DOB09/14/2022FAILURE TO SUBMIT AN ACCEPTABLE INSPECTN RPT FOR STRUCTURALLY COMPROMISED BLDG.
DOB03/04/2022V-DOB VIOLATION - ACTIVE
DOB04/05/2019VIOLATION ISSUED TO ELEVATOR - FAILURE TO FILE CATEGORY 1 2017 INSPECTION/TEST
ECB08/15/2018EXPIRED PERMIT FOR TEMPORARY CONST EQUIPMENT.NOTED:@TIME OF INSP I OBSERVED SIDEWALK SHED IN PLACE W/PERMIT #140649608 EXPIRED 6/13/2018.REM:COMPLY W/CODE-RENEW PERMIT.$-3,069 due
DOB07/11/2018V-DOB VIOLATION - ACTIVE
HPD12/22/2016§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT OVEN/RANGE IN THE ENTIRE APARTMENT LOCATED AT APT 803, 8th STORY, 3rd APARTMENT FROM EAST AT SOUTH
HPD12/10/2016§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES .. IN THE ENTIRE APARTMENT LOCATED AT APT 803, 8th STORY
HPD10/16/2016§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES ..... IN THE ROOM LOCATED AT B-ROOM 1002, 1st STORY, 2nd B-ROOM FROM NORTH AT EAST
HPD09/18/2016§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES .... IN THE ENTIRE APARTMENT LOCATED AT APT 817, 8th STORY, 1st APARTMENT FROM WEST AT NORTH
HPD09/08/2016§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES ... IN THE ENTIRE APARTMENT LOCATED AT APT 1817, 18th STORY, 1st APARTMENT FROM NORTH AT EAST
HPD08/28/2016§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT THE RANGE IN THE KITCHEN LOCATED AT APT 701, 7th STORY
HPD08/01/2016§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT STOVE IN THE ENTIRE APARTMENT LOCATED AT APT 713, 7th STORY
DOB06/01/2016FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB07/13/2015VW-VIOLATION WORK WITHOUT PERMIT - ACTIVE
HPD10/11/2014§ 27-2005, 2007 ADM CODE ARRANGE AND MAKE SELF-CLOSING THE DOORS AT ENTRANCE TO APARTMENT LOCATED AT APT 1804, 17th STORY, 4th APARTMENT FROM EAST AT SOUTH
DOB06/05/2014BLDG IS A 17 STORY CLASS 1 MASONRY CLAD FRAMED BLDG W/ CONCRETE FLOORS BUILT ON OR AROUND 1920. THE BUILDING IS CURRENTLY OWNED BY DHS AND HOUSES INDIVIDUALS AND FAMILIES ON THE UPPER FLOORS. ON 6/5/14 THE BUILDINGS EAST STAIRWAY "A" WAS VIEWED AS SEVEREL DETERIORATED IN SEVERAL LOCATIONS MAKING IT UNSAFE FOR PASSAGE
DOB04/15/2011V-DOB VIOLATION - ACTIVE
DOB01/18/2011V-DOB VIOLATION - ACTIVE
DOB01/13/1997V-DOB VIOLATION - ACTIVE
DOB02/27/1991VP-VIOLATION UNSERVED ECB-ACTIVE
DOB07/03/1990V-DOB VIOLATION - ACTIVE
ECB06/03/2024FOUND FEDERAL FST-175 NOT OPERABLE, WITH EXPOSED WIRING, SAFETY RELIEF VALVE (1) LABEL NOT LEGIBLE, BODY DRAINS ALSO MISSING.Nothing owed — awaiting certificate of correction
ECB06/03/2024WORK WITHOUT A PERMIT DEVICE HAVE A ACTIVE STATUS BUT WAS REMOVED.Nothing owed — awaiting certificate of correction
ECB06/03/2024FOUND FEDERAL FST-250, WITH EXPOSED WIRING, SAFETY RELIEF VALVE LABELS NOT LEGIBLE AND BODY DRAINS MISSING.Nothing owed — awaiting certificate of correction
ECB06/03/2024FUSE ON THE CONTROLLER NO GOOD JUMP(CU). IN CAR PHONE NOT WORKING.Nothing owed — awaiting certificate of correction
