ECB09/12/2025FOUND HYDROTHERM GAS FIRED BOILER MISSING RATING TAG, RELIEF VALVES IN WRONG POSITION CORRECT VIOLATING CONDITION AND SUBMIT A CERTIFICATE OF CORRECTION$6K due
ECB09/12/2025FOUND HYDROTHERM GAS FIRED BOILER MISSING RATING TAG RELIEF VALVES IN WRONG POSITION NEEDS SPILL SWITCHES CORRECT VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORRECTION$6K due
ECB05/08/2026REISSUED ECB#35720063K FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED AT CEILING AND WALL INSIDE ELECTRICAL ROOM WATER PENETRATION LEAK.REM:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB05/08/2026REISSUED ECB#35655406P FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6,FGC APPENDIX E.NOTED:AT GAS METER ROOM AND ELECTRICAL ROOM NO FRESH AIR OR MECHANICAL VENTILATION SYSTEM INSTALLED.Nothing owed — awaiting certificate of correction
ECB08/27/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT CEILING INSIDE ELECTRICAL ROOM WATER PENETRATION(LEAK). REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB06/15/202228-301.1 REISSUE35561471Y(8/4/21) FAILURE TO PROVIDE VENTILATION TO GAS METER RM PER P115.6(1968CODE),FGC APPEXE(E4)(2014)@BSMT GAS METER RM,NO PROPER VENTILATION SYSTEMS ATOI.COMPLY W/NOTICE OF VIO.Nothing owed — awaiting certificate of correction
ECB03/16/2022MISSING RATING PLATE ON BOILER,RELIEF VALVE NOT VERTICAL,SPILL SWITCHES MISSING,REMOTE SWITCH FOR BOILER NOT AT ARMS LENGTH,CORRECT VIOLATION & SEND IN CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB03/16/2022MISSING RATING PLATE,ON BOILER,NO SWITCH AT DOOR TO BOILER ROOM,NO CLEAN OUT AT BASE OF CHIMNEY,RELIEF VALVE TO BE VERTICAL,ILLEGAL VALVES ON WEIL MC.MODUEL CORRECT VIOLATION AND SEND IN CERTIFICATE OF CORRECTINothing owed — awaiting certificate of correction
ECB08/04/202128-301.1 REISSUE35498491M NOTED:@BSMT LEVEL GAS&ELECTRICAL METER RM,DOESNT HAVE ANY FRESH AIR OR MECHANICAL VENTILATION SYSTEM INSTALLED.COMPLY W/NOTICE OF VIOLATION.Nothing owed — awaiting certificate of correction
ECB06/17/2020SEC. 28-301.1 REISSUE#35452173N FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE),FGC APPENDIX E(E4)(2019 CODE). NOTED:AT BASEMENT LEVEL,NO VENTILATION PROVIDED TO GAS METER ROOM.Nothing owed — awaiting certificate of correction
ECB02/18/2020LICENSE MASTER PLUMBER#0909 PULLED EMERGENCY WORK NOTIFICATION (EWN)#Q-00280433 ON 12-12-2019 TO RESTORE HEAT TO THE BUILDING BY REPLACING SEVERAL FEET OF GAS PIPING. BUT FAILURE TO COMPLY WITH THE RULES OF EWNNothing owed — awaiting certificate of correction
ECB09/09/201928=301.1:FAILURE O PROVIDE VENTILATION TO GAS METER ROOM PER P 115.6(1968 CODE) FOC APPENXIS E(E4) (2014 CODE0 NOTED AT BASEMENT GAS METER ROOM WITH HAVING NO VENTILATION SYSTEM INSTALLED COMPLY WITH NOTICE OFNothing owed — awaiting certificate of correction