DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB09/23/2024VIOLATION ISSUED-FAILURE TO FILE 2023 EXTERNAL LOW PRESSURE INSPECTION
DOB09/23/2024VIOLATION ISSUED-FAILURE TO FILE 2023 EXTERNAL LOW PRESSURE INSPECTION
ECB09/06/2023GOVERNAL BOILER 190,000BTU IS UNUSED AND NOT LEGALLY ABANDONED;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTION$500 due
ECB09/06/2023NO COMBUSTION AIR DUCT FROM THE OUTDOORS/INCORRECT HEATING PIPE SUPPORT/NO CHIMNEY BASE CLEANOUT/DEBRIS IN BOILER ROOM/HWH FLUES HAVE NO SUPPORT/HWH'S ARE MISSING SAFETY DISCHARGE PIPES;CORRECT VIOLATION AND SU$625 due
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
DOB03/03/2015VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2013 INSPECTION REPORT
DOB03/03/2015VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2013 INSPECTION REPORT
DOB03/01/2013VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2011 INSPECTION REPORT
DOB03/01/2013VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2011 INSPECTION REPORT
DOB12/13/2011VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2010 INSPECTION REPORT
DOB12/13/2011VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2010 INSPECTION REPORT
DOB12/31/2009V-DOB VIOLATION - ACTIVE
DOB12/31/2009V-DOB VIOLATION - ACTIVE
HPD01/06/2006SECTION 27-2005 ADMIN. CODE: REPLACE WITH NEW THE MISSING GLASS LOWER SASH WINDOW CENTER ROOM 2ND. STORY APT.
HPD01/06/2006SECTION 27-2038 ADMIN CODE: PROVIDE ADEQUATE LIGHTING FOR 60 WATTS 1ST. TO 2ND. STORY PUBLIC HALL.
HPD01/06/2006SECTION 27-2005 ADMIN. CODE: REPLACE WITH NEW THE BROKEN OR DEFECTIVE GLASS LOWER SASH SOUTH EAST ROOM 2ND. STY. APT.
HPD01/06/2006SECTION 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE SASHES MAKE OPERABLE UPPER AND LOWER WINDOWS FRONT ROOMS 2ND. STORY APT.
HPD01/06/2006SECTION 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR CEILING AND WALLS FRONT WEST ROOM 2ND. STY. APT.
HPD07/26/2004SECTION 27-2013 ADMIN. CODE: PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT CEILINGS THROUGHOUT, 2ND STOIRY SOUTHWEST APARTMENT.
HPD07/26/2004SECTION 27-2013 ADMIN. CODE: PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT DAMAGED BY FIRE, WALLS CEILING PRIVATE HALL 2ND STORY REAR APARTMENT.
HPD07/26/2004SECTION 27-2031 ADMIN. CODE: PROVIDE HOT WATER AT ALL HOT WATER FIXTURES KITCHEN AND BATHROOM, 2ND STORY EAST APT 2B.
HPD07/26/2004SECTION 27-2031 ADMIN. CODE: PROVIDE HOT WATER AT ALL HOT WATER FIXTURES KITCHEN AND BATHROOM, 1ST STORY EAST APT 1B.
HPD07/26/2004SECTION 27-2026 ADMIN. CODE: REMOVE ALL OBSTRUCTIONS AND REPAIR ALL DEFECTS IN WASTE LINE KITCHEN AND BATHTUB BATHROOM 2 STY. WEST APT. 1B ER-1.
HPD07/26/2004SECTION 27-2031 ADMIN. CODE: PROVIDE HOT WATER AT ALL HOT WATER FIXTURES KITCHEN AND BATHROOM 2 STY. WEST APT. 1B ER-1.
HPD07/26/2004SECTION 27-2005 ADMIN. CODE: REMOVE THE ILLEGAL FASTENING KEY ACTIVATED DOUBLE CYLINDER LOCK DOOR STREET TO BLDG. 1ST. STORY.
HPD07/26/2004SECTION 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF VERMIN MICE AND ROACHES 2 STY. WEST APT. 1B.
HPD07/26/2004SECTION 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE BELL SYSTEM ENHANCE TO 2 STY. WEST APT. 1B.
HPD07/26/2004SECTION 27-2005 ADMIN. CODE: PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR CENTER ROOM 2 STY. WEST APT. 1B.
HPD07/26/2004SECTION 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR WALLS AND CEILING EAST AND CENTER ROOMS. 2 STY. WEST APT. 1B
HPD07/26/2004SECTION 27-2005 ADMIN. CODE: PROPERLY SECURE THE LOOSE GLASS ALL SASH THROUGHOUT, 2ND STORY SOUTHWEST APARTMENT.
HPD07/26/2004SECTION 27-2024 ADMIN. CODE: PROVIDE ADEQUATE SUPPLY OF HOT WATER FOR THE FIXTURES ALL FIXTURES IN BATHROOM AND KITCHEN, 2ND STORY SOUTHWEST APARTMENT.
HPD07/26/2004SECTION 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE TOP SASH AT FRONT ROOM WINDOW, 2ND STORY SOUTH WEST APARTMENT.
HPD07/26/2004SECTION 27-2005 ADMIN. CODE: REPLACE WITH NEW THE BROKEN OR DEFECTIVE GLASS UPPER & LOWER SASHES KITCHEN BATHROOM, PRIVATE HALL 2ND STORY REAR APARTMENT.
HPD07/26/2004SECTION 27-2005 ADMIN. CODE: REPLACE WITH NEW THE BROKEN OR DEFECTIVE DAMAGED BY FIRE SKYLIGHT OVER 2ND STORY PUBLIC HALL.
HPD02/05/2004SECTION 27-2005 ADMIN. CODE: REMOVE THE TORN AND/OR LOOSE FLOOR COVERING AT BATHROOM, 2nd STORY, APARTMENT
HPD02/05/2004SECTION 27-2005 ADMIN. CODE: REPLACE WITH NEW THE BROKEN OR DEFECTIVE GASKET REFRIGERATOR LOWER DOOR IN THE KITCHEN LOCATED AT APT 2-A, 2nd STORY, APARTMENT AT NORTH
HPD02/05/2004SECTION 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF VERMIN MICE IN THE ENTIRE APARTMENT LOCATED AT APT 2-A, 2nd STORY, APARTMENT AT NORTH
HPD02/05/2004SECTION 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR CEILING AND WALLS IN THE PRIVATE HALL, SOUTHEAST ROOM AND IN THE 2nd ROOM FROM EAST AT SOUTH LOCATED AT APT 2-A, 2nd STORY
HPD02/05/2004SECTION 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF VERMIN ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 2-A, 2nd STORY, APARTMENT AT NORTH
HPD02/05/2004SECTION 27-2023 ADMIN. CODE: PROVIDE SUFFICIENT,PROPER AND SEPARATE METAL RECEPTACLES FOR THE DEPOSIT OF GARBAGE, RUBBISH AND OTHER WASTE MATERIAL AND ARRANGE FOR COLLECTION AND DISPOSAL OF SUCH MATERIAL.
HPD02/05/2004SECTION 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE GLASS UPPER SASH IN THE KITCHEN AND IN THE PRIVATE HALLWAY LOCATED AT APT 2-A, 2nd STORY, APARTMENT AT NORTH
HPD02/05/2004SECTION 27-2064 ADM CODE - PROVIDE IN ACCORDANCE WITH THE RULES AND REGULATIONS OF THIS DEPARTMENT A WATERPROOF FLOOR AND BASE FOR THE WATER CLOSET AT BATHROOM, 2nd STORY, APARTMENT
HPD01/07/2004SECTION 27-2005 ADMIN. CODE: REPAIR THE ROOF SO THAT IT WILL NOT LEAK CEILINGS IN THE ENTIRE APARTMENT LOCATED AT APT 2-R, 2nd STORY, APARTMENT AT WEST
HPD01/07/2004SECTION 27-2005 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF EXCESSIVE GAP AT ENTRANCE DOOR AND THRESHOLD IN THE ENTRANCE LOCATED AT APT 2-R, 2nd STORY, APARTMENT AT WEST
HPD01/07/2004SECTION 27-2005 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF EXPOSED ELECTRICAL WIRES AT CEILING LOOSE AND HANGING IN THE FOYER LOCATED AT APT 2R, 2nd STORY, APARTMENT AT WEST
ECB08/22/2007BQ9/B4B/38/36/50A/50B/50C/50D/50E/.50A-FLUE PIPE NOT PROPERLY SEALED CHIMNEY.50B-BOILER ROOM NOT A STORAGE ROOM.50C-PIPE BACK FLOW PREVENTORDOWN NO THREADED END.50D-PIPE SAFETY OR RELIEF VALVE DISCHARGE DOWN NONothing owed — awaiting certificate of correction
ECB08/22/2007B4B/4A/19B/36/38/22A/.50A-HOLES IN BOILER ROOM WALLS & CEILING.50B-PIPE SAFETY ON RELIEF VALVE DISCHARGE DOWN NO THREADED END.50C-REMOVE THREADED END FROM BACK FLOW PREVENTOR DISCHARGE.Nothing owed — awaiting certificate of correction
Predominantly retail with other uses · Owner of record: 1632 BROADWAY REALTYCOMPANY · 5,340 sf lot · 1.82 FAR built · Flood zone X