ECB07/10/2026Failure to maintain building in code-compliant manner. Hole penetration above door leading into mechanical room. Covered up went a vent cover. Located at basement level., repair and/replace$2K due
ECB07/10/2026Failure to maintain building in code-compliant manner. At time of inspection, observed storage inside mechanical room. (mircowave, refrigerator lockers, clothes, tools) located at basement level., repair and/re$2K due
ECB07/10/2026Electrical closet not dedicated to electrical distribution equipment only. Observed in the main electrical room the installation of verizon telephone / wifi equipment. All electrical rooms /closet shall be dedi$1K due
ECB07/10/2026Failure to provide adequate grounding of electrical systems. Observed in the main electrical rm and at the main water service no installation of electrode ground rod. This is second means of grounding must be p$2K due
ECB02/17/2026Failure to comply with the commissioner's order to file a certificate of correction with the dept of buildings for summons 39074450M, file a certificate of correction$1K due
ECB11/25/2022I observed on the roof the use of emt outdoors, the conduit is also in a state of corrosion. Also noted the generator in a severe state of corrosion. This is an immediate hazard as corrosion of electrical equipNothing owed — awaiting certificate of correction
ECB11/25/2022I observed on all floors no remote shut-down at the exterior of the boiler rooms as per mc 1006.8.1; MC1006.8.1, comply with code; install remote shut-downNothing owed — awaiting certificate of correction
ECB11/25/2022I observed on the rooftop level defective wiring to the lights sj cord is only permitted in damp locations exposure to the elements is considered a wet location. As per table in ec 400.4 photos taken., provideNothing owed — awaiting certificate of correction
ECB11/25/2022I observed in throughout the cellar level wall mounted blower units from a a.c. Split unit, the wiring to the unit is flexible cord this is not permitted as permanent wiring, also noted in the boiler rooms theNothing owed — awaiting certificate of correction
ECB11/25/2022I observed on the exterior of the building a compressor unit and in the cellar level wall mounted blower units from a split a.c system with new branch circuit wiring equipment disconnect and interconnect wiringNothing owed — awaiting certificate of correction