DOB04/20/2026EMERGENCY WORK ORDER.@CELLAR&SUBCELLAR LVLS,CRCKD WALLS &WALLS W/ MISSNG BRCKS WERE OBSRVD.CHIMNEY@ROOF NEAR THE MIDDLE OF EXP4 HAD MULT CRCKS&WAS STRAPPD.CELLAR&SUBCELLAR LVLS HAD PRE-EXISTNG.OWNR TO RTAIN NYSPE&GC REG W/DOB TO IMMED 1.NYSPE TO SUBMIT MEANS&METHDS FOR TEMP SHORNG/STBLIZTN OF CHIMNEY&SIDEWALK
DOB04/20/2026FAILURE TO MAINTAIN BLDG IN SAFE MANNER.@CELLAR&SUBCELLAR LEVELS,CRCKD WALLS&WALLS W/MISSNG BRCKS WERE OBSRVD.CHIMNEY@ROOF NEAR THE MIDDLE OF EXP4WALL HAD MULT CRCKS&WAS STRAPPED.CELLAR&SUBCELLAR.1.OWNR TO RTAIN NYSPE TO EVAL ENT STRCTRE&FILE RPAIR DWGS W/DOB, 2.BLDG TO BE PERM RPAIRD UNDR PRMT STRTNG BY 6/1/2026
DOB04/15/2026OBSERVED IN THE BASEMENT WATER LEAKING FROM SPRINKLER SYSTEM PIPE ONTO THE FLOOR
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB05/12/2025STRUCTURE RENDERED NON COMPLIANT DUE TO VEHICLE IMPACTING SHED. AT TIME OF INSPECTION THE VERTICAL POST AND I-BEAM WAS BENT KNOCKING SHED OUT OF PLUMB.
DOB09/23/2024VIOLATION ISSUED-FAILURE TO FILE 2023 EXTERNAL LOW PRESSURE INSPECTION
DOB09/18/2024FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB07/03/2024REMEDY IMMEDIATELY INSTALL 90' LINEAR FEET OFF SIDEWALK SHED AT EXPOSURE #1 CENTRE STREET. 80' LINEAR FEET OF SIDEWALK SHED AT EXPSOUR E #2 ON GRAND STREET AND 120' LINEAR FEET OF SIDEWALK SHED AT EXPOSURE #3 ON BAXTER STREET. TO PROTECT AND SECURE PUBLIC SAFETY
DOB02/12/2024V-DOB VIOLATION - ACTIVE
DOB02/12/2024V-DOB VIOLATION - ACTIVE
DOB10/04/2023FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB11/05/2022EMERGENCY WORK ORDER DUE TO MULTIPLE TWISTED I-BEAMS ON SIDEWALK SHED ON EXP3 EAST ELEVATION WITH UNSAFE CONDITION. SHED TO BE IMMED REPAIRED. REMEDY: REPAIR/REPLACE DAMAGED I-BEAMS
DOB11/04/2022FTM BLDG IN CODE COMPLIANT MANNER. OBSERVED CRACKED CHIMNEY, SEVERE SPALLING THROUGHOUT FACADE. DAMAGED CORNICE CRACKED WINDOW PANES, AND LEAKING PARAPET WALL. DEFECTIVE WINDOW LINTALS AND SILLS. SPALLING BRICK AND STONE. ALL DEFECTS ARE THROUGHOUT FACADE. REMEDY: MAINTAIN BLDG IN A CODE COMPLIANT MANNER
DOB11/18/2021VEHICLE IMPACTING SIDEWALK SHED
DOB04/07/2021V-DOB VIOLATION - ACTIVE
DOB04/07/2021V-DOB VIOLATION - ACTIVE
DOB04/15/2020V-DOB VIOLATION - ACTIVE
DOB04/15/2020V-DOB VIOLATION - ACTIVE
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB08/02/2019FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB07/24/2019FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB05/02/2019FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB03/03/2015VIOLATION ISSUED FOR FAILURE TO FILE 2013 ANNUAL HIGH PRESSURE BOILER INSPECTION
DOB03/03/2015VIOLATION ISSUED FOR FAILURE TO FILE 2013 ANNUAL HIGH PRESSURE BOILER INSPECTION
DOB11/07/2014V-DOB VIOLATION - ACTIVE
DOB05/30/2014VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
DOB05/30/2014VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
DOB03/13/2014V-DOB VIOLATION - ACTIVE
DOB05/04/2011FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB10/20/2010V-DOB VIOLATION - ACTIVE
