ECB05/21/2026REISSUE: 35724625L DATE OF ISSUE: 09/10/2025. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGESAND PUBLIC CORRIDORS PER BC 1006.1; 27-381. AT 4TH FL. NEAR STAIRWAY "$10K due
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
ECB05/21/2026REISSUE #35724626N DATE OF ISSUE: 09/10/2025. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED OBSERVED AT STAIRCASE "C" BETWEEN 5TH FLOOR AND 4TH FLOOR 8 PANENothing owed — awaiting certificate of correction
ECB05/21/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3; 27-345. AT CELLAR ROOM, ELECTRICAL METER ROOM NO FIRE STOPPING AT WALL AREAS OBSERVED HOLES IN WALLS. REMEDY: PROVIDE/MAINTANothing owed — awaiting certificate of correction
ECB05/21/2026REISSUE #35724627P DATE OF ISSUE: 09/10/2025. FAILURE TO MAINTAIN BUILDING IN MAINTAIN IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED EXTERIOR STEPS OUTSIDE OF THE KITCHEN BY LODING DOCKNothing owed — awaiting certificate of correction
ECB05/21/2026REISSUE: 35725299J DATE OF ISSUE: 09/10/2025. EXIT DOOR NOT SELF-CLOSING PROPERLY AT THE TIME OF INSPECTION. AT 1ST FLOOR EXIT-7, OUTSIDE TWO EXIT DOORS. REMEDY: REPAIR OR REPLACE ALL DEFECTIVE EMERGENCY OUTSIDNothing owed — awaiting certificate of correction
ECB05/21/2026REISSUE #35423346J DATE OF ISSUE: 07/11/2019. FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. AT THE TIME ON INSPECTION OBSERVED AND NOTED AT FRONT OF BUILDING SPALLING AND MISSING MORTAR AT BRICKS THROUNothing owed — awaiting certificate of correction
ECB10/28/2025RE-ISSUE #35692237X. EXIT DOOR NOT SELF-CLOSING. EXIT DOOR NOT SELF-CLOSING PROPERLY. AT TIME OF INSPECTION AT THE ROOF "STAIR C" EXTERIOR DOOR. REMEDY: REPAIR/REPLACE DOOR.Nothing owed — awaiting certificate of correction
ECB10/28/2025RE-ISSUE #35692234K. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: OBSERVED AR "STAIRCASE C" BETWEEN 5TH AND 4TH FLR 8 PANELS ARE MISSING ON THE STAIRCASE. REMEDY: REPAIR AND/OR REPLACE PANELS.Nothing owed — awaiting certificate of correction
ECB10/28/2025RE-ISSUE #35692235M. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PERBC 1006.1; 27-381. NOTED: AT THE TIME OF INSPECTION OBSERVED EMERGENCYNothing owed — awaiting certificate of correction
ECB10/28/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: INTERIORSMOKE DOORS DO NOT SELF-CLOSE PROPERLY. 1ST FLR-"STAIR A", "GYM DOOR D", "CAFETERIA EXIT NEAR RM 111". BASEMENT-"BOILER ROOM EXIT". CLASSROONothing owed — awaiting certificate of correction
ECB10/28/2025RE-ISSUE #35676376X. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT THE TIME OF INSPECTION, OBSERVED THAT THE EXTERIOR STEPS OUTSIDE OF THE KITCHEN BY THE LOADING DOCK IS CRACKED AND UNEVEN. RNothing owed — awaiting certificate of correction
ECB10/07/2024REISSUE #35676320R. DATE OF ISSUE: 07/10/2023. EXIT DOOR NOT SELF-CLOSING PROPERLY AT THE TIME OF INSPECTION. AT STAIR "A" 1ST FLOOR ONE EXIT NOT SELF-CLOSING PROPERLY, AT 2ND FLOOR AUDITORIUM ONE EXIT DOOR NOTNothing owed — awaiting certificate of correction
ECB10/07/2024REISSUE #35676323M. DATE OF ISSUE: 07/10/2023. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION, OBSERVED AND NOTED THAT AT ROOM 507 AND STAIRCASE "C" BETWEEN 5TH AND 4TH FL THERNothing owed — awaiting certificate of correction