ECB06/03/2024DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED(CU). IN CAR PHONE NOT WORKING. EMERGENCY IN CAR STOP SWITCH NO BUZZER.Nothing owed — awaiting certificate of correction
ECB06/03/2024REAR DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED(CU). FUSE ON THE CONTROLLER JUMPED(CU). IN CAR PHONE NOT WORKING. CLEAN UP AND PROPERLY STORED EXTRA PARTS IN THE MACHINE ROOM.Nothing owed — awaiting certificate of correction
ECB04/28/2023CLASS 1: UPON INSPECTION FOUND DEVICE TO BE OUT OF SERVICE. RESTORE TO SERVICE REPAIR IMMEDIATELY AS PER 1RCNY 11-02.Nothing owed — awaiting certificate of correction
ECB01/11/2023AS PER ONE FEDERAL FST-250 BOILER; COVER FOR SOLENOID VALVE AT BURNER MISSING-HOLES IN CEILING-COMBUSTION AIR FAN NOT WORKING-NO GUARDS ON FAN BELT-HOLE IN DUCT FOR COMBUSTION AIR-NO BODY DRAINS ON SAFETY VALVENothing owed — awaiting certificate of correction
ECB01/10/2023OBSERVED IN THE GAS METER ROOM THAT IS LOCATED IN HE BASEMENT/CELLAR NO VENTILATION. GAS METER ROOMS SHALL BE VENTED., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB01/10/2023OBSERVED: AT THE BASEMENT LEVEL, ELECTRICAL ROOM AND STORAGE ROOMS, FOUNDATION WALLS WITH CRACKS, LOSS OF MORTAR AND STONES IN DIFFERENT LOCATIONS., MAINTAIN EXTERIOR BUILDING WALLNothing owed — awaiting certificate of correction
ECB01/10/2023AS PER ONE FEDERAL FST-175; OPEN ELECTRICAL BOX ON FLUE PIPE OF BOILER-CIRCULATOR IN FRONT OF BOILER LEAKING-NO BODY DRAINS ON SAFETY VALVE.Nothing owed — awaiting certificate of correction
ECB01/10/2023OBSERVED IN THE BOILER ROOM LOCATED IN BASEMENT/CELLAR DEFECTIVE FLANGE ON PUMP. FLANGE HAD AN ACTIVE LEAK THAT WAS DRIPPING ON ELECTRICAL CONDUIT., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB01/10/2023OBSERVED IN THE BOILER ROOM LOCATED IN THE BASEMENT BROKEN PIPE VENT USED FOR MECHANICAL VENTILATION., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB01/10/2023OBSERVED: FROM CELLAR LEVEL TO 18TH FLOOR, EXISTING EMERGENCY LIGHTS (28 UND) ARE NOT OPERATIONAL WHEN TESTED., REPAIR/REPLACE LIGHTINGNothing owed — awaiting certificate of correction
ECB12/21/2022ELEVATOR CURRENTLY STUCK ON 18TH FLOOR WITH DOORS CLOSED AND SAFETY CIRCUITS OPEN; ELEVATOR OUT OF SERVICE; REPAIR AND RETURN TO SERVICENothing owed — awaiting certificate of correction
ECB07/12/2022UPON INSPECTION ENTIRE DEVICE FOUND TO BE OUT OF SERVICE. REPAIR AND RETURN TO SERVICE IMMEDIATELY AS WELL AS NOTIFY THE DEPT. OF BUILDINGS.Nothing owed — awaiting certificate of correction
ECB04/19/2022I DID NOT OBSERVE VENTILATION IN THE GAS METER ROOM AS PER APPENDIX E OF THE FGC GAS METER ROOM SHALL HAVE PROPER VENTILATION., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB04/19/20222/X/10 OUT SIDE COMM INOPERATIVE REPAIR,52/O/2 HOIST ROPES DIRTY CLEAN,59/M/P MACHINE BRAKE TAG EXPIRED PROVIDE.Nothing owed — awaiting certificate of correction
