HPD09/17/2026§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED WIRE AT WEST WALL NEAR COMPACTOR CHUTE AT PUBLIC HALL, 17th STORY, SECTION ''2324''
HPD09/17/2026§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT DOOR AT ROOF AT 2nd PUBLIC HALL BULKHEAD FROM NORTH, 17th STORY, SECTION ''2324''
HPD09/17/2026§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH AT FIRE DOOR STAIRCASE B AT PUBLIC HALL, 17th STORY, SECTION ''2324''
HPD09/17/2026§ 27-2042 ADM CODE PROVIDE A MIRROR IN SELF-SERVICE ELEVATOR ARRANGED SO AS TO ENABLE A PERSON ENTERING, TO VIEW INSIDE OF ELEVATOR NUMBER ID#2P3570 , SECTION ''2324''
HPD09/17/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH AT FIRE DOOR STAIRCASE B AT PUBLIC HALL, 17th STORY, SECTION ''2324''
HPD09/01/2026HMC- §272024 PROVIDE AND MAINTAIN A PURE AND WHOLESOME WATER SUPPLY THAT WAS FOUND DISCOLORED AT AT BATHTUB IN THE BATHROOM LOCATED AT APT 4S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''2344''
HPD09/01/2026§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE THE HINGES IN THE ENTRANCE LOCATED AT APT 4S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''2344''
HPD08/24/2026§ 27-2026 ADM CODE REMOVE ALL OBSTRUCTIONS AND REPAIR ALL DEFECTS IN DRAIN PIPE UNDER BATHTUB IN THE BATHROOM LOCATED AT APT 4S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD08/24/2026§ 27-2005 HMC: REFIT THE DOOR AND FRAME AT ENTRANCE IN THE FOYER LOCATED AT APT 4S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD08/24/2026§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE ENAMEL GLAZE SURFACE FINISH AT BATHTUB IN THE BATHROOM LOCATED AT APT 4S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD08/24/2026§ 27-2026 ADM CODE REMOVE ALL OBSTRUCTIONS AND REPAIR ALL DEFECTS IN DRAIN PIPE UNDER SINK IN THE KITCHEN LOCATED AT APT 4S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD08/24/2026§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL WALLS AND CEILING IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 4S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD08/24/2026§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING IN THE BATHROOM LOCATED AT APT 4S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD08/03/2026§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st BATHROOM FROM NORTH LOCATED AT APT 4W, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD08/03/2026§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 2nd BATHROOM FROM NORTH LOCATED AT APT 4W, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD07/14/2026§ 27-2005, 2007 ADM CODE FIRE EGRESS DEFECTIVE. REMOVE OBSTRUCTING BARS OR UNLAWFUL GATES FROM AT LEAST 1 WINDOW OR PROVIDE APPROVED TYPE GATE IN THE ENTIRE APARTMENT LOCATED AT APT 1B, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
HPD06/20/2026§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE FOYER , THE 4th ROOM FROM NORTH AT WEST, THE 4th ROOM FROM NORTH AT EAST, THE KITCHEN LOCATED AT APT 4S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD06/20/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL OUTLET AT WEST WALL IN THE 4th ROOM FROM NORTH AT EAST LOCATED AT APT 4S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''2344''
HPD06/18/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL OUTLETS AT EAST AND WEST WALL IN THE 2nd ROOM FROM EAST LOCATED AT APT 4S, 4th STORY, 22nd APARTMENT FROM NORTH AT EAST , SECTION ''2344''
HPD06/18/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MECHANICAL STOPPER AT BATHTUB IN THE BATHROOM LOCATED AT APT 4S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD06/18/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL OUTLET EAST WALL IN THE 3rd ROOM FROM EAST LOCATED AT APT 4S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''2344''
HPD05/21/2026§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT FIRE DOOR AT WEST STAIRWELL ''A'' AT PUBLIC HALL, 1st STORY, SECTION ''2344''
HPD04/11/2026§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... MORE THAN 10 SQ.FT, BUT LESS THAN 30 SQ.FT AT CEILING NORTH WALL IN THE PRIVATE HALLWAY LOCATED AT APT 16K, 16th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''2334'' ORIGINAL VIOLATION 18781481 ISSUED 11-APR-26 HAS BEEN UPGRADED TO CLASS C PER ADMINISTRATIVE CODE 27-2017.3a(5)(a) or (b).
