ECB02/17/2026FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPT OF BUILDINGS FOR SUMMONS 39074450M, FILE A CERTIFICATE OF CORRECTION$1K due
ECB07/10/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF INSPECTION, OBSERVED STORAGE INSIDE MECHANICAL ROOM. (MIRCOWAVE, REFRIGERATOR LOCKERS, CLOTHES, TOOLS) LOCATED AT BASEMENT LEVEL., REPAIR AND/REHearing held — result not yet published$2K proposed
ECB07/10/2026ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED IN THE MAIN ELECTRICAL ROOM THE INSTALLATION OF VERIZON TELEPHONE / WIFI EQUIPMENT. ALL ELECTRICAL ROOMS /CLOSET SHALL BE DEDIHearing held — result not yet published$1K proposed
ECB07/10/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. HOLE PENETRATION ABOVE DOOR LEADING INTO MECHANICAL ROOM. COVERED UP WENT A VENT COVER. LOCATED AT BASEMENT LEVEL., REPAIR AND/REPLACEHearing held — result not yet published$2K proposed
ECB11/25/2022I OBSERVED ON THE EXTERIOR OF THE BUILDING A COMPRESSOR UNIT AND IN THE CELLAR LEVEL WALL MOUNTED BLOWER UNITS FROM A SPLIT A.C SYSTEM WITH NEW BRANCH CIRCUIT WIRING EQUIPMENT DISCONNECT AND INTERCONNECT WIRINGNothing owed — awaiting certificate of correction
ECB11/25/2022I OBSERVED ON THE ROOF THE USE OF EMT OUTDOORS, THE CONDUIT IS ALSO IN A STATE OF CORROSION. ALSO NOTED THE GENERATOR IN A SEVERE STATE OF CORROSION. THIS IS AN IMMEDIATE HAZARD AS CORROSION OF ELECTRICAL EQUIPNothing owed — awaiting certificate of correction
ECB11/25/2022I OBSERVED ON ALL FLOORS NO REMOTE SHUT-DOWN AT THE EXTERIOR OF THE BOILER ROOMS AS PER MC 1006.8.1; MC1006.8.1, COMPLY WITH CODE; INSTALL REMOTE SHUT-DOWNNothing owed — awaiting certificate of correction
ECB11/25/2022I OBSERVED ON THE ROOFTOP LEVEL DEFECTIVE WIRING TO THE LIGHTS SJ CORD IS ONLY PERMITTED IN DAMP LOCATIONS EXPOSURE TO THE ELEMENTS IS CONSIDERED A WET LOCATION. AS PER TABLE IN EC 400.4 PHOTOS TAKEN., PROVIDENothing owed — awaiting certificate of correction
ECB11/25/2022I OBSERVED IN THROUGHOUT THE CELLAR LEVEL WALL MOUNTED BLOWER UNITS FROM A A.C. SPLIT UNIT, THE WIRING TO THE UNIT IS FLEXIBLE CORD THIS IS NOT PERMITTED AS PERMANENT WIRING, ALSO NOTED IN THE BOILER ROOMS THENothing owed — awaiting certificate of correction