ECB02/17/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER FOR SUMMONS 39128994L. OBSERVED RESIDENTIAL GAS FLEX ON COMMERCIAL LAUNDRY EQUIPMENT (6 DRYERS)., REPAIR AND/REPLACE$6K due
ECB02/17/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE) FOR SUMMONS 39128982Y. OBSERVED NO FIRE-STOPPING AT ALL HOLE PENETRATIONS THROUGH$6K due
ECB02/17/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8 (2014 CODE); 27-371; BC 1008.1.9 (2014 CODE); BC 1010.1.8 (2022 CODE); BC 1010.1.9 (2022 CODE) FOR S$6K due
ECB02/17/2026UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE FOR SUMMONS 39128987N. OBSERVED THE USE OF FLEXIBLE CORDS AS PERMANENT WIRING AT PARKING LOT, GAS ME$4K due
ECB02/17/2026FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS FOR SUMMONS 39128988P., FILE A CERTIFICATE OF CORRECTION$1K due
ECB02/17/2026FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS FOR SUMMONS 39128985J., FILE A CERTIFICATE OF CORRECTION$1K due
ECB11/10/2025OBSERVED IN BASEMENT FERNCO COUPLINGS AND PVC WASTE LINES. IN BOILER ROOM INSTALLED SPRINKLER HEAD BACKWARDS AND USING UNIONS ON GAS LINES. IN LAUNDRY ROOM USING BUSHING AND LACK SUPPORT ON GAS LINE. ON FIRST F$6K due
ECB11/10/2025FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. OBSERVED SECURITY DESK AND CHAIR OBSTRUCTING PASSAGEWAY. LOCATE IN MAIN LOBBY AREA. POTENTIAL FIRE HAZARD., REMOVE OBSTRUCTION$6K due
ECB11/10/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED EXCESSIVE STORAGE IN BOILER ROOM. (BICYCLE, RADIO, TOOL BOX, BOXES) POTENTIAL FIRE HAZARD., REPAIR AND/REPLACE$12K due
HPD05/27/2025§ 27-2056.7 ADM CODE: CORRECT FAILURE TO PROVIDE TO THE DEPARTMENT WITHIN 45 DAYS OF DEMAND ALL RECORDS REQUIRED TO BE MAINTAINED BY OWNER PURSUANT TO LOCAL LAW 1 OF 2004 RELATED TO LEAD-BASED PAINT NOTICES, INSPECTIONS AND REMEDIATION/ABATEMENT ACTIVITIES.
DOB12/01/2024FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
ECB10/30/2024I OBSERVED IN THE GAS METER ROOM, THE LAUNDRY ROOM, THE BOILER ROOM AND THE EXTERIOR PARKING LOT, THE USE OF FLEXIBLE CORDS AS PERMANENT WIRING. EC 400.8 PROHIBITS THIS. ALSO NOTED THE FAILURE TO SUPPORT BOXES$8K due
ECB10/30/2024I OBSERVED THE GROUND CONDUCTOR AND CLAMP NOT SECURELY ATTACHED TO THE WATER MAIN TO PROVIDE GROUND PROTECTION FOR THE MAIN ELECTRICAL SERVICE. PHOTOS TAKEN., PROPERLY INSTALL GROUND ELECTRODE CONDUCTOR; PROPER$24K due
ECB10/30/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVED HOLE PENETRAIONS THROUGHOUT BUILDING. INCASE OF EMERGENCY THIS CREATES F$12K due
ECB10/30/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1 (2014 CODE); 27-371; BC 1008.1.9 (2014 CODE); BC 1010.1.8 (2022 CODE); BC 1010.1.9 (2022 CODE). OBSERV$6K due
ECB10/30/2024OBSERVED IN EXCESSIVE COMBUSTIBLE STORAGE IN THE BOILER ROOM AND ALSO IN THE GAS METER ROOM LOCATED ON THE FIRST FLOOR. AS PER E 3 OF THE FUEL GAS CODE, GAS METER ROOMS, WHEN PROVIDED, SHALL AT ALL TIMES BE KEP$3K due
ECB10/30/2024I OBSERVED ON THE ROOF, THE 2ND FLOOR PANTRY,AND STAFF BATHROOM, THE EXTERIOR FRONT AND BACK THE USE OF CONVENIENCE OUTLETS NOT OF THE GFCI TYPE NOR PROTECTED AS REQUIRED FOR OUTSIDE OUTLETS AND WITHIN 6 FT OF$10K due
ECB10/30/2024OBSERVED RESIDENTIAL GAS FLEX ON COMMERCIAL LAUNDRY EQUIPMENT ( 3 DRYERS). AS PER CHAPTER 411 OF THE FUEL GAS CODE COMMERCIAL APPLIANCES SHALL BE INSTALLED WITH RIGID PIPING., REPAIR AND/REPLACE$6K due
ECB10/30/2024FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. OBSERVED AC UNIT INSTALL INTO A ROOM BY PASSAGEWAY AT STAIRCASE, LOCATED ON 3 FLOOR. IN CASE AN EMERGENCY TRIPPING HAZARD WILL OCCUR., REMOVE OBSTRUCTION$6K due
ECB10/30/2024EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING AT UTILITY AND MECHINAL ROOMS THROUGHOUT BUILDING. IN CASE OF EMERGENCY THIS CAN CAUSE A FIRE OR HAZARDOUS SMOKE CONDITION, REPAIR/REPLACE DOOR$3K due
ECB10/30/2024OBSERVED NEWLY INSTALLED 4 INCH AND 2 INCH PVC PIPING IN GAS METER ROOM LOCATED ON THE FIRST FLOOR. NO PERMITS ON FILE AT THE DOB FOR THIS APPLICATION., OBTAIN ALL PERMITS$1K due
ECB10/30/2024OBSERVED NO VENTILATION IN THE GAS METER ROOM. AS PER E 4 OF THE FUEL AS CODE GAS METER ROOMS SHALL BE PROPERLY VENTED., REPAIR AND/OR REPLACE$3K due