HPD04/11/2026§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... MORE THAN 10 SQ.FT BUT LESS THAN 30 SQ.FT AT NORTH, EAST WALLS AND CEILING IN THE BATHROOM LOCATED AT APT 16K, 16th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''2334'' ORIGINAL VIOLATION 18781482 ISSUED 11-APR-26 HAS BEEN UPGRADED TO CLASS C PER ADMINISTRATIVE CODE 27-2017.3a(5)(a) or (b).
HPD04/11/2026§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... MORE THAN 10 SQ.FT BUT LESS THAN 30 SQ.FT AT WINDOW CASING IN THE BATHROOM LOCATED AT APT 16K, 16th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''2334'' ORIGINAL VIOLATION 18781479 ISSUED 11-APR-26 HAS BEEN UPGRADED TO CLASS C PER ADMINISTRATIVE CODE 27-2017.3a(5)(a) or (b).
HPD04/11/2026§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... MORE THAN 10 SQ.FT BUT LESS THAN 30 SQ.FT ON THE WEST WALL AND WINDOW CASING IN THE 2nd ROOM FROM EAST LOCATED AT APT 16K, 16th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''2334'' ORIGINAL VIOLATION 18781480 ISSUED 11-APR-26 HAS BEEN UPGRADED TO CLASS C PER ADMINISTRATIVE CODE 27-2017.3a(5)(a) or (b).
HPD04/11/2026§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE WEST AND NORTH WALLS IN THE BATHROOM LOCATED AT APT 16K, 16th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''2334''
HPD04/11/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MECHANICSL VENTILATION SYSTEM AT NORTH WALL IN THE BATHROOM LOCATED AT APT 16K, 16th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''2334''
HPD03/18/2026§ 27-2005 ADM CODE PROVIDE AN UNLOCKABLE SLIGHT BOLT OR HOOK ON ROOF DOOR THAT ALLOWS RE-ENTRY FROM ROOF TO PUBLIC HALL AT 2nd PUBLIC HALL BULKHEAD FROM EAST, 17th STORY
HPD03/18/2026§ 27-2005 ADM CODE PROVIDE AN UNLOCKABLE SLIGHT BOLT OR HOOK ON ROOF DOOR THAT ALLOWS RE-ENTRY, FROM ROOF TO PUBLIC HALL, SECTION 2344 AT 1st PUBLIC HALL BULKHEAD FROM EAST, 17th STORY
HPD12/01/2025§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSE WIRING AT SOUTH WALL ( NEAR HOPPER CHUTE) AT ELECTRICAL BOX AT PUBLIC HALL, 21st STORY
ECB10/24/2025FAILURE TO MAINTAIN FACADE WALL"S" AND APPURTENANCES. NOTE: AT THE TIME OF INSPECTION I OBSERVED AT EXP #1, WEST ELEVATION CRACKED CONCRETE BETWEEN 11TH FLOOR AND 14TH FLOOR. SPALLING BRICK MORTAR JOINTS AT 21S$5K due
HPD06/05/2025§ 27-2056.7 ADM CODE: CORRECT FAILURE TO PROVIDE TO THE DEPARTMENT WITHIN 45 DAYS OF DEMAND ALL RECORDS REQUIRED TO BE MAINTAINED BY OWNER PURSUANT TO LOCAL LAW 1 OF 2004 RELATED TO LEAD-BASED PAINT NOTICES, INSPECTIONS AND REMEDIATION/ABATEMENT ACTIVITIES.
