ECB11/03/2025Failure to maintain building in code-compliant manner. At time of inspection observed cracksand missing mortar joint on exp #1 and also on exp #4. Remedy: repair and replace.$12K due
ECB01/29/2025Failure to comply with commissioner's order contained in summons #39075326J issued on 12/08/2022, and failure to file a certificate of correction pursuant to 28.201.1 and 1 rcny 102-01(d)(2). An acceptable cert$6K due
ECB05/23/2024Observed a burnham boiler model SIN5LNI serial# 65302615 with storage in boiler room, missing chimney cleanout , missing fire damper on combustion air intake. Correct all violating conditions and submit a certi$3K due
ECB12/08/2022Found fulton oil fired boiler model fb-10 NB#116499 active and operating with defects. Chimney cleanout not found. Door not self closing due to pipe run across door opening. Correct all violating conditions and$315 due
ECB03/15/2022Remove storage,pipe leaking on fitting by low wtr cut off ,which is too low & needs to be relocated,seal base of chimney & install clean out,missing fire dampers for combustion air remove clogged screen holes tNothing owed — awaiting certificate of correction
ECB08/17/201836,4A,15,38,50A,50B,50C,50D. B254-36 found pennco gas fired boiler not registered 50A-wrong material for pipe support; b-no flue support c-discharge on boiler relief valve wrong material; d-no signage on dooNothing owed — awaiting certificate of correction
ECB05/19/2017As per class 2 (B265) 28-303.7 failure to file a complete boiler inspection report as per DOB records. Submit a current B09 report.Nothing owed — awaiting certificate of correction