ECB03/12/2026REISSUE: 35692108J. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ROOF BULKHEAD HAS WATER PENETRATION THROUGH DOOR SADDLE. REMEDY: COMPLY WITH CODE.Nothing owed — awaiting certificate of correction
ECB03/12/2026REISSUE: 35692107H. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ROOF LEVEL WATER RISES AFTER RAIINS. LEAKS THROUGH 5TH FLOOR CLASSROOMS. REMEDY: COMPLY WITH CODE.Nothing owed — awaiting certificate of correction
ECB02/06/2026HAZARDOUS CEASE USE BOILER#4>BRICK SET HP BOILER HAS LOOSE I BEAM+BRICKS RIGHT SIDE+LOOSE BRICKS@TOP STEAM DRUM+CORRODED FLUE@CHIMNEY BASE;CORRECT ALL HAZARDOUS CONDITIONS IMMEDIATELY+CALL DOB 212 6020580 TO LINothing owed — awaiting certificate of correction
ECB08/25/2025OBSERVED ONE OIL FIRED WEILMCALIN 782 945000 BTU BOILER, MISSING THE SIGHT GLASS AND THE JACKET COMING APART. CORRECT ALL VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORRECTIONSNothing owed — awaiting certificate of correction
ECB05/01/2025REISSUE #35682865H: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: OBSERVED FROM ROOFTOP, AT BULKHEAD WATER RISES CONTINUE PENETRATING THROUGH DOOR/SADDLE WHICH LEADS TO LANDING, WATERS AND CEILING. REMNothing owed — awaiting certificate of correction
ECB05/01/2025REISSUE #35682867L; FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: OBSERVED @ 5TH FLOOR CLASSROOMS #526 CEILING DAMAGE CAUSED BY WATER INFILTRATION THROUGH FROM ROOF. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB05/01/2025REISSUE #35682866J; FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: OBSERVED AT ROOF LEVEL WATER LEVEL RISE AFTER RAINS CAUSE LEAKS THROUGH ROOFIG MATERIALS AND ONTO 5TH FLOORS CLASSROOM(S). REMEDY: REPANothing owed — awaiting certificate of correction
ECB03/14/2025REISSUE #35682869P: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: OBSERVED @ STAIRCASE #16 AND #15 WATER INFILTRATION FROM ROOFTOP BULKHEAD LEADS ONTO STAIRS, WALLS AND CEILING. REMEDY: REPAIR AND/OR RNothing owed — awaiting certificate of correction
ECB07/29/2024FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. CLASS 2 ITEMS: SERVICE TO THE SECOND FLOOR CURRENTLY DISABLED, RESTORE SERVICE TO THE SECOND FLOOR. CLASS 1 ITEM: BRAKE MONITOR SWITCH MISSING A BOLT, PROVNothing owed — awaiting certificate of correction
ECB07/29/2024RTS CLASS 2: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE. REMEDY: RESTORE TO SERVICE AND CALL THE DOB ELEVATOR DIVISION AT (212) 393-2144 FORNothing owed — awaiting certificate of correction
ECB07/29/2024FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. CLASS 2 ITEMS: FIRE EXTINGUISHER EXPIRED, UPDATE. IN CAR COMMUNICATION INOPERATIVE, REPAIR. PIT DIRTY, CLEAN.Nothing owed — awaiting certificate of correction
ECB06/27/2024REISSUE #35672064Z. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC GYMNASIUM PER BC 1006.1; 27-381. NOTED: ON THE THIRD FLOOR GYMNASIUM EIGHT LIGHTS, TNothing owed — awaiting certificate of correction
ECB06/27/2024REISSUE #35672062P. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT ROOF LEVEL THERE ARE LEAKS AT VARIOUS LOCATIONS. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB06/27/2024REISSUE #35655163J. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT STAIRS 15 AND 16 THERE ARE SIGNS OF WATER PENETRATION FROM BULKHEAD AND ROOF THAT IS CAUSING DAMAGE TO THE CEILING AND WALLSNothing owed — awaiting certificate of correction
ECB06/27/2024REISSUE #35672061N. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: ON THE FIFTH FLOOR IN ROOM 526 THE CEILING IS DAMAGE, DUE TO LEAK ON THE ROOF. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB06/27/2024REISSUE #35672063R. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: OBSERVED AT ROOF TOP BULKHEAD, WATER IS PENETRATING THROUGH DOORS, AND IS GETTIING CORRIDORS, STAIRS, AND CEILING WALLS DAMAGE.Nothing owed — awaiting certificate of correction