HPD10/31/2024§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING, NOETH WALL AND WEST WALL IN THE 2nd BATHROOM FROM NORTH LOCATED AT APT 4W, 4th STORY, 3rd APARTMENT FROM SOUTH AT WEST
HPD10/31/2024§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 1st BATHROOM FROM NORTH LOCATED AT APT 4W, 4th STORY, 3rd APARTMENT FROM SOUTH AT WEST
ECB09/12/2024FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS#3555979L ISSUED ON 10/23/2021,AND FAILURE TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28.201.1 AND 1RCNY 102-01(D)(2).AN ACCEPTABLE CERTIFICA$1K due
HPD09/04/2024§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FROM WEST AT NORTH WALL, 1st DOOR FRAME FROM WEST AT NORTH WALL IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 4W, 4th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''2344''
HPD09/04/2024§ 27-2056.7, 27-2056.8, 27-2056.9 ADM CODE -CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY PERFORMING ACTIVITIES NECESSARY TO ABATE TESTED LEAD-BASED PAINT FROM REQUIRED WINDOW AND/OR DOOR FRICTION SURFACES FOR APARTMENT AND MAKE FLOORS SMOOTH AND CLEANABLE, POSITIVE LEAD-BASED PAINT IN AN APARTMENT WITH A CHILD UNDER SIX LOCATED AT APT 4W, 4th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''2344''
HPD07/03/2024§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING (LESS THAN 10 SQ.FT.) IN THE BATHROOM LOCATED AT APT 4S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''2344'' ORIGINAL VIOLATION 17093931 ISSUED 03-JUL-24 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
DOB06/23/2024FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2023)
DOB05/02/2024FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
ECB02/01/2024FAILURE TO FILE ACCEPTABLE AMENDED CYCLE REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FACADES REPORT REQUIRED BY 28-302.5 FOR CONTROL #608633. AGG2 HISTORY OF NONCOMPLIANCE ON 37022399$6K due
DOB10/04/2023FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB10/04/2023FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB10/04/2023FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB10/04/2023FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB10/04/2023FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB04/22/2023FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2022)
HPD03/23/2023HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 12A, 12th STORY, 1st APARTMENT FROM SOUTH AT WEST
DOB02/22/2023FAILED TO FILE FISP CYCLE 9B TECHNICAL REPORT BY 2/21/2023
ECB02/06/2023FAILURE TO PROVIDE ADEQUATE SAFETY MEASURES WHERE REQUIRED TO SECURE AND PROTECT PUBLIC SAFETY FROM DOCUMENTED UNSAFE FACADE.FACADE TECHNICAL REPORT BY QEWI(RA/PE)FILED UNSAFE ON 3/2/2007.NOTE OBSERVED INADEQUA$25K due
ECB01/20/2023AT TIME OF INSPECTION ON EXISTING 21 STORY OCCUPIED BUILDING, I OBSERVED INSTALLED SWS IN ALL PLACES OF PEDESTRIAN WALKWAYS & PATHWAYS AT EXTERIOR AREA OF EXISTING WITH INADEQUATE PEDESTRIAN PROTECTION-NETTING$2K due
ECB12/15/2022FAILURE TO TAKE & PROVIDE ADEQUATE SAFETY MEASURES WHERE REQUIRED TO SECURE & PROTECT PUBLIC SAFETY FROM DOCUMENTED UNSAFE FACADE.THE RAIPE TRG REPORT FILED UNSAFE ON 3/2/2007.NOTE:OBSERVED INADEQUATE SAFETY ME$10K due
ECB10/26/2022FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 7B AND 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL#808633.AGG2 HISTORY OF NONCOMPLI$6K due
ECB10/18/2022FAILURE TO MAINTAIN EXTERIOR BLDG FACADE&APPURTENANCE.NOTE:AS PREV V35651467K ISSUED8/5/22&OF TODAY TOI ON10/14/22 OBSERVED@EXP1&3W&E ELEVATIONS W/CRACKED CONCRETE CORNERS OF SLABS.ALSO OBSERVED SPALLING ON EDG$6K due
HPD10/12/2022§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING IN THE BATHROOM LOCATED AT APT 4S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''2344'' ORIGINAL VIOLATION 15427574 ISSUED 12-OCT-22 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
DOB08/21/2022FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2021)
DOB08/05/2022EMERGENCY WORK ORDER DUE TO DEFECTIVE CONCRETE BALCONY CONDITIONS REMEDY:REPAIR AND RESTORE CONDE COMPLAINT CONDITIONS TO SIDEWALK SHED PROTECTION ALSO REMOVE ANY & ALL LOOSE CONCRETE MATERIAL FROM BUILDING FACADES
ECB08/05/2022SIDEWALK SHED DOES NOT MEET CODE SPECIFICATIONS.OBSERVED SWS MISSING PARAPET WALL & LOOSE METAL DECKING MATERIAL ON EXP #1 #2 #4.EXP #3 REMAINING PARAPET WALLS HAVE LOOSE & WARPED PLYWOOD PANELS.CENTER SECTION$2K due
ECB08/05/2022FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE & APPURTENANCES.NOTE:OBSERVED DEFECTIVE BALCONIES ON EXP #1 #3 WEST & EAST ELEVATIONS CRACKED CONCRETE CORNERS OF SLABS.SPALLING ON EDGE OF CONCRETE SLABS CONDITIONS$2K due
ECB08/05/2022UNLAWFUL ACTS.FAILURE TO COMPLY WITH VACATE ORDER OF COMMISSIONER.VACATE ORDER #LLFA01MR ISSUED 10/23/2021 REQUIRES IMMEDIATE VACATE OF ALL BALCONIES OBSERVED PEOPLE ON BALCONY 7TH FLOOR EXP #1.REMEDY:COMPLY WI$5K due
HPD06/27/2022§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING AND NORTH WALL (12 SQ. FT.) IN THE BATHROOM LOCATED AT APT 4S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST ORIGINAL VIOLATION 15236887 ISSUED 27-JUN-22 HAS BEEN UPGRADED TO CLASS C PER ADMINISTRATIVE CODE 27-2017.3a(5)(a) or (b).
