ECB06/13/2018B154,3B,50A,51. FULTON V.T. BOILER #2, 10HP,NB607374, HP STM,GAS 1990 3B-REFERENCED BOILER #3 IN OPERATION WITH FLUE GAS LEAKAGE FROM LOOSE FLUE PIPE AND BREECHING JOINTS;RE-CONSTRUCT FLUE PIPE RUN WITH 24 GAUGNothing owed — awaiting certificate of correction
ECB06/13/2018B154,3B,50A,51. FULTON V.T. BOILER #1, 15HP,NB79931, HP STM,GAS 1997 3B-REFERENCED BOILER #3 IN OPERATION WITH FLUE GAS LEAKAGE FROM LOOSE FLUE PIPE AND BREECHING JOINTS;RE-CONSTRUCT FLUE PIPE RUN WITH 24 GAUGNothing owed — awaiting certificate of correction
ECB06/13/2018B154,3B,50A,51. FULTON V.T. BOILER #3, 15HP,NB105464, HP STM,GAS 2008 3B-REFERENCED BOILER #3 IN OPERATION WITH FLUE GAS LEAKAGE FROM LOOSE FLUE PIPE AND BREECHING JOINTS;RE-CONSTRUCT FLUE PIPE RUN WITH 24 GAUGNothing owed — awaiting certificate of correction
ECB01/21/2017FAILURE TO MAINTAIN EXTERIOR BLDG FACADE AND APPURTENANCES *AMENDED REPORT FILE SAFE. NOTED: EAST ELEVATION EXP1:HORIZONTAL CRACK IN STONE (13 FL),CRACK/DAMAGED STONE (8 FLR) CRACKS IN DECORATIVE STONES (4THNothing owed — awaiting certificate of correction
ECB05/08/200618A/50. FULTON VT BOILER,15 HP,NB 60727,GAS 1990. 18A-CORRODED HANDHOLES ON BOILER. REPAIR 50-STEAM PRESSURE GAUGE HAS A DIAL RANGE OF 0-200PSI. INSTALL A REPLACEMENT PRESSURE GAUGE 0-300 PSI.Nothing owed — awaiting certificate of correction
ECB06/04/200451.CEASE USE.1990 FULTON 60727-HIGH CARBON MONOXIDE.51-SEALED BOILER-341 P.P.M OUT OF CASING AROUND TOP HAND HOLE.Nothing owed — awaiting certificate of correction