ECB03/14/2023REISSUE 35655160Y FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ROOFTOP BULKHEAD WATER INFILTRATED THRU DOORS WATER GETTING STAIRS & CORRIDORS DAMAGE TO CEILING & WALLS.REMEDY:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB03/14/2023REISSUE 35655162H FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. 5TH FL RM 526 CEILING DAMAGED/SPALLING CAUSED BY WATER LEAK.REMEDY:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB03/14/2023REISSUE 35655161X FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ROOF LEVEL SEVERAL AREA LEAKS FROM PARAPET WALLS DETERIORATED CONDITIONS ON WALLS.REMEDY:REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB05/06/2022REISSUE35560952K(4/29/21) FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.@RM526@5FL,CEILING DAMAGED/DETERIORATED/SPALLING CAUSED BY LEAK FROM ROOF.REPAIR &OR REPLACENothing owed — awaiting certificate of correction
ECB05/06/2022REISSUE35560951Z(4/29/21) FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER@STAIRS15&16 WATER INFILTRATED FROM BULKHEAD&ROOF CAUSED SPALLING/DETERIORATED ON WALLS&CEILING 5-3FLS.REPAIR &OR REPLACENothing owed — awaiting certificate of correction
ECB05/06/2022REISSUE35560955X(4/29/21) FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:@ROOFTOP BULKHEAD WATER INFILTRATED THRU DOOR/DOORJAMB ONTO STAIRS&CORRIDORS DOORS.CAUSED DAMAGE TO CEILING&WALLS.REPAIR &OR REPLACENothing owed — awaiting certificate of correction
ECB05/06/2022REISSUE35560953M(4/29/21) FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:@ROOF LEVEL IN SEVERAL AREA LEAKS FROM PARAPET WEEP HOLES INTO BLDG.CAUSED DETERIORATED CONDITIONS ON WALLS&CEILING.REPAIR &OR REPLACENothing owed — awaiting certificate of correction
ECB04/29/2021REISSUE35422593M DOI5.13.19 FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER NOTE IN STAIRWAY15&16 WATER PENETRATION FROM ROOF LEAK CAUSING DAMAGE TO CEILING&WALL.REPAIR &/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB04/29/2021REISSUE35422589J DOI5.13.21 FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER NOTE@ROOF LEVEL,BULKHEAD WATER PENETRATION AROUND DOORJAMB CAUSING DAMAGE TO INTERIOR WALLS.REPAIR &/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB04/29/2021REISSUE35422591Z DOI5.13.19 FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER NOTE:@5FL 526 CEILING DAMAGE DUE TO ROOF LEAK.REPAIR &/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB04/29/2021REISSUE35422588H DOI5.13.21 FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER NOTE@ROOF LEVEL ROOF LEAKS IN VARIOUS AREAS&VARIOUS ROO LEAKS FROM PARAPET WEEP HOLES.REPAIR &/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB05/13/2019FAILURE TO MAINTAIN BLD.IN CODE COMPLIANT MANNER.NOTE:AT 5TH FLOOR 526CEILING DAMAGE DUE TO ROOF LEAK.REM:REPAIR OR REPLACE.Nothing owed — awaiting certificate of correction
ECB05/13/2019FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTE AT ROOF LEVEL ROOF LEAKS IN VARIOUS AREA AND VARIOUS ROOFS LEAKS FROM PARAPET WEEP HOLES. REMEDY: REPAIR AND OR REPLACENothing owed — awaiting certificate of correction
ECB05/13/2019FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTE IN STAIRWAY15&16,WATER PENETRATION FROM ROOF LEAK CAUSING DAMAGE TO CEILING AND WALL.REM:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB09/14/2011WORK W/O PERMIT.ERECTED FULL HEIGHT PARTITIONS IN CLASS ROOMS CREATING ADDITIONAL STORAGE ROOM OR OFFICE W/ SUSPENDED LIGHT FIXTURES PASSING THROUGH WALL W/O FIRE STOP.DIVIDED CLASSROOMS 429,328,318,208,206 W/Nothing owed — awaiting certificate of correction
Public elementary, junior or senior high · Owner of record: NYC DEPARTMENT OF EDUCATION · 322,000 sf lot · 0.66 FAR built · Flood zone X