ECB10/20/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVED HOLE PENATRATIONS. LOCATED AT BASEMENT LEVEL. HOLE ABOVE COMPACTOR TUNNENothing owed — awaiting certificate of correction
ECB10/20/2025WEIL MCLAIN BOILER MODEL- EG65. CEILING INSULATION IS HANGING ON TOP OF BOILER. REPLACE INSULATION.Nothing owed — awaiting certificate of correction
ECB11/21/2024EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING DOORS AT BASEMENT LEVEL AND ROOF LEVEL. POTENTIAL FIRE OR SMOKE HAZARD., REPAIR/REPLACE DOORNothing owed — awaiting certificate of correction
ECB11/21/2024I OBSERVED IN THE FIRST FLOOR MAINTENANCE ROOM NO GFCI PROTECTION WITHIN 6 FEET OF A SINK., INSTALL GFC1 PROTECTION; PROVIDE GFCI PROTECTION.Nothing owed — awaiting certificate of correction
ECB11/14/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVED HOLE PENETRAIONS IN HALLWAY AT ROOF LEVEL AND THROUGHOUT BASEMENT. POTENNothing owed — awaiting certificate of correction
ECB01/02/2024UNLAW ACTS: FAILURE TO COMPLY WITH COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39076993H ISSUED ON 01/04/2023 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01., COMPLY WITHNothing owed — awaiting certificate of correction
ECB04/27/2023I OBSERVED IN THE MAINTENANCE CLOSET THE RECEPTACLE WITHIN 6 FEET OF THE SINK NOT OF THE GFCI TYPE., INSTALL GFC1 PROTECTIONNothing owed — awaiting certificate of correction
ECB01/10/2023OBSERVED GAS PIPING IN BASEMENT HAS AREAS OF RUST AND CORROSION., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB01/10/2023OBSERVED EXCESSIVE COMBUSTIBLE STORAGE IN THE BOILER LOCATED IN THE BASEMENT, NO STORAGE SHALL BE STORED IN THE BOILER ROOM., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB01/10/2023OBSERVED: AT CELLAR LEVEL, BOILER ROOM, CEILING DOES NOT MEET TECHNICAL SPECIFICATIONS AND FIRE DEPARTMENT REQUIREMENTS.(INSULATION EXPOSED WITHOUT FIRE PROTECTION), REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB01/10/2023OBSERVED: AT CELLAR LEVEL, FRONT EXIT DOOR AND FIRST FLOOR MAIN ENTRANCE DOOR DO NOT CLOSE PROPERLY WHEN INSPECTED., REPAIR/REPLACE DOORNothing owed — awaiting certificate of correction
ECB01/10/2023OBSERVED: AT ROOF LEVEL, STAIRCASE EXTERIOR WALLS CRACKED NEAR EXIT DOOR, MAINTAIN EXTERIOR BUILDING WALLNothing owed — awaiting certificate of correction
ECB01/04/2023OBSERVED: AT CELLAR LEVEL, EXIT PASSAGEWAY FROM BOILER ROOM TO THE FRONT IS BEING OBSTRUCTED BY FLAMMABLE MATERIALS, SUCH AS WOOD DOORS, CARTON BOARD BOXES, EQUIPMENT AND OTHER MATERIALS. ALSO, SEVERAL WINDOWSNothing owed — awaiting certificate of correction
ECB11/05/2021FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.LACK OF EMERGENCY LIGHTING FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-542.OBSERVED 6 STORY BUILDING WITH FRONT AND BACK EXITS W/O EMERGNothing owed — awaiting certificate of correction
ECB10/15/2021INSULATION ON THE BOILER ROOM CEILING IS LOOSE AND FALLING/FRESH AIR LOUVER IS 1/2 CLOGGED;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB03/22/2019FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES NOTED: OBSERVED HORIZONTAL CRACKS AND BULGIN CEMET ALONG THE LENGTH OF THE RETAINING WALL AT FRONT OF BUILDINGS SOUTH ELEVATION (EXP1).RMDY: MAINTAIN EXTERNothing owed — awaiting certificate of correction
ECB09/28/2018FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED:AT BULKHEAD EXTERIOR, ABOVE BULKHEAD EXIT DOOR, BRICKS ARE LOOSE AND MORTAR MISSING. ALSO AT FRONT AREAWAY BELOW BUILDING ENTRANCE STAIRS, RETAININGNothing owed — awaiting certificate of correction
ECB09/14/2018EC250.53 WATER METER JUMPER IS MISSING. OBSERVED THE FOLLOWING VIOLATING CONDITION IN THE CELLAR. WATER METER JUMPER (MAIN GROUNDING JUMPER) MISSING; NOT INSTALLED. REM: COMPLY WITH EC CODE.Nothing owed — awaiting certificate of correction
ECB06/27/201850A-F. AS PER CLASS 2(B254)28-301.1. FAILURE TO MAINTAIN. (50A)SAFETY VALVE FOR HEATING BOILER LEAKING.(50B)HOT WATER PIPING NOT CAPPED.(50C)NO PROVING SWITCH INSTALLED ON MOTORIZED FRESH AIR DAMPERS.(50D)DRAINNothing owed — awaiting certificate of correction
ECB04/20/20185 - FOUND HYDROTHERM BOILER MODEL MR500BP 500,000 BTUS WITH DEFECTS TOBACKFLOW. CORRECT ANY OTHER VIOLATIONS AND SUBMIT A CERTIFICATE OF CORRECTION.Nothing owed — awaiting certificate of correction
ECB03/23/2018FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NO FIRE STOPPINGPER BC712.3;27-345.NOTED:OBSERVED AT CELLAR WITHIN BOILER-ROOM-THERE IS AN APPROX 12 INCH X 16 INCH HOLE IN THE CONCRETE CEILING NEAR EXPANSNothing owed — awaiting certificate of correction
ECB03/23/2018FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES.NOTED:OBSERVED ATFRONT OF BUILDING THE RETAINING WALL HAS CRAKCS ALONG THE ENTIRE LENGTH OF WALL,SPALLING AND BULGING CONCRETE NEXT TO STAIRS TO CELLAR AND GNothing owed — awaiting certificate of correction
ECB03/23/2018FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:(INTERIOR)NOTED:OBSERVED AT ROOF AND STAIR BULKHEAD-SPALLING AND BULGING PLASTER AROUND THE SKYLIGHT DUE TO WATER PENETRATION.REM:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB03/23/2018FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:OBSERVED AT REAR OF BUILDING FIRE ESCAPE DROP LADDER HAS COME OFF OF THE TWO(2)SIDE SLIDING RAILS/GUIDE AND IS ONLY BEING SUSPENDED BY THE IRON HOOK.RNothing owed — awaiting certificate of correction
ECB08/30/2017FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED IN BSMT ANUNSERVICEABLE ELECTRICALLY POWERED GARBAGE COMPACTOR.MECHANICAL PARTS & ELECTRICAL COMPONENTS ARE EXTREMELY CORRODED DUE TO LACK OF MAINTENANothing owed — awaiting certificate of correction
ECB08/22/2017FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: OBSERVED AT ROOF BULKHEAD, CEILING AROUND SKYLIGHT HAS SPALLING PLASTER DUE TO WATER PENETRATION. REM: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB08/22/2017FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED: OBSERVED AT FRONT OF BUILDING, RETAINING WALL HAS A CRACK ACROSS THE LENGTH OF THE ENTIRE WALL. REM: MAINTAIN EXTERIOR BUILDING WALL.Nothing owed — awaiting certificate of correction
ECB08/22/2017FGC 411.1 RESIDENTAIL GAS FLEX USED ON COMMERCIAL EQUIPMENT.OBSERVED ON 08/22/2017 @ABOVE ADDRESS RESIDENTAIL GAS FLEX USED ON COMMERCIAL LAUNDRY EQUIPMENT.COMPLY W/SUMMONS.Nothing owed — awaiting certificate of correction
ECB03/27/2017SEC. 408.2 DRIPS FUTURE CONNECTION EXIST DOWN STREM OF APPLICANCE. OBSERVED ON 3-27-17 IN BASEMENT/CELLAR FUTURE GAS CONNECTION IN COMPACTOR ROOM. REMEDY: COMPLY W/SUMMONS.Nothing owed — awaiting certificate of correction
ECB03/27/2017SEC. 401.1 GAS PIPING NOT LABELED OBSERVED ON 3-27-17 IN BASEMENT/CELLAR GAS PIPING NOT LABELED. REMEDY: COMPLY W/SUMMONS.Nothing owed — awaiting certificate of correction
ECB03/27/2017FAIL TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 3-27-17 JIM CAPS INSTALLED IN BOILER AREA. REMEDY: REMOVE ALL NON COMPLYING MATERIAL OR EQUIPMENT.Nothing owed — awaiting certificate of correction
ECB09/16/2016FAILURE TO MAINTAIN IN CODE COMPLIANT MANNER. DEFECTS NOTED:RETAINING WALL AT FRONT OF PREMISES HAS APPRX 2"WIDE HORIZONTAL CRACK ALONG THE LENGTH OF THE WALL.RMDY:COMPLY WITH NOTICE OF VIOLATION.Nothing owed — awaiting certificate of correction
ECB09/16/2016FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.DEFECT NOTE:APPROXIMAELY 9SF AREA CEILING MISSING AT 1ST FLR LOBBY. RMDY:REPAIR AND/OR REPLACE CEILING.Nothing owed — awaiting certificate of correction
ECB09/16/2016EXIT DOOR NOT SELF-CLOSING THE FOLLOWING DOORS NOT SELF-CLOSING.EXIT DOOR TO ROOF LEVEL, ELECTIRC/GAS METER ROOM DOOR AT CELLAR LEVEL.RMDY:REPAIR/REPLACE DOORS.Nothing owed — awaiting certificate of correction
ECB09/16/2016FAILURE TO HAVE NEW OR ALTERED PLY SYSTEM TESTED. OBSERVED ON 9/16/16 AT 10:15AM IN BST NEW HOT WATER STORAGE TANK AND ALL ASSOC WATER PIPING. NO DOB INSPECTIONS ON FILE FOR WORK. PHOTO TAKEN.RMDY:PERFORM INSPENothing owed — awaiting certificate of correction