DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
ECB04/20/2026FAILURE TO MAINTAIN BUILDING WALLS OR APPRURTANANCES.NOTED:EXPOSURE#3 RETAINING WALL CONSISTS OF VERTICAL CRACKS AND MISSING CHUNKS OF CONCRETE AT BASE OF FENCE POSTS AND SPALLING CONCRETE IN VARIOUS LOCATIONSNothing owed — awaiting certificate of correction
ECB04/20/2026REISSUE ON ECB#35720689M FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:FIRE RATED CLASSROOMS AND SMOKE DOORS NOT SELF CLOSING DUE TO MISSING OR FAMILY HARDWARE OR BINDING ON CLASSROOMS 333,342,331Nothing owed — awaiting certificate of correction
ECB04/20/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:CRACKED GLASS AT EXPOSURE#1 AT EXIT 00 ABOVE DOORWAY VISION PANEL MULLION ON WIRE MESH GLASS PANEL.INCLUDING MISSING VISION PANEL WIRE MESH GLASS PANENothing owed — awaiting certificate of correction
ECB04/20/2026REISSUE ON ECB#35720667L FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT EXPOSURE#3 IN SCHOOL PLAYYARD OBSERVED SUNKEN ASPHALT PAVEMENT NEXT TO JUNGLE GYM AND BY BASKET BALL COURT APPROXIMATELY 3Nothing owed — awaiting certificate of correction
ECB04/20/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT EXPOSURE#1 SLIDE RAIL SHOOT WITH MISSING ROTTED STEEL BOWING UPWARDS CAUSING POTENTIAL IMPALEMENT OBSERVED UPON INSPECTION.REM:REPAIR AND/OR REPLACNothing owed — awaiting certificate of correction
ECB04/20/2026REISSUE ON ECB#35720666J FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:EMERGENCY ILLUMINATED DISCHARGE LIGHTS AND ENothing owed — awaiting certificate of correction
ECB04/20/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:ROOF CHIMNEY WITH MISSING ROOF HOOD EXPOSING COMPLETE CHIMNEY SHAFT FOR WATER INLET AND OF FALL PROTECTION OBSERVED UPON INSPECTION.REM:REPAIR AND/ORNothing owed — awaiting certificate of correction
ECB07/11/2025REISSUE #35684975H DATE OF ISSUE: 09-30-2024. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED EXP #3 HALLAND AVE SIDE FENCE HAS LARGE HOLE WITH LOOSE/MISSINGNothing owed — awaiting certificate of correction
ECB07/11/2025REISSUE #35688974Y DATE OF ISSUE: 09-30-2024. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE-IME OF INSPECTION OBSERVED AND NOTED AT CELLAR LEVEL RM B22 GAS METER AND SPINKLER CENTRAL VALVE; LOCANothing owed — awaiting certificate of correction
ECB07/11/2025REISSUE #35684976J DATE OF ISSUE: 09-30-2024. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT REAR SCHOOL PLAY YARD BY BASKET BALL COURT AND JUNGLE GYM, SENothing owed — awaiting certificate of correction
ECB07/11/2025REISSUE #35688970R DATE OF ISSUE: 09-30-2024. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGESAND PUBLIC CORRIDORS PER BC 1006.1; 27-381. AT THE TIME OF INSPECTIONNothing owed — awaiting certificate of correction
ECB07/11/2025REISSUE #35688972K DATE OF ISSUE: 09-30-2024. EXIT DOOR NOT SELF-CLOSING PROPERLY. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT CELLAR LEVEL EXIT-3(INSIDE) 3 EXIT DOORS, 1ST FL. GY 2 EXIT DOORS, AT 2ND FLOORNothing owed — awaiting certificate of correction
ECB06/17/2025REISSUE #35688973M DATE OF ISSUE: 09-30-2025. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT CELLAR LEVEL ELECTRICAL ROOM WATER INFILTRATION THROUGH FOUNDNothing owed — awaiting certificate of correction
ECB09/30/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT CELLARLEVEL ELECTRICAL ROOM, WATER INFILTRATION THROUGH FOUNDATION WALL. RUSTED ELECTRICAL EQUIPMENT WITH WATER DRIPPING INTO BUCKETS UNDERNEATH SNothing owed — awaiting certificate of correction
ECB09/30/2024REISSUE #35663418M, FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED INTERIOR FPSC DOORS NOT OPENING/CLOSING PROPERLY. AT 3RD FLCORRIDOR SMOKE DOOR BY RM. 309, 2ND FL. STAIR C AND A PLUS SMOKE DOORNothing owed — awaiting certificate of correction
ECB09/30/2024EXIT DOOR NOT SELF-CLOSING. NOTED EXTERIOR EXIT DOORS NOT SELF-CLOSING/OPENING PROPERLY AT STAIR B BULKHEAD ROOF ACCESS. MAIN ENTRANCE(3 DOORS) AND CELLAR LEVEL CAFETERIA KITCHEN EXIT DOOR. REMEDY: REPAIR AND/ONothing owed — awaiting certificate of correction
ECB09/30/2024FAILURE TO MAINTAIN BUILDING IN OCDE-COMPLIANT MANNER. NOTED AT REAR SCHOOL PLAY YARD, BY BASKET BALL COURT AND BY JUNGLE GYM, SECTIONS OF SUNKEN ASPHALT PAVEMENT APPROC 3" DEEP, 4'X8' SECTION AND 2'X6' SECTIONNothing owed — awaiting certificate of correction
ECB09/30/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT CELLARLEVEL RM B22(GAS METER AND SPRINKLER CENTRAL VALVE) LOCATED WITHIN EXCESSIVE AMOUNTS OF COMBUSTIBLE STORAGE, PARTIALLY OBSTRUCTING ACCESS TONothing owed — awaiting certificate of correction
ECB09/30/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED EXP #3 HOLLAND AVE SIDE FENCE HAS LARGE HOLE WITH LOOSE/MISSING WIRE MESH EXPOSING SHARP EDGES AND CREATING PENETRATION/FALLING HAZARD. ALSO FENCE GANothing owed — awaiting certificate of correction
ECB09/30/2024REISSUE #35672974H, FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED APPROX 40% OF EMERGENCY LIGHTS NOT WORKING WHNothing owed — awaiting certificate of correction
ECB06/29/2023EXIT DOOR NOT SELF CLOSING PROPERLY AT THE TIME OF INSPECTION. AT THE TIME OF INSPECTION AT FIRST FLOOR AUDITORIUM RIGHT SIDE OF STAGE 2 EMERGENCY EXIT DOOR. AT 1ST FLOOR GYM 2 EXIT DOORS, AT 2ND FLOOR EXIT-1 ONothing owed — awaiting certificate of correction
ECB06/29/2023REISSUE #35665120Z DATE OF ISSUE:07.21.22 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ILLUMINATION FOR EXITS, EXIT DISCHARGE AND PUBLIC CORRIDORS PER BC 1006.1;27-381. AT THE TIME OF INSPECTION OBSERVNothing owed — awaiting certificate of correction
ECB07/21/2022RE-ISSUE #35591729J-FAILURE TO MAINTAIN BUILDING CODE-COMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS PER BC1006.1;27-381.NOTED:AT VARIOUS LOCATIONS THROUGHOUT ENTIRE SCHOOL EXISTINGNothing owed — awaiting certificate of correction
ECB02/07/200650A/50B. 50A- PIPE DOWN SAFETY VALVE DISCHARGE TO A SAFE POINT TO PREVENT SCALDING 50B- INSTALL AN INCLINED LADDER TO PROVIDE ACCESS TO THE TOP OF THE BOILERNothing owed — awaiting certificate of correction
ECB02/07/200650A/50B. 50A- PIPE DOWN SAFETY VALVE DISCHARGE TO A SAFE POINT. 50B- INSTALL AN INCLINED LADDER TO PROVIDE SAFE ACCESS TO THE TOP OF THE BOILER.Nothing owed — awaiting certificate of correction
ECB02/07/200650A/50B. 50A- PIPE DOWN THE SAFETY VALVE DISCHARGE TO A SAFE POINT TO PREVENT SCALDING. 50B- INSTALL AN INCLINED LADDER TO PROVIDE SAFE ACCESS TO THE TOP OF THE BOILER.Nothing owed — awaiting certificate of correction