ECB04/06/2026FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES. NOTED:AT EXP 1(W. ELEV) OBSERVED HAIRLINE CRACKS BETWEEN 1ST FLOOR AND 4TH FLOOR. THESE CONDITIONS EXISTED ON ECB VIO #35689664N DATED ON 01/25/20$5K due
ECB04/06/2026FAILURE TO MAINTAIN/PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTED: OBSERVED AT EXP 1(W. ELEV) AND EXP 4(S. ELEV). OBJECTS ARE ON FIRE ESCAPES.ALSO OBSERVED AC UNITS ARE BLOCKING FIRE ESCAPES AT MULTIPLE LOCATIONS$2K due
HPD12/13/2025§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM BOILER ROOM LOCKED AT BASEMENT
HPD04/27/2025§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF INSTALLED SCREWS AND BRACKET PREVENTING THE LOWER SASH WINDOW FROM OPENING AT PUBLIC HALL, 1st STORY
HPD04/27/2025§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF PLEXIGLASS INSTALLED ABOVE THE 1ST UPPER SASH WINDOW AT THE EAST WALL (NEXT TO THE ELEVATOR) AT PUBLIC HALL, 1st STORY
HPD12/13/2024§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING CONSISTING OF PANIC PUSHBAR INSTALLED ON ROOF DOOR THAT DOES NOT ALLOW RE-ENTRY FROM ROOF TO BULKHEAD AT 6TH STORY AT PUBLIC HALL
DOB09/18/2024FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
HPD05/15/2024§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING APPROXIMATELY 20 SQ.FT IN THE BATHROOM LOCATED AT APT 4A, 4th STORY, 3rd APARTMENT FROM EAST AT SOUTH
DOB10/04/2023FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB10/04/2023FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB07/31/2018FAILED TO FILE FISP CYCLE 8B TECHNICAL REPORT BY 02/21/2018
DOB02/24/2017VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2015 INSPECTION REPORT
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB06/01/2016FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB03/31/2014VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2012 INSPECTION/TEST
DOB12/13/2011VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2010 INSPECTION/TEST
HPD07/03/2008§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) CEILING, SOUTH WALL IN THE BATHROOM LOCATED AT APT 4F, 4th STORY, 3rd APARTMENT FROM SOUTH AT WEST
HPD07/03/2008§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) CEILING, 1st WALL CABINET FROM NORTH AT EAST WALL IN THE 1st KITCHEN FROM NORTH AT WEST LOCATED AT APT 4F, 4th STORY, 3rd APARTMENT FROM SOUTH AT WEST
DOB11/30/2007V-DOB VIOLATION - ACTIVE
DOB07/26/2007V-DOB VIOLATION - ACTIVE
ECB08/07/2025CLASS 1 RTS:FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE ONLY DEVICE IN THE BUILDING IS FOUND TO BE INOPERATIVE, CREATING A HANothing owed — awaiting certificate of correction
ECB07/17/2025FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS FOR VIOLATION #39136614K ISSUED ON 1/27/2027 FTM FOR EXIT SIGN NOT ILLUMINATED AT EXIT LEADINNothing owed — awaiting certificate of correction
ECB07/17/2025FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER NOTED AT TIME OF INSPECTION AT BASEMENT OBSERVED ILLEGAL STORAGE IN GAS METER ROOMS AND ELECTRICAL ROOM CONSISTING OF HOUSEHOLD ITEMS AND CONSTRUCTION MATNothing owed — awaiting certificate of correction
ECB03/25/2025RESPONDING TO A 311 COMPLAINT. UPON INSPECTION, DEVICE IS FOUND NOT WORKING, UNDER CEASE USE ORDER, AND NOT LIFTED,CEASE USE ISSUED FOR, RECURRING CONDITIONS.REMDY; REPAIR THEN CONTACT NYCDOB FOR RE- INSPECTIONNothing owed — awaiting certificate of correction
ECB02/05/2025CEASE USE ITEM 1: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE, CALL OR EMAILTHE D.O.B. EIR@BUILDINGS.NYC.GOV. ELEVATOR DIVISION AT (212)Nothing owed — awaiting certificate of correction
ECB01/27/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1 (2014 CODE); 27-381; BC 1008.1 (2022 CODE). NOTED BASEMENT LEVEL EMERGENCY LIGHTNothing owed — awaiting certificate of correction
ECB01/27/2025FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED ILLEGAL STORAGE IN MAIN GAS METER ROOM, FURNITURE, CLOTHING, MATTRESSES, APPLIANCES, PAPERS ETC. GAS METER ROOM BY ELEVATOR HAS STORAGE OF PAINT & FUNothing owed — awaiting certificate of correction
ECB01/25/2025FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES. NOTE: AT THE TIME OF INSPECTION OBSERVED(1) CRACKED WINDOW GLASS AT EXP #1(WEST ELEV.) ALSO CRACKED FACADE BRICKS BETWEEN 1ST AND 4TH FLOOR. (2)SPNothing owed — awaiting certificate of correction
ECB05/13/2024RESPONDING TO 311 ELEVATOR COMPLAINT, UPON INSPECTION OF SINGLE CAR BUILDING, VIOLATION WAS ISSUED AS A CLASS 1 FOR MISSING DLM IN CONTROLLER, REMEDY; FILE APPLICATION WITH NYCDOB THEN INSTALL THE FILE TEST WITNothing owed — awaiting certificate of correction
ECB08/23/2023FAILURE TO CERTIFY: FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS FOR NOV 38274376N. REMEDY: FILE CERTIFICATE OF CORRECTION.Nothing owed — awaiting certificate of correction
ECB07/10/2023GAS BEING SUPPLIED TO BUILDING WITHOUT INSPECTION AND CERTIFICATION BY DOB. GAS BEING SUPPLIED TO BUILDING W/O INSPECTION/CERTIFICATION BY D.O.B. NOTE GAS SUPPLIED TO BSMT DRYERS, NO INSPECTION ON FILE FOR THISNothing owed — awaiting certificate of correction
ECB06/28/2023RESPONDING TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION OF DEVICE VIOLATION WAS FOUND ITEMS ARE,/ NO DOOR LOCK MONITORING WAS INSTALL IN CONTROLLER, REMEDY; FILE APPLICATION THEN INSTALL DEVICE THEN FILE TEST WNothing owed — awaiting certificate of correction
ECB05/05/2023CONTRARY TO DOB/OFFICIAL RECORDS WHICH INDICATES CLASS 'A' APTS THROUGHOUT: AT TIME OF INSPECTION - 5TH FLR APT 5E WAS OBSERVED CREATED & OCCUPIED AS 3 SRO'S/ A B-UNIT APT WITH SHARED KITCHEN & BTHRM. EACH SLEENothing owed — awaiting certificate of correction
ECB03/23/202242M07: 42-M-07 NO DOOR LOCK MONITORING INSTALLED IN CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF 2014 N.Y.C BUILDING CODE. REMEDY: FILE APPLICATION & INSTALLNothing owed — awaiting certificate of correction
ECB03/16/2014FAIL MAINTAIN BLDG IN COMPLIANT MANNER:INSTALL/MAINTAIN PLUMBING EQUIP.NOTE:DRYERS INSTALLED W/RESIDENTIAL COOKING FLEX CONNECTIONS.DRYERS MUST BE PIPED W/SCH 40 STEEL PIPING.REM:REMOVE NON-COMPLYING MATERIALSNothing owed — awaiting certificate of correction