HPD06/21/2026§ 27-2026 ADM CODE REMOVE ALL OBSTRUCTIONS AND REPAIR ALL DEFECTS IN AT WASTE LINE AT WASH BASIN IN THE BATHROOM LOCATED AT APT 409, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
ECB04/22/2026CLASS 1 - CEASE USE VIOLATION: FAILURE TO MAINTAIN ELEVATOR DEVICE IN A SAFE CONDITION. DOOR ZONE RESTRICTOR FOUND DEFECTIVE/INOPERATIVE, FAILING TO RESTRICT HOISTWAY DOOR OPENING OUTSIDE THE DOOR ZONE. IN ADDI$5K due
DOB03/27/2026BOROUGH COMMISSIONER HAS ORDERED ALL WORK STOPPED UNDERPERMIT# B00911674-I1 ON 3/26/26.
ECB03/24/2026FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS. NO CERTIFICATE OF CORRECTION ON FILE FOR VIO#391148744R AS OF 3/24/26., FILE A CERTIFICATE O
ECB03/24/2026FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS. NO CERTIFICATE OF CORRECTION ON FILE FOR VIO#39148741L AS OF 3/24/26., FILE A CERTIFICATE OF
ECB05/19/2026LAARS BOILER#1 HAS THREADED END ON SAFETY DISCHARGE PIPE+BROKEN TRI GAUGE ON HW STORAGE TANK#2+BYPASS AROUND BACKFLOW PREVENTER;CORRECT VIOLATION+SUBMIT CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB05/19/2026ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN THE BASEMENT LAUNDRY RM THE NEW INSTALLATION OF EMT PIPES AND 30 AMP RECEPTACLES, BREAKERS IN PANEL FOR NEW ELECTRIC DRYERS. 27-3018(B) CHECKED BIS / DOB NOW NO PERNothing owed — awaiting certificate of correction
ECB05/19/2026LAARS BOILER#3 HAS A OUTSIDE COMBUSTION AIR INLET LOUVER WITH A STRIPED BACKDRAFT DAMPER LOCKING SCREW+AO SMITH HWH HAS INCORRECT SAFETY DISCHARGE PIPE;CORRECT VIOLATION+SUBMIT CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB05/19/2026ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED ON THE 6TH FL THAT THE ELECTRICAL CLOSET IS NOT DEDICATED THE INSTALLATION OF INTERNET/ CAMERA EQUIPMENT IN THE SAME CLOSET ASNothing owed — awaiting certificate of correction
ECB05/22/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED UNPERMITTED FLEX HOSE ON EXHAUSTED OF COMMERCIAL DRYER SMOOTH INTERIOR. (MECHANICAL CODE 504.8.1), REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB05/22/2025EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING DOORS AT EXITS AND MECHANICAL/UTILITY ROOMS THROUGHOUT BUILDING. POTENTIAL HAZARD., REPAIR/REPLACE DOORNothing owed — awaiting certificate of correction
ECB02/13/2025FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS #39097465R ISSUED ON 10/19/2023, AND FAILURE TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28.201.1 AND 1 RCNY 102-01(D)(2). AN ACCEPTABLE CERTNothing owed — awaiting certificate of correction
ECB10/19/2023BACK FLOW PREVENTER FOR DOMESTIC HOT WATER BOILER LEAKING., MAINTAIN BOILER; CORRECT VIOLATING CONDITION AND SUBMIT A CERTIFICATE OF CORRECTION.Nothing owed — awaiting certificate of correction