DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
ECB09/02/2021BURNHAM IN7 FTM MISSING PIPE INSULATION INCORRECT HEADER INSTALLATION MISSING MANUAL RESET LWCO & PRESSURE CONTROL MISSING SIPHON ON STEAM GAUGE CAN NOT FEED DIRECTLY INTO BOILER (2014 TAG ON BOILER=UNREGISTERE$3K due
DOB10/01/2015VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2014 INSPECTION REPORT
HPD02/07/2012SECTION 27-2005 ADMIN. CODE: PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WINDOW SILL AT FRONT YARD , 2nd STORY
HPD06/17/2009SECTION 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 4R, 4th STORY, APARTMENT AT SOUTH
DOB01/01/2009V-DOB VIOLATION - ACTIVE
HPD09/07/2008SECTION 27-2018 ADM CODE ABATE THE NUISANCE CONSISTING OF VERMIN ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT BSMT, 1st APARTMENT FROM EAST AT SOUTH
HPD09/07/2008SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILINGS IN THE ENTIRE APARTMENT LOCATED AT APT BSMT, 1st APARTMENT FROM EAST AT SOUTH
HPD09/07/2008SECTION 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT SINK IN THE KITCHEN LOCATED AT APT BSMT, 1st APARTMENT FROM EAST AT SOUTH
HPD09/07/2008SECTION 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE GLASS AT LOWER SASH WINDOW IN THE 2nd ROOM FROM NORTH LOCATED AT APT BSMT, 1st APARTMENT FROM EAST AT SOUTH
HPD09/07/2008SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR WALLS IN THE ENTIRE APARTMENT LOCATED AT APT BSMT, 1st APARTMENT FROM EAST AT SOUTH
HPD09/07/2008SECTION 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE SPRINKLER HEAD IN THE KITCHEN LOCATED AT APT BSMT, 1st APARTMENT FROM EAST AT SOUTH
HPD09/07/2008SECTION 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE ELECTRICAL OUTLET AT WEST WALL IN THE KITCHEN LOCATED AT APT BSMT, 1st APARTMENT FROM EAST AT SOUTH
HPD09/07/2008SECTION 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE 2nd ROOM FROM NORTH LOCATED AT APT BSMT, 1st APARTMENT FROM EAST AT SOUTH
HPD09/07/2008SECTION 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE ELECTRICAL LIGHT SWITCH AT NORTH WALL IN THE 2nd ROOM FROM NORTH LOCATED AT APT BSMT, 1st APARTMENT FROM EAST AT SOUTH
HPD09/07/2008SECTION 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE ELECTRICAL OUTLET AT SOUTH WALL IN THE 2nd ROOM FROM NORTH LOCATED AT APT BSMT, 1st APARTMENT FROM EAST AT SOUTH
HPD09/07/2008SECTION 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE MARBLE SADDLE AT DOOR TO REAR YARD IN THE 2nd ROOM FROM NORTH LOCATED AT APT BSMT, 1st APARTMENT FROM EAST AT SOUTH
HPD09/07/2008SECTION 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE ELECTRICAL LIGHT SWITCH AT WEST WALL IN THE BATHROOM LOCATED AT APT BSMT
HPD09/07/2008SECTION 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILES AT FLOOR IN THE BATHROOM LOCATED AT APT BSMT
HPD09/07/2008SECTION 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CONCRETE FLOOR AT DOOR IN THE ENTRANCE LOCATED AT APT BSMT
HPD09/07/2008SECTION 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING DOUBLE CYLINDER KEY OPERATED LOCK AT METAL DOOR IN THE ENTRANCE LOCATED AT APT BSMT
HPD09/07/2008SECTION 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT BSMT, 1st APARTMENT FROM EAST AT SOUTH
DOB01/25/2005V-DOB VIOLATION - ACTIVE
HPD03/15/2001SECTION 27-2050 ADM CODE PROVIDE AN ANGLE HOSE VALVE OR SILL COCK AT EXTREME END OF HIGHEST LINE OF SPRINKLERS. AT PUBLIC HALL, 1st STORY
HPD03/15/2001SECTION 27-2050 ADM CODE PROVIDE 3 EXTRA SPRINKLER HEADS AND SUITABLE WRENCH FOR EMERGENCY PURPOSES AT O.S.Y. VALVE OF SPRINKLER IN ACCORDANCE WITH THE RULES AND REGULATIONS OF THIS DEPARTMENT .. AT METER ROOM, CELLAR
HPD03/15/2001SECTION 27-2050 ADM CODE SEAL IN OPEN POSITION THE O.S.Y. VALVE OF THE SPRINKLER SYSTEM IN ACCORDANCE WITH THE RULES AND REGULATIONS OF THIS DEPARTMENT .. AT METER ROOM, CELLAR
HPD03/15/2001SECTION 27-2050 ADM CODE PROVIDE A PIECE OF GARDEN HOSE 10 FEET IN LENGTH WITH FEMALE COUPLING AND A 10 QUART PAIL ON PREMISES TO TEST SPRINKLER SYSTEM. AT PUBLIC HALL, 1st STORY
DOB08/16/1993V-DOB VIOLATION - ACTIVE
HPD06/08/1987D26-10.01 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE PAVING FRONT SOUTH COURT TO BLDG.
HPD11/23/1984D26-17.10 ADM CODE PROVIDE READY ACCESS TO BUILDING'S HEATING SYSTEM CELLAR DOOR LOCKED.
HPD11/23/1984D26-21.03 ADM CODE PAINT OR POST A SIGN INDICATING FLOORS ON WALLS AT OR NEAR STAIRS ALL STYS PUBLIC HALL.
HPD11/23/1984D26-17.10 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDING'S HEATING SYSTEM 1 STY PUBLIC HALL AND ON BOILER ROOM DOOR.
HPD04/13/1982D26-10.01 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR THE CEILING 2ND STY NORTH APT 2-F BATHROOM. , SECTION '' ''
HPD10/19/1981D26-10.01 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE SAGGING WOOD FLOOR BASEMENT APT 1 FRONT TO REAR. LOCATED AT APT 1
HPD10/19/1981D26-10.01 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE PLASTERBOARD CLG CELLAR THROUGHOUT.
HPD10/19/1981D26-10.01 ADM CODE MAKE SAFE BY PROPERLY REPAIRING THE STRUCTURAL DEFECT SAGGING SUPPORT BEAMS CELLAR CLG FRONT TO REAR.
HPD10/19/1981D26-10.01 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE PAVING CELLAR REAR WEST.
HPD04/10/1974SECTION 65 M/D LAW PROVIDE UNDER COMPLETED PERMIT, A PROPER ENCLOSURE FOR THE CENTRAL HEATING PLANT, CELLAR CENTER.
HPD07/14/1972D26-10.01 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDED CEILING OF CELLAR CENTER.
HPD07/14/1972D26-21.07 ADM CODE PROVIDE A PIECE OF GARDEN HOSE 10 FEET IN LENGTH WITH FEMALE COUPLING AND A 10 QUART PAIL ON PREMISES TO TEST SPRINKLER SYSTEM.