ECB10/07/2024REISSUE #35676322K. DATE OF ISSUE: 07/10/2023. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. AT THE TIME OF INSPECTIONothing owed — awaiting certificate of correction
ECB07/10/2023REISSUE #35657863J DATE OF ISSUE: 05.27.22 EXIT DOORS ARE NOT SELF CLOSING PROPERLY AT THE TIME OF INSPECTION OBSERVED THAT AT 1ST FLOOR AUDITORIUM. REAR RIGHT DOOR & AT CAFETERIA. 3 EXIT DOORS ARE NO SELF CLOSNothing owed — awaiting certificate of correction
ECB07/10/2023REISSUE #35657867R DATE OF ISSUE: 05.27.22 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1,27.2381 AT THE TIME OF INSPECTION OBSENothing owed — awaiting certificate of correction
ECB07/10/2023REISSUE #35657866P DATE OF ISSUE: 05.27.22 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED THAT AT STAIR CASE "C" BETWEEN 5TH AND 4TH FLOOR THERE APPROX 8 PANELS MISSINNothing owed — awaiting certificate of correction
ECB07/10/2023REISSUE #35655338M DATE OF ISSUE: 06.02.21 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED THAT THE EXTERIOR STEPS OUTSIDE OF THEK ITCHEN BY THE LODING DOCK AND PARKINGNothing owed — awaiting certificate of correction
ECB05/27/2022FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.ILLUMINATION FOREXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC1006.1;27-381.NOTED EXISTING EMERGENCY LIGHTS WITH BATTERY BACK-UP POWER THROUGHOUT 1ST FLONothing owed — awaiting certificate of correction
ECB05/27/2022REISSUE#35577216N.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED OBSERVED AT STAIR C WALL THAT DIVIDES STAIRWELLS IS MISSING ITS GLASS WIRE MESH PANELS ON 4TH FLOOR UP TO THE 5TH FLOOR.REMEDY:REPAINothing owed — awaiting certificate of correction
ECB05/27/2022REISSUE#35577214J.EXIT DOOR NOT SELF-CLOSING.NOTED OBSERVED AT EXIT 7 MIDDLE JAMB IS LOOSE/ATTACHED,DOOR NOT CLOSING PROPERLY,EXIT 4 DOOR NOT OPENING PROPERLY,CAFETERIA FPSC DOORS BY EXIT 5,AUDITORIUM REAR RIGHNothing owed — awaiting certificate of correction
ECB06/03/2021FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: DURING INSPECTION OBSERVED AT STAIRCASE'C'BETWEEN THE 5TH & 4TH FL. THERE APPROX 7PANELS MISSING BETWEEN THE STAIRCASE WHICH CAN TURN INTO SOMEONE GETTINothing owed — awaiting certificate of correction
ECB06/03/2021REISSUE#35500914P EXIT DOOR NOT SELF CLOSING. NOTE: DURING INSPECTION OBSERVED AT 4TH FL-STAIR'C'DOOR IS NOT CLOSING PROPERLY WHEN TESTED. REMEDY: REPAIR/REPLACE DOOR.Nothing owed — awaiting certificate of correction
ECB06/25/2020EXIT DOOR NOT SELF CLOSING. NOTED: EXIT 2 DOOR BY THE STAIRCASE'G'NOT SELF CLOSED. ALSO ROOM 401 DOOR NOT CLOSE. STAIRCASE'C'4TH FL EXIT DOOR IS NOT SELF CLOSE. REMEDY: REPAIR & OR REPLACE.Nothing owed — awaiting certificate of correction
ECB06/25/2020REISSUE#35423346J. FAILURE TO MAINTAIN BLDG WALL & APPURTENANCES AT EXP#2 MISSING MORTOR AT BRICK THROUGHTOUT WHOLE FACADE MAINLY 3RD,4TH,& 5TH FLOORS,CAUSING WATER PENETRATION ROOM 505,405(A,B),305,205.Nothing owed — awaiting certificate of correction
ECB07/11/2019FAILURE TO MAINTAIN BLD.WALLS AND APPURTENANCES.SPALLING AND MISSING MORTAR AT BRICKS THROUGHOUT ALL FACADE EXPOSURES MAINLY 4TH & 5TH FLOORS.REM:COMPLY WITH CODE ,MAINTAIN EXTERIOR BLD.WALLS.Nothing owed — awaiting certificate of correction