDUCTORS. THIS IS A MAJOR SHOCK HAZARD., COMPLY WITH EC; REPAIR/AND OR REPLACE DEFECTIVE LIGHTS AND PROPER$4K due
ECB11/17/2021I OBSERVED IN THE BASEMENT AT GAS METER ROOM/ SPRINKLER ROOM POTABLE WATER PIPING FROM WATER METER BEING SUPPORTED IMPROPERLY. THE WATER PIPE IS BEING SUPPORTED WITH ROPE THAT IS ATTACHED TO THE OVER HEAD PIPIN$625 due
ECB11/17/2021NOTED: OBSERVED AT FIRST FLOOR EXTERIOR EXIT DOOR LEADING OUT TO THE FRONT OF BUILDING (WEST) IS NOT SELF CLOSING., REPAIR/REPLACE DOOR$625 due
ECB11/17/2021NOTED. OBSERVED THROUGHOUT EACH FLOOR, HOLES AND OPENINGS IN FIRE RATED GYPSUM BOARDS IN EVERY MAINTENANCE CLOSET, 4TH FLOOR STAIRWELL "A", AT BRIGHT SPACE MULTI-PURPOSE ROOM, TUNNEL TO REAR YARD., REPAIR AND/O$625 due
DOB04/29/2021FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
ECB03/20/2019FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES,NOTED: OBSERVED @REAR, EXP#3 OF BOTH EAST AND WEST BUILDINGS = STEPCRACKS/VERTICAL CRACKS UNDERNEATH THE WINDOWS OF THE FIRST UPTO THE FIFTH STORY, ALSO$6K due
ECB09/12/2018FAILURE TO INSTALL GROUND FAULT CIRCUIT INTERRUPTER(GFCI)PROTECTION ASREQUIRED. OBSERVED IN THE CELLAR. RECEPTACLE NEXT TO UTILITY SIGN WHERE WSASHER MACHINE IS GETTING POWERED IS NOT GFCI PROTECTED.$10K due
ECB05/31/2018FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 5/ 31/18 AT ABOVE ADDRESS. NO VENTILATION IN GAS METER ROOM IN BASEMENT/ CELLAR LEVEL. RMDY: REPAIR AND/OR REPLACE.$3K due
ECB04/05/2016EXIT DOOR NOT SELF-CLOSING.THE FOLLOWING DOORS NOT SELFCLOSING.STAIR1BEXIT DOOR, STAIRS 12A EXIT DOOR AND STAIR 3A EXIT DOOR. RMDY: REPAIR/ REPLACE DOORS.
ECB05/06/2019PIPING AT MIXING VALVE CORRODED, REPAIR OR REPLACE CORRODED PIPING. COMBUSTION AIR FAN INOPERABLE, REPAIR OR REPLACE FAN. SAIL SWITCH ALSO INOPERABLE. BOILERS IN NEED OF MAINTENANCE AIR INTAKE FILTERS DIRTY .Nothing owed — awaiting certificate of correction
ECB09/12/2018FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON ROOF. APPROX 4 EXHAUST FANS WHICH CIRCULATE FRESH AIR THROUGHOUT BLDG INOPERABLE;NOT WORKING. REMEDY: REPAIR & OR REPLACE.Nothing owed — awaiting certificate of correction
ECB12/15/2017FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 12/15/2017 @ ABOVE ADDRESS NO VENTILATION IN THE WATER & GAS METER ROOM. PHOTOS TAKEN. REM: REPAIR &/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB09/26/2016FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: LACK OF EMERGENCY LIGHTING FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS PER BC1006.1;27-542. NOTE: INOPERATIVE EMERGENCY LIGHTS W/BATTERY BACKUP AT 2ND FL STAINothing owed — awaiting certificate of correction