DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB09/08/2017V-DOB VIOLATION - ACTIVE
ECB06/26/2026REISSUE #35658993Y. DATE OF ISSUE: 06/02/2022. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER AT THE TIME OF INSPECTION OBSERVED AND NOTED AT (1ST FLOOR)MAIN ENTRANCE CEILING IS IN STATE OF DISREPAIR WITNothing owed — awaiting certificate of correction
ECB08/25/2025IN CELLAR BOILER ROOM>AO SMITH GAS HOT WATER HEATERS HAVE SPILL SWITCHES HANGING LOOSE+NOT INTERLOCKED WITH WATER HEATERS TO STOP THE FIRING IF SPILLAGE IS DETECTED, MAINTAIN BOILER; CORRECT VIOLATION+SUBMIT CENothing owed — awaiting certificate of correction
ECB10/17/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT 2 FLOOR CLASSROOM 216, 1FL. 118 DOORS ARE NOT CLOSING PROPERLY. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB10/17/2024REISSUE #35658003Y. NOTED: AT 1 FLOOR MAINTENANCE AREA CEILING SPALLING AND WATER PENETRATION ROOF LEAKING. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB06/02/2022REISSUED#35582243P-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANENR.NOTED:OBSERVED AT EXP#3/REARYARD,SEVERAL WINDOWS ON THE 2ND FLOOR ARE CRACKED/BROKEN.REARYARD HAS PLAY GROUND FOR THE STUDENTS,CREATING ANothing owed — awaiting certificate of correction
ECB06/02/2022FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:OBSERVED AT(1ST FLR)MAIN ENTRANCE,CEILING IS IN STATE OF DISREPAIR WITH HOLE APPROXIMATELY 4 INCH X ARE TO PREVIOUS LEAK COMING FROM THE ROOF.ALSO ATNothing owed — awaiting certificate of correction
ECB06/21/2021FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED:AT GROUND LEVEL AT EXPOSURE#2 AND EXPOSURE#3. INTERIOR FACADES,ALSO 2ND FL WINDOWS OVER PLAY AREA HAVE TEN(10) CRACKED/BROKEN WIRE MESH GLASSES. RNothing owed — awaiting certificate of correction
ECB11/15/2016FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: AT 2ND FL BOYS BATHROOM WATER PENETRATION @ CEILING DIE TO ROOF LEAK. REMEDY: MAKE NECESSARY REPAIRS.Nothing owed — awaiting certificate of correction
ECB11/15/2016FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: AT THE CELLAR AT ELECTRICAL ROOM,SHOVELS,SNOW SHOVELS,RAKE,SEED SPREADER,FLOOR POLISHER,CEILING TILES,WHEEL CART BEING STORED CREATING HAZARDOUS CONDITINothing owed — awaiting certificate of correction