HPD06/07/2022§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE FOYER , THE BATHROOM LOCATED AT APT 4S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD06/07/2022§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROX. 10 SQ. FT AT CEILING, NORTH WALL IN THE BATHROOM LOCATED AT APT 4S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST ORIGINAL VIOLATION 15202278 ISSUED 07-JUN-22 HAS BEEN UPGRADED TO CLASS C PER ADMINISTRATIVE CODE 27-2017.3a(5)(a) or (b).
DOB06/01/2022FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB03/02/2022FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB10/23/2021VACATE ORDER: OBSERVED SPALLING, CRACKED CONCRETE BALCONY SLABS, PRESENTING HAZARDOUS CONDITION BELOW. REMEDY: IMMED VACATE ALL BALCONIES AND AREA BELOW. PROVIDE AND MAINTAON SAFETY MEAURES TO PREVENT ACCESS TO ALL BALCONIES AND AREA BELOW
DOB06/20/2021FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2020)
DOB02/17/2021FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB01/06/2021FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB01/06/2021FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB12/23/2020FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB10/14/2020FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB10/14/2020FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB06/29/2020FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2019)
DOB06/28/2020FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2018)
ECB06/17/2020FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 7B & 8B REPORT CRITICALEXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL & APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL#808633. AGG2 HISTORY OF NONCOMPLIANCE ON$6K due
HPD02/21/2020§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT THE CEILING (APPROX.12 SQ. FT.) IN THE BATHROOM LOCATED AT APT 21K, 21st STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''#2334''
HPD01/25/2020§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING IN THE BATHROOM LOCATED AT APT 21K, 21st STORY, 3rd APARTMENT FROM SOUTH AT WEST
HPD01/07/2020§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT IN THE BATHROOM LOCATED AT APT 21K, 21st STORY, 3rd APARTMENT FROM SOUTH AT WEST
HPD01/07/2020§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT NORTH WALL, CEILING, EAST WALL IN THE KITCHEN LOCATED AT APT 21K, 21st STORY, 3rd APARTMENT FROM SOUTH AT WEST
HPD12/13/2019§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROX 16 SQ. FT AT CEILING IN THE BATHROOM LOCATED AT APT 21K, 21st STORY, 3rd APARTMENT FROM SOUTH AT WEST ORIGINAL VIOLATION 13504096 ISSUED 13-DEC-19 HAS BEEN UPGRADED TO CLASS C PER ADMINISTRATIVE CODE §27-2017.3a(5)(a) or (b).
DOB11/08/2019VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
ECB01/14/2019FAILURE TO SUBMIT A REQUIRED CYCLE 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL #808633. AGG2 HISTORY OF NONCOMPLIANCE ON 3700119$6K due
DOB07/31/2018FAILED TO FILE FISP CYCLE 8B TECHNICAL REPORT BY 02/21/2018
DOB04/06/2018VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2016 INSPECTION REPORT
DOB03/27/2018FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 IN 2017
DOB09/15/2017VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2016 INSPECTION/TEST
DOB02/24/2017VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2015 INSPECTION REPORT
DOB12/01/2016VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2015 INSPECTION/TEST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB06/01/2016FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB06/01/2016FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB10/01/2015VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2014 INSPECTION REPORT
DOB06/10/2015VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2014 INSPECTION/TEST
DOB06/10/2015VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2014 INSPECTION/TEST
DOB03/03/2015VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2013 INSPECTION REPORT