HPD09/23/2026§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT 2nd COMMUNITY BATHROOM FROM EAST, 2nd STORY
HPD09/23/2026§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AT 2nd COMMUNITY BATHROOM FROM EAST, 2nd STORY
HPD09/23/2026§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT 2nd COMMUNITY BATHROOM FROM EAST, 2nd STORY
ECB01/08/2026ACCESS GRANTED. NO CERTIFICATE OF CORRECTION ON FILE FOR CLASS 1 VIOLATION #39151203L ISSUED 6/16/2025. ALTHOUGH THE VIOLATING CONDITION INVOLVING STORAGE ITEMS UNDER THE STAIRCASE HAS BEEN REMOVED, THE VIOLATI$1K due
ECB01/08/2026ACCESS GRANTED, NO CERTIFICATE OF CORRECTION ON FILE FOR CLASS 1 AGGRAVATED VIOLATION #39114531H ISSUED 5/16/2024. OBSERVED SAFETY SYSTEM ROOFTOP GENERATOR NOW REPAIRED., FILE A CERTIFICATE OF CORRECTION$1K due
ECB01/08/2026ACCESS GRANTED. NO CERTIFICATE OF CORRECTION ON FILE FOR CLASS 1 AGGRAVATED VIOLATION #39151201H ISSUED 6/16/2025. FIRESTOPPING HAS BEEN COMPLETED AND PLASTIC PANELS REMOVED; NO VIOLATING CONDITIONS OBSERVED.,$1K due
ECB01/08/2026ACCESS GRANTED, NO CERTIFICATE OF CORRECTION ON FILE FOR CLASS 1 VIOLATION #39074772P ISSUED 11/30/2022. OBSERVED SAFETY SYSTEM ROOFTOP GENERATOR NOW REPAIRED., FILE A CERTIFICATE OF CORRECTION$1K due
ECB06/16/2025UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. OBSERVED EXCESSIVE STORAGE UNDERNEATH STAIRCASE. LOCATED IN STORAGE AT BASEMENT LEVEL. (CARDBOARD BOXES. GARBAGE BAGS, PAINT BUCKETS, CLEANING EQUIPMENT AND$3K due
ECB06/16/2025EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING DOORS IN RPZ ROOM ON FIRST FLOOR AND GAS METER ROOM AT BASEMENT LEVEL. POTENTIAL FIRE HAZARD., REPAIR/REPLACE DOOR$655 due
ECB06/16/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVE HOLE PENETRATIONS AND UNPERMITTED PLASTIC ACCESS PANELS THROUGHOUT THE BU$12K due
ECB06/13/2025CLASS 2 ITEMS: DOOR OPERATOR COVER MISSING, PROVIDE. IN CAR 4 FLOOR BUTTON LIGHT INOPERATIVE, REPAIR. PIT DIRTY, CLEAN ENTIRE PIT AREA.$655 due
DOB12/11/2024FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
ECB05/16/2024I OBSERVED THROUGHOUT THE ENTIRE FIRST FLOOR THE INSTALLATION OF NEW LIGHTS CONDUITS AND RACEWAYS TO SUPPLY POWER TO EXIT SIGNS, POWER MODULES FOR OUTLETS AND DATA TO DESKS IN THE REAR OFFICE AREA. ALL ELECTRIC$4K due
ECB05/16/2024I OBSERVED IN THE BASEMENT AREA THE UNPERMITTED STORAGE BENEATH THE ATS EQUIPMENT OF FURNITURE AND BUILDING EQUIPMENT. NO STORAGE IS PERMITTED WITHIN 30-36 INCHES OF ELECTRICAL EQUIPMENT., PROVIDE/MAINTAIN ACCE$2K due
ECB05/16/2024I OBSERVED IN THE ROOFTOP GENERATOR ROOM THE GENERATOR STILL IN A STATE OF DISREPAIR AND NOT IN USE AS REQUIRED FOR ALL SAFETY SYSTEMS., COMPLY WITH EC; COMPLY WITH EC AND MAINTAIN ALL SAFETY SYSTEMS.$16K due
DOB05/31/2018FAILED TO FILE FISP CYCLE 8A TECHNICAL REPORT BY 02/21/2017
ECB06/11/2026CLASS 1 C/U: FIREFIGHTER SERVICE PHASE I NOT OPERATING AS REQUIRED; KEY CANNOT BE REMOVED WHEN FIRE RECALL IS ACTIVATED AS PER ASME A17.1/CSA B44 2.27.2 AND NYC BC APPENDIX K3. IMMEDIATE HAZARDOUS CONDITION. REHearing held — result not yet published
ECB06/09/2026AT TIME OF INSPECTION MISSING TRAP WRAPS AND OPEN ENDED TOILETS SEATS THROUGHOUT BUILDING 420.3 WATER CLOSET SEATS. WATER CLOSETS SHALL BE EQUIPPED WITH SEATS OF SMOOTH, NONABSORBENT MATERIAL. ALL SEATS OF WATEHearing held — result not yet published$2K proposed
ECB06/09/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF INSPECTION, OBSERVED THE FOLLOWING VIOLATING. .HOLE PENETRATIONS IN BATHROOM ON THE 8TH FLOOR. PLASTIC ACCESS PANELS LOCATED IN THE FRONT OF THEHearing held — result not yet published$6K proposed
ECB06/09/2026AT TIME OF INSPECTION GAS LEAK WAS OBSERVED IN THE BASMENT AS PER PC 102.3 . INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHALL BE MAINTAINED IN PROPER OPERATING CONDITION IN ACCORDANCE WITH THE ORIGHearing held — result not yet published$2K proposed
ECB02/09/2024FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39074771N ISSUED ON 11/30/22 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01. (MISCELLANEOUS VIOLATIONothing owed — awaiting certificate of correction
ECB11/30/2022I OBSERVED ON THE ROOFTOP LEVEL THE GENERATOR DEFECTIVE AND INOPERABLE. THE SAFETY SYSTEM SHALL BE MAINTAIN AND IN OPERATION AT ALL TIMES., COMPLY WITH EC; MAINTAIN SAFETY SYSTEMS AT ALL TIMES.Nothing owed — awaiting certificate of correction
ECB04/07/2022I OBSERVED AN ACTIVE LEAK ON A DEFECTIVE HOT WATER STORAGE TANK IN THE BOILER ROOM THAT IS LOCATED IN THE BASEMENT/CELLAR., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB09/09/2019I OBSERVED IN THE CELLAR THE GROUNDING ELECTRODE CONDUCTOR WATER CLAMP DETERIORATED TO THE POINT OF DISREPAIR, I OBSERVED UNDERNEATH THE POTABLE WATER METER, ELECTRICAL CONDUIT COMPLETELY DETERIORATED AND UN-MNothing owed — awaiting certificate of correction