DOB01/19/2007V-DOB VIOLATION - ACTIVE
DOB01/06/2006V-DOB VIOLATION - ACTIVE
DOB10/04/2000V-DOB VIOLATION - ACTIVE
DOB05/04/1998V-DOB VIOLATION - ACTIVE
DOB07/31/1987V-DOB VIOLATION - ACTIVE
ECB05/19/2026AT TIME OF INSPECTION OF A 6 STORIES BUILDING I OBSERVED SIDEWALK SHED IN PLACE ON EXPOSURES # 1,2,AND 3, UPON REVIEW THE DEPARTMENT RECORD TO VERIFY COMPLIANCE INSPECTION REVEALS THAT THERE IS NO PERMIT OBTAINNothing owed — awaiting certificate of correction
ECB04/15/2026OBSERVED IN THE BASEMENT WATER LEAKING FROM SPRINKLER SYSTEM PIPE ONTO THE FLOOR. SPRINKLER HEAD DAMAGED AND MISSING SPRINKLER PROTECTIVE GUARDS AROUND SPRINKLER HEADS WHICH IS CONTRARY TO CODE SECTIONS BC 101.Nothing owed — awaiting certificate of correction
ECB04/15/2026OBSERVED IN THE BASEMENT WASTE LINES ARE NOT PROPERLY CAPPED AND FERNCO COUPLINGS ARE BEING USED ON WASTE LINES. THE EJECTOR PUMP DISCHARGE LINE IS IMPROPERLY INSTALLED THE WASTE LINE REDUCED IN SIZE SMALLER THNothing owed — awaiting certificate of correction
ECB04/15/2026ISSUED NOV FAILIER TO MANTAIN FOR CHIMNEY ON ROOF WITH MAJOR CRACK AND SLIGHT DELECTION; SPRINKLER SYSTEM OFF;WATER LEAKING IN BASEMENT; EXIT DOORS SCREWED CLOSED THUS CREATING SAFETY HAZARD, REPAIR AND/REPLACENothing owed — awaiting certificate of correction
ECB04/15/2026OBSERVED OUTSIDE IN FRONT OF THE BUILDING THE FIRE DEPARTMENT CONNECTION IS TOO CLOSE TO THE STEPS. AT THE REAR SIDE OF THE BUILDING FIRE DEPARTMENT CONNECTION MISSING CAPS WHICH IS CONTRARY TO CODE SECTIONS FCNothing owed — awaiting certificate of correction
ECB04/15/2026OBSERVED THROUGHOUT THE BUILDING SPRINKLER HEADS ARE OBSTRUCTED. ON THE SECOUND FLOOR THERE IS A LACK SPRINKLER COVERAGE UNDER THE MEZZANINE LEVEL IN THE NORTH SIDE APARTMENT AND NO SPINKLER COVERAGE ON SOUTH ENothing owed — awaiting certificate of correction
ECB05/12/2025TEMPORARY CONSTRUCTION EQUIPMENT ON SITE WITH EXPIRED PERMIT. AT TIME OF INSPECTION SHED INSTALLED UNDER PERMIT NUMBER M00161861-I1-SH HAS AN EXPIRED PERMIT DATE OF 12-31-2020. THERE ARE NO UPDATED PERMITS ON FNothing owed — awaiting certificate of correction
ECB04/21/2025AT TIME OF INSPECTION OF A 6 STORIES BUILDING I OBSERVED SIDEWALK SHED IN PLACE AT EXPOSURE # 1 AND 2 UPON REVIEW THE DEPARTMENT RECORD TO VERIFY COMPLIANCE IT SHOWS THAT THE SIDEWALK SHED PERMIT HAD EXPIRED SINothing owed — awaiting certificate of correction
ECB08/20/2024FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER.NOTES:MULTIPLEHAZARDOUS CONDITIONS OBSERVED BROKEN GLASS PANE.DELAMINATED/SPALLING MASONRY AT 2ND STRY AND 3RD STRY.DEFECTIVE AT 2ND STRY/CORNICE AT ROOFNothing owed — awaiting certificate of correction
ECB07/01/2024FAILURE TO MAINTAIN BUILDING FACADE IN A CODE-COMPLIANT MANNER. NOTED AT TIME OF INSPECTION, AT WEST ELEVATION EXPOSURE #1, NORTH ELEVATION EXPOSURE #2 AND EAST ELEVATION EXPOSURE #3 OBSERVED SEVERLY CRACKED MANothing owed — awaiting certificate of correction
ECB02/22/2023AT THE TIME OF MY INSPECTION OBSERVED SIDEWALK SHED AT EXP#1,2 AND 3. AFTER REVIEW DEPARTMENT RECORDS REVEALED THAT SIDEWALK SHED PERMIT EXPIRED ON 12/31/20.Nothing owed — awaiting certificate of correction
ECB02/16/2023AT THE TIME OF INSPECTION OF A 6 STORY BUILDING PARTIALLY OCCUPIED, NO CONSTRUCTION ACTIVITIES RECORDED WHILE RESPONDING TO A COMPLAINT CONCERNING UNSAFE SIDEWALK SHED I OBSERVED SHED PERMIT EXPIRED ON 12/31/2Hearing held — result not yet published
ECB11/09/2022PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATIONS. OBSERVED INADEQUATE SHED LIGHTING, DAMAGED MUD SILLS, TWISTED I-BEAMS, AND DAMAGED PARAPET WALL PANELS. REMEDY: COMPLY WITH CODE SPECIFICATIONSNothing owed — awaiting certificate of correction
ECB11/04/2022FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY.OBSERVED FIRE ESCAPE EGRESS BLOCKED BY SIDEWALK SHED DEBRIS.REMEDY:REMOVE OBSTRUCTIONNothing owed — awaiting certificate of correction
ECB11/04/2022TEMPORARY CONSTRUCTION EQUIPMENT ON-SITE EXPIRED PERMIT.PERMIT#M00161861-L1-SH EXPIRED 11/31/20.AS OF TODAY 11/04/22 NO PERMIT IN PROGRESS OR ON RECORD.REMEDY:RENEW PERMIT.Nothing owed — awaiting certificate of correction
ECB11/23/2021PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATION AT TIME OF INSPECTION ON A 6TH STY OBSERVED SIDEWALK SHED ERECTED.OBSERVED THE PARAPET WALL NOT SECURE TO THE SWS.A OPEN GAP ABOUT 3-4 INCHES AT EXPO#2 CRENothing owed — awaiting certificate of correction
ECB11/23/2021PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATION AT TIME OF INSPECTION ON A 6TH STY OBSERVED SIDEWALK SHED ERECTED AT EXPO#1.MISSING CAPS FROM THE BOLTS AT SWS CAN CREATED A HAZARDOUS CONDITION FOR PEDESTNothing owed — awaiting certificate of correction
ECB11/19/2021TEMPORARY CONSTRUCTION EQUIPMENT ONSITE WITH EXPIRED PERMIT(SWS).NOTE:AT INSPECTION OF 6 STORY ALT BLDG,NO ACTIVE WORK OBSERVED SIDEWALK SHED AT EXPOSURES 1,2&3 IN GOOD CONDITION BUT THE PERMIT NUMBER M00161861Nothing owed — awaiting certificate of correction
ECB07/03/2019FAILURE TO MAINTAIN BLDG WALLS & APPURTENANCE. NOTE: AT 6 STY BROWNSTONE ALL EXPOSURES AT 5TH & 6TH FL MISSING BRICKS & MORTAR AT ROOF LEVELSHINGLES MISSING. REMEDY: SIDEWALK SHED INSTALLED PERMIT#M00161861.Nothing owed — awaiting certificate of correction
ECB04/30/2019SIDEWALK SHED PARAPET PANEL.NOTE:AT THE TIME OF MY INSPECTION,I OBSERVED A SIDEWALK SHED ERECTED AT EXPO 1,2 AND 3.I ALSO OBSERVED THAT THERE WERE NO PARAPET PANEL INFORMATION POSTED ON TEH SIDEWALK SHED PARAPENothing owed — awaiting certificate of correction
ECB04/30/2019TEMPORARY CONSTRUCTION EQUIPMENT ON SITE NO PERMIT.NOTE:AT THE TIME OFMY INSPECTION I OBSERVED A SIDEWALK SHED ERECTED AT EXPO 1,2 AND 3.UPON REVIEW THE PERMIT VALIDITY ON THE BUILDING INFORMATION SYSTEM(BIS)ITNothing owed — awaiting certificate of correction
ECB04/21/2019FAILURE TO MAINTAIN EXTERIOR FACADE IN A CODE COMPLIANT MANNER. BROWN STONE IS FAILING,MISSING AND IN DANGER OF FALLING ON ENTIRE FACADE FRONTING CENTRE,GRAND AND BAXTER STREETS. DEFECTS ENDANGER THOUSANDS OF PNothing owed — awaiting certificate of correction
ECB02/27/2013FAILURE TO COMPLY W/COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DOB FOR NOV#34852921X ISSUED ON 11/4/11 PURSUANT TO 28-204.4 & 1RCNY 102-01.WORK W/O A PERMIT ON THE 3RD FLR.RMDY:FILE A CNothing owed — awaiting certificate of correction
ECB03/29/2011UNLAWFUL ACTS. FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER. RESPONDENT FAILED TO CORRECT THE CONDITIONS CITED IN THE PRIOR NOV #34852921X FOR WORK W/O A PERMIT @ 3RD FL COMMERCIAL SPACE UNDER RENOVATION.Nothing owed — awaiting certificate of correction
ECB01/31/2011FAILURE TO MAINTAIN BLDG IN A CODE-COMPLIANT MANNER,ILLEGAL DOOR HARDWARE. NOTED: AT FRONT ENTRANCE/EXIT DOOR A KEYED LOCK IS IN PLACE W/THEPOTENTIAL OF BEING LOCKED & NOT ABLE TO BE OPENED FROM INTERIOR.Nothing owed — awaiting certificate of correction
ECB11/04/2010UNLAWFUL ACTS. FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER IN THAT A STOP WORK ORDER HAS BEEN ISSUED & CONSTRUCTION WORK IS BEING PERFORMED W/O HAVING STOP WORK ORDER(RESIREDED). REMEDY: COMPLY W/COMMISSIONothing owed — awaiting certificate of correction
ECB11/04/2010WORK W/O PERMIT: AT 3RD FL RENOVATING COMM SPACE IN LANDMARK BUILDING NO PERMITS POSTED OR PLANS (APPROVED AT SITE. REMEDY: STOP ALL WORK & OBTAIN PERMITS.Nothing owed — awaiting certificate of correction
ECB03/02/2010FAILURE TO COMPLY W/ AN ORDER OF THE COMMS RESPONDENT FAILED TO FILE A CERT OF CORRECTION FOR #34775265Z AT 2ND FL ERECTED PARTITION & CUT WOOD FL JOISTS REM; FILE CERT OF CORRECTIONNothing owed — awaiting certificate of correction
ECB10/29/2009FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FIRE A CERTIFICATE OF CORRECTION W/DEPT OF BUILDINGS. FOR THE VIOL #34775256-2. REMEDY: COMPLY W/CODE. FIRE CERTIFICATE OF CORRECTION.Nothing owed — awaiting certificate of correction
ECB10/29/2009FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. RESPONDENT HAS FAILED TO COMPLY WITH THE CONDITIONS IN #34775265-Z. 2ND FLR N/W UNIT PARTITIONS ERECTED WOOD FLR JOINTS WERE CUT DOWN IN SIZE. SPRINKLERNothing owed — awaiting certificate of correction
ECB04/28/200942D6.42N9.58Y13.37M7.37D6.42D SECURE TIMER ON BACK OF CONTROLLER JUMPER ON 'SR RELAY 58 BEARING LEAK 37 PROVIDE SIGNAGE ON DOORNothing owed — awaiting certificate of correction
ECB04/08/2009WORK W/O A PERMIT NOTED:AT 2ND STORY NORTH WEST CORNER COMMERICIAL UNIT PARTITIONS ERECTED MEZZANINE ERECTED CEILING ALTERED 3'X17'JOISTS CUT DOWN APPROX 4" TO 3"X13" SPRINKLER HEADS REMOVED SPRINKLER SYSTEM ALNothing owed — awaiting certificate of correction
ECB12/07/2001WORK WITHOUT A PERMIT. WORK NOTED: SUBDIVIDED THIRD FLOOR INTO MEETING ROOM THREE OFFICES, TWO BATHROOMS AND A KITCHEN ETT. WITHOUT PERMIT. REMEDY: STOP ALL WORK IMMEDIATELU. OBTAIN PERMIT AND APPROVALS FROM BNothing owed — awaiting certificate of correction
ECB04/17/199673X RESTORE TO SERVICENothing owed — awaiting certificate of correction
ECB05/16/199122Q,48T,49T,73O,08I,Nothing owed — awaiting certificate of correction