HPD05/04/2026(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
HPD07/15/2025§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDENT MATERIAL AT CEILING AT CELLAR
HPD07/15/2025§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AT CELLAR
HPD07/15/2025§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED ELECTRIAL WIRING AT CEILING AND WEST WALL AT CELLAR
HPD07/15/2025§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION EXTENSTION AT REAR YARD (APPROX. 20X35 FT)
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
DOB04/25/2023VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
DOB04/25/2023VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
DOB11/08/2019VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
DOB11/08/2019VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
DOB07/24/2019FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB07/24/2019FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB01/02/2013FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB01/02/2013FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
HPD07/06/2012§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. LOCATED AT APT 3, 4th STORY
HPD07/06/2012§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING LOCATED AT APT 3, 4th STORY
DOB04/05/2010V-DOB VIOLATION - ACTIVE
HPD10/15/2007§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE KITCHEN , THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 3, 4th STORY, 1st APARTMENT FROM NORTH AT EAST
DOB08/16/1993V-DOB VIOLATION - ACTIVE
ECB04/25/2019FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER; I OBSERVED IN RESTAURANT AREA PROPANE TANKS AND HOSES ATTACHED TO GAS PIPING BEING USED TO COOK FOOD AND RESIDENTIAL GAS FLEX CONNECTOR INSTALLED ON BACKNothing owed — awaiting certificate of correction
ECB04/25/2019WORK WITHOUT A PERMIT; I OBSERVED NEWLY INSTALLED GAS PIPING IN RESTAURANT FROM ONE SIDE OF GAS PIPING TO THE OTHER AND PROPANE HOSES ATTACHED. NO PERMITS ON FILE FOR GAS PIPING , OBTAIN PERMITNothing owed — awaiting certificate of correction
ECB10/12/2016WORK W/O A PERMIT. NOTE AT THE TIME OF INSPECTION A PLAYFORM OF QUESTIONALBE CONSTRUCTION(STEEL & WOOD)& SUPPORTING AN A/C CONDENSER UNIT APPROX 10FT HIGH,WAS OBSERVED ERECTED IN THE REAR YARD OF A RESTURANT.Nothing owed — awaiting certificate of correction
ECB12/17/2012FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER CONTAINED IN NOTICE OF VIOLATION #34981030N ISSUED ON 8/7/12. FOR WORK W/O A PERMIT. CONVERTED PREMISES INTO 12 SRO'S. REMEDY: COMPLY W/THE COMM'S ORDER.Nothing owed — awaiting certificate of correction
ECB08/27/2012OCCUPANCY CONTRARY TO THAT ALLOWED BY C/O AND DOB RECORDS ENTIRE BLDG CONVERTED FROM 4 STYS, 3 CLASS 'A' APTS INTO 4 STYS, 'B' ROOMS ALL STYS THRU/OUT. PARTITIONS ERECTED SUBDIVIDING APTS INTO SEPARATE OCCUPIEDNothing owed — awaiting certificate of correction
ECB08/24/2012OCCUPANCY CONTRARY TO THAT ALLOWED BY C/O AND DOB RECORDS 4STY CLASS A APT CONVERTED INTO 5 SRO ROOMS SINGLE ROOM OCCUPANCY THRU OUT 4STY INADEQUATE LIGHT & VENTILATION REM: DISCONTINUE ILLEGAL USE OF AMENDED CNothing owed — awaiting certificate of correction
ECB08/07/2012RESIDENCE ALTERED FOR OCCUPANCY AS A DWELLING FOR MORE THAN LEGALLY APPROVED NUMBER OF FAMILIES LEGAL OCCUPANCY 3 FAMILY OF ONE APT PER FLR AS PER CO#150580. AT TIME OF INSPECTION OBSERVED ILLEGAL PARTITION INSNothing owed — awaiting certificate of correction
ECB08/07/2012FAILURE TO PROVIDE UNOSTRUCTED EXIT PASSAGEWAY DUE TO INSTALLED PARTITIONS ON FLOORS 2,3 & 4 REAR FIRE ESCAPE IS NOT ACCESSIBLE 4 FLOOR HAS 4 SRO'S 3RD FL HAS 5 SRO'S & 2ND FL HAS 3 SRO'S. ROOMS ADJECENT TONothing owed — awaiting certificate of correction
ECB11/05/2011OCCUPANCY CONTRARY TO THAT ALLOWED BY C/O AND DOB RECORDS. 3 STY CLASSA APT CONVERTED INTO 5 B ROOMS THRU/OUT. PARTITIONS ERECTED FROM FLR TO CEILING W/LOCK DOORS IN ALL ROOMS. INADEQUATE LIGHT & VENTILATION.Nothing owed — awaiting certificate of correction
ECB03/29/2010FAILURE MAINTAIN BLDG WALLS OR APPURTENCES IN THAT @ FRONT OF BLDG MASONARY DECORATIVE PIECE ABOVE WINDOW @ 4TH FL HAD PULLED AWAY FROM BLDG& FELL TO THE GROUND.REM-MAINTAIN EXTERIOR BLDG WALL.INSTALL SIDEWALKNothing owed — awaiting certificate of correction
ECB07/28/2009OCCUPANCY CONTRARY TO THAT ALLOWED BY C OF O AND DEPT OF BLDGS RECORDS2 STY CLASS "A" APT CONVERTER INTO 5 CLASS "B" ROOMS REM: DISCONTINUE ILLEGAL USE OF AMENDED C OF O.Nothing owed — awaiting certificate of correction
ECB06/11/2008EXIT PASSAGEWAY TOTAL OBSTRUCTION - NOTED: AT REAR OF EXISTING 4 STORY MULTIPLE DWELLING 1 STORY MASONRY EXTENSION ERECTED AT REAR HAS OBSTRUCTED REAR FIRE ESCAPE DROP LADDER FROM DROPPING TO GROUND LEVEL.Nothing owed — awaiting certificate of correction
ECB06/11/2008SEC. 26-126.3. FAILURE TO CERTIFY CORRECTION OF A VIOLATION. NOTED: ECB #34612860Z VIOLATION ISSUED 10/19/07 CONDITION STILL EXISTS. REMEDY:COMPLY W/CERTIFICATE OF CORRECTION FORTHWITH.Nothing owed — awaiting certificate of correction
ECB12/29/2007FAILURE TO PROVIDE AT LEAST 2 MEANS OF EGRESS FROM ROOM OR SPACE WHEN REQUIRED. NOTED: AT REAR OF BLDG FIRE ESCAPE THAT IS 2ND MEANS OF EGRESS IS BLOCKED & ELIMINATED FROM A STRUCTURE EXTENSION ATTACHED TO BLDGNothing owed — awaiting certificate of correction
ECB12/29/2007WORK W/O A PERMIT. NOTED: AT REAR OF BLDG IS ERECTED A STRUCTURE W/CONCRETE BLOCKS & METAL ROOF ATTACHED TO EXISTING BLDG & ELIMINATE FIRE ESCAPE FROM 2ND FL TO GROUND. REMEDY: OBTAIN PERMIT OR RESTORE TO PRIORNothing owed — awaiting certificate of correction
ECB12/29/2007FAILURE TO MAINTAIN BLDG. NOTED: AT REAR OF BLDG FIRE ESCAPE IS DEFECTIVE, BROKEN, MISSING STEPS & DEBRIS ALL OVER. REMEDY: MAINTAIN BLDG (FIRE ESCAPE).Nothing owed — awaiting certificate of correction
ECB10/31/2007FAILURE TO MAINTAIN PLUMBING. HAZARDOUS. OBSERVED THE FOLLOWING IN THECELLAR: A WATER LEAK FROM 1 ST FLR STORE TOILET PIPE & WATER SOAKED & ROTTED FLR JOISTS. PVC PIPING & FENCO COUPLING FOR 1ST FLR DRAINS:Nothing owed — awaiting certificate of correction
ECB10/19/2007ALTERED BLDG OCCUPIED W/O A VALID COFO NOTED: COFO 150580 INDICATES OFFICES AT 1ST FL HAS NOW BEEN CONVERTED TO A RESTAURANT.REMEDY: OBTAIN VALID COFO.Nothing owed — awaiting certificate of correction
ECB06/26/2006OCCUPANCY CONTRARY TO THAT OF BLDG DEPT C OF O # 150580 ISSUED SEPT 21INDICATE BUILDING IS LEGALLY APPROVED FOR 2ND FLOOR 3RD FLOOR AND 4 FLOOR ONE FAMILY ON EACH FLOOR 1ST FL OFFICE BUILDING OCCUPIES AT 1ST FLNothing owed — awaiting certificate of correction
Primarily 3 family with 1 store or office · 1,800 sf lot · 2 FAR built · Flood zone X