ECB01/26/2022APARTMENTS ON THE 1 LINE THROUGH THE 3 LINE(701- 702 703, 1501 AND 1601) DO NOT HAVE GAS FOR COOKING. ITS FROM THE 7 FLOOR TO THE 18 FL. THE GAS IS WORKING IN THE BUILDING IN THE OTHER APTS., REPAIR AND/OR REPLNothing owed — awaiting certificate of correction
ECB12/22/2021I DID NOT OBSERVE ANY FRESH AIR VENTILATION IN THE GAS METER ROOM., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB12/13/2021ELEVATOR REMOVED WITHOUT PERMITNothing owed — awaiting certificate of correction
ECB10/15/2021CONDENSATE PUMP NEAR BOILER NUMBER ONE W/OPEN ELECTRICAL CONNECTION BOX-GUARDS FOR FUEL PUMP PULLEYS NOT IN PLACE.Nothing owed — awaiting certificate of correction
ECB09/30/2021UNLAWFUL ACTS,FAILURE TO COMPLY W/ AN ORDER OF THE COMMISSIONER. FAILURE TO CORRECT AND CERTIFY SUMMONS#39009608M WORK W/O A PERMIT ON EVERYFLOOR THE INSTALLATION OF A 42 CKT PANEL AND 4X4 J-BOX AND A RUN OF 4"Nothing owed — awaiting certificate of correction
ECB09/24/2021NOTED: OBSERVED EXISTING EMERGENCY LIGHT WITH BATTERY BACKUP POWER BY 1710,1608, ENTIRE 14TH. FLOOR, 9TH. FLOOR STAIR "A", 7TH. FLOOR STAIR "A", BY ROOM #708, 6TH. FLOOR STAIR "A", 4TH. FLOOR - BY ROOM #410, 3RNothing owed — awaiting certificate of correction
ECB07/15/2021FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER AT TIME OF INSPECTION NOTED:AT CELLAR GAS METER ROOM.HAS NO NATURAL OR MECHANICAL VENTALATION. REMEDY:COMPLY W/CODE.Nothing owed — awaiting certificate of correction
ECB07/09/2021AN UNLAWFUL ACT.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.FAILURE TO CORRECT AND CERTIFY SUMMONS#39009608M & 39009609Y ISSUED ON 9/12/2019 FOR ELECTRICAL WORK WITHOUT A PERMIT AND UNAPPROVED/UNSAFE/UNNothing owed — awaiting certificate of correction
ECB06/04/2021FAILURE TO MAINTAIN IN CODE COMPLIANT MANNER.NO FIRE STOPPING PER BC 712.3;27-345.NOTE AT CELLAR LEVEL AT GAS METER ROOM NO FIRE STOPPING AROUND PIPES AND HOLES PENETRATING THROUGH WALLS.REM:PROVIDE AND MAINTAINothing owed — awaiting certificate of correction
ECB06/04/202128-301.1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NO FRESH AIR VENTILATORS NOTE:AT CELLAR LEVEL IN GAS METER ROOM NO FRESH AIR VENTILATION PROVIDED.REM:COMPLY WITH VIOLATION PROVIDE VENTILATION.Nothing owed — awaiting certificate of correction
ECB05/28/2021FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER I OBSERVED ON THE GROUND FLOOR ALARM PANEL FOR FIRE COMMAND STATION WAS NOT WORKING. ALSO 18 FLOOR NO ACTIVE SPRINKLER SYSTEM IN PLACE GAGE WAS SHOWING ZERONothing owed — awaiting certificate of correction
ECB04/16/2021FAILURE TO MAINTIAN BUILDING IN CODE-COMPLIANT MANNER NOTED:AT TIME OFMY INSPECTION I OBSERVED AT CELLAR LEVEL IN GAS METER ROOM I OBSERVED PENETRATING HOLES IN THE WALL AROUND NO FIRE STOPPING WAS PROVIDE,VIOLNothing owed — awaiting certificate of correction
ECB04/16/2021FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM NOTED AT TIME OF MY INSPECTION I OBSERVED AT GAS METER ROOM THERE NO FRESH AIR VENTILATION IN GAS METER ROONothing owed — awaiting certificate of correction
ECB03/01/2021FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NO FIRE STOPPING PERBC712.3;27-345.NOTED:AT CELLAR LEVEL IN GAS METER RM OBSERVE PENETRATING HOLES IN THE WALL(AROUND PIPE & ELSEWHERE).REMEDY:REPAIR OR REPLACENothing owed — awaiting certificate of correction
ECB03/01/2021FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER-FAILURE TO PROVIDE VENTILATION TO GAS METER RM.NOTED:NO FRESH AIR VENTILLATION IN GAS METER RM.REMEDY: REPAIR OR REPLACENothing owed — awaiting certificate of correction
ECB12/02/2020GAS PIOLIT REGULATOR DEFECTIVE-#1 HW STORAGE TANK TEMPERATURE GAUGE DEFECTIVE-CONDENSATE TANK GLASS UNPROTECTED-HW COIL IS MISSING THE HW MIXING VALVE; CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB10/20/2020FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER: FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM. NOTE NO FRESH AIR VENTILATION IN GAS METER ROOM. REMEDY: REPAIR AND OR REPLACE PROVIDE VENTILATIONNothing owed — awaiting certificate of correction
ECB10/20/2020FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:NO FIRE STOPPINGPER BC 712.3;27-345. NOTE AT CELLAR LEVEL IN GAS METER ROOM NO FIRE STOPPING AROUND PIPES PENETRATING THROUGH WALL. REMEDY:PROVIDE AND MAINTNothing owed — awaiting certificate of correction
ECB08/14/2020FAILURE TO MAINTAIN BUILDINGIN CODE COMPLIANT MANNER NO FIRE STOPPING PER BC 712,7L27-345 NOET AT CELLAR LEVEL IN GAS METER ROOM NO FIRE STOPPING AROUND PIPES PENETRTAING THRU WALL PROVIDE AND MAINTAIN FIRE STONothing owed — awaiting certificate of correction
ECB08/14/2020FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER FAILURE TO PROVIDE VENTALITION TO GAS METER ROOM PER 115.6(1968 CODE) NOTE AT GAS METER ROOM NO FRESH AIR VENTALATOIN IN ROOM PROVIDE VENTILATIONNothing owed — awaiting certificate of correction
ECB01/22/2020FAILURE TO MAINTAIN BUILDING CODE-COMPLIANT MANNER.NOTED:AT CELLAR LEVEL AT GAS METER ROOM HAS NO REQUIRED VENTELTION FRESH AIR OR MECHANICAL.NEED TO PROVIDE FRESH AIR VENTELATION IN GAS ROOM.REMEDY:COMPLY WITHNothing owed — awaiting certificate of correction
ECB12/14/2019FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED AT CELLAR:CELLAR GAS METER ROOM HAS NO REQUIRED VENTELATION FRESH AIR OR MECHANICAL.REMEDY:REPAIR/REPLACE.Nothing owed — awaiting certificate of correction
ECB11/08/2019AN UNLAWFUL ACT FAILURE TO COMPLY WITH AN ORDER FO THE COMMISSIONER FAILURE TO CORRECT AND CERTIFY SUMMONS NU,BERS 39009608M AND 390096094.COMPLY WITH EC CODE/OBTAIN PERMITNothing owed — awaiting certificate of correction
ECB10/24/2019FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTