HPD07/22/2026§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL WALLS, CEILING, DOORS AND TRIM IN THE ENTIRE APARTMENT LOCATED AT APT 4I, 4th STORY, 4th APARTMENT FROM EAST AT SOUTH
HPD12/13/2025§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED AT BOILER ROOM, 1st STORY
HPD12/13/2025HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 41, 4th STORY, 4th APARTMENT FROM EAST AT SOUTH
HPD12/13/2025HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 41, 4th STORY, 4th APARTMENT FROM EAST AT SOUTH
DOB06/22/2024FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2022)
HPD11/29/2023§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT HOPPER CHUTE DOOR AT PUBLIC HALL, 6TH STORY
HPD11/29/2023§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT HOPPER CHUTE DOOR AT PUBLIC HALL, 5TH STORY
ECB01/13/2023FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 9A REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL#907837.REM:SUBMIT ACCEPTABLE REQUIRED T$1K due
HPD11/29/2022§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM LOCKED DOOR AT BOILER ROOM
HPD08/02/2022§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE ENTRANCE DOOR INTERIOR SIDE IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 6A, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''WEST''
HPD08/02/2022§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE BELL BUZZER/INTERCOM SYSTEM LEADING FROM VESTIBULE TO APT. LOCATED AT APT 6A, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''WEST''
DOB03/16/2022FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB02/22/2022FAILED TO FILE FISP CYCLE 9A TECHNICAL REPORT BY 02/21/2022
HPD01/22/2022§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED AT BOILER ROOM
HPD01/12/2022§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED AT BOILER ROOM
DOB12/22/2021FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
HPD10/01/2021§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE INOPERATIVE BELL AND RETURN BUZZER SYSTEM FROM 1ST STORY PUBLIC HALL VESTIBULE TO APT LOCATED AT APT 4I, 4th STORY
DOB06/20/2021FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2020)
DOB09/02/2020FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB09/02/2020FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB06/29/2020FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2019)
DOB12/26/2019FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB10/10/2019V-DOB VIOLATION - ACTIVE
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
HPD05/07/2019§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM BOILER ROOM LOCKED AT BASEMENT
DOB03/18/2019FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2018)
HPD09/21/2018§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING INSIDE CLOSET AT EAST IN THE 2nd ROOM FROM EAST AT SOUTH LOCATED AT APT 6A, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT WEST
HPD09/21/2018§ 27-2005 HMC:TRACE AND REPAIR THE SOURCE AND ABATE THE NUISANCE CONSISTING OF MOLD ... AT BASEBOARD / WOOD FLOOR ( 1 SQ FT ) BELOW 1ST CLOSET DOOR AT WEST IN THE PRIVATE HALLWAY LOCATED AT APT 6A, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT WEST
HPD09/21/2018§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK ABOVE THE CEILING IN THE 3rd ROOM FROM EAST AT SOUTH LOCATED AT APT 6A, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT WEST
HPD09/21/2018§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE HEADER RECESS TO WINDOW AT WEST IN THE 3rd ROOM FROM EAST AT SOUTH LOCATED AT APT 6A, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT WEST
HPD09/21/2018§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE 3rd ROOM FROM EAST AT SOUTH LOCATED AT APT 6A, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT WEST
HPD08/27/2018§ 27-2005 HMC:TRACE AND REPAIR THE SOURCE AND ABATE THE NUISANCE CONSISTING OF MOLD ... AT WEST WALL ( APPRX 2 SQ FT ) IN THE PRIVATE HALLWAY LOCATED AT APT 6A, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH
DOB04/06/2018VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2016 INSPECTION REPORT
DOB04/06/2018VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2016 INSPECTION REPORT
DOB03/27/2018FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2017)
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
DOB08/02/2017FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB02/24/2017VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2015 INSPECTION REPORT
DOB02/16/2017FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 IN 2016
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB05/30/2014VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
DOB01/31/2013FAILED TO FILE FISP CYCLE 7A TECHNICAL REPORT BY 02/21/2012
DOB05/03/2012FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
HPD12/16/2008§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) SOUTH WALL, 1st WINDOW FRAME FROM NORTH AT EAST WALL IN THE 1st BATHROOM LOCATED AT APT 5H, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD06/02/2008§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) NORTH WALL, EAST WALL IN THE BATHROOM LOCATED AT APT 1A, 1st STORY, 3rd APARTMENT FROM EAST AT SOUTH
DOB11/30/2007V-DOB VIOLATION - ACTIVE
DOB01/31/2005V-DOB VIOLATION - ACTIVE
DOB08/08/2002V-DOB VIOLATION - ACTIVE
ECB02/24/2022CLASS 1 VIOLATION ISSUED, / RTS, RECURRING , UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT-OF-SERVICE CREATING A HAZARDOUS CONDITION AS PER 1RCNY 11-02, REMEDY; RESTORE TO SERVICE IMMEDIATELY AND, NOTIFY NYCDONothing owed — awaiting certificate of correction
ECB11/17/2021CLASS 1 VIOLATION ISSUED RTS UPON INSPECTION THE DEVICE IS FOUND TO BE OUT-OF-SERVICE AS PER 1RCNY 11.02 RESTORE TO SERVICE IMMEDIATELY AND NOTIFY NYCDOB THE DEVICE HAS BEEN RETURNED TO SERVICE.Nothing owed — awaiting certificate of correction
ECB09/14/2021CLASS 1 VIOLATION ISSUED AS PER BC3001.2&27-987. DOB RECORDS SHOW THE ONLY ELEVATOR IN BUILDING AS ACTIVE, UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT-OF-SERVICE CREATING A HAZARDOUS CONDITION PER 1RCNY 11-0Nothing owed — awaiting certificate of correction
ECB05/21/2020CLASS 1 ITEMS. NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY; FILE APPLICATIONNothing owed — awaiting certificate of correction
ECB01/28/2020CLASS 1= NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER ,REMEDY; FILE APPLICATION,/ CLASS 2, IN CAR PHONE NOT WORKINGNothing owed — awaiting certificate of correction
ECB10/04/2019CEASE USE =05-H-10,02-X-10,39-O-02,59-BB-07,45-M-13,100-M-07=ONE CEASE USE ITEM 05-A-# REPAIR CAR DOOR RESTRUCTRO CONTATC NYC DOB FOR RESTORE TO SERVICE RE-INSPECTION (2) -02-X# NYC DOB RESTORE TO SERVICE RE-INNothing owed — awaiting certificate of correction
ECB08/05/201939-O-02, 100-M-07, 45-M-13, 59-BB-07, 15-M-07, 64-M-07, 02-X-10, 05-E-10. 39-O #CLEAN CAR TOP. 100-M #PROVIDE COVER ON TOP OF CONTROLLER FORHEALTH REGISTOR. 45-M #PROVIDE LED SEAL, 59-BB# PROVIDE NEW TAG,Nothing owed — awaiting certificate of correction
ECB02/11/201914O02,39O02,41M07,56Y13,67X10,70O02,80B07. 14O02-CAR MIRROR DIRTY, CLEAN; 39O02-CAR EXCESSIVELY DIRTY WITH OIL CLEAN;41M07-MOTOR ROOM DOOR SIGN MISSING PROVIDE; 56Y13-HOIST MACHINE LEAKING OIL SEAL; 67X10-PHONNothing owed — awaiting certificate of correction
ECB03/22/2016FAILURE TO MAINTAIN EXTERIOR BLDG EAST ELEVATION,EXP#3 OBSERVE CRACKS,DETERIORATING & BUGLING IN MASONRY STUCCO FRAME.(SOUTH END).SOUTH ELEVATION,EXP#4 OBSERVE BENDING & DETERIORATING IN LINTEL FACADE ON THE 2NNothing owed — awaiting certificate of correction
ECB08/17/2015FAILURE TO MAINTAIN EXTERIOR BLDG.WEST ELEV.EXP.1 PARAPET HORIZONTAL CRACKS MISSING.MORTAR STONE BAN CRACKED AND CHIPPED ABOVE 6FL BELOW 6TH FL-5TH FL,WOOD UNDER A/C CRACKED SILLS FLS,55,44 FLOWERS ON 1ST FLOORNothing owed — awaiting certificate of correction
ECB02/17/2011FAILURE TO MAINTAIN EXTERIOR BLDG.NOTED:IMPROPERLY INSTALLED WINDOW A/C'S W/ BRICKS & WOOD ON SILLS @ ALL 4 ELEVATIONS.EXPOSURE#1 (WEST ELEVATION)MORTAR KOINT UNDER 4 FLR MASONRY MEDALLION IS PROJECTING OVER SINothing owed — awaiting certificate of correction
ECB12/29/2008FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER UPON INSPECTION I OBSERVED ROOF DRAIN NOT COLLECTING STORM WATER PROPERLY WITNESSED WATER SEALING AROUND DRAIN OPENING ON ROOF REMEDY: REPAIR AND OR REPLACENothing owed — awaiting certificate of correction
ECB04/01/200326Q07-03O02-80B11-39G12-62O02-60L12. 03-TOP OF CAR, 80-B-11 ROSTTE MUST COMPLY WITH RULE 212.9F ANSI A17.1 1987 39 FUSE JUMPED.Nothing owed — awaiting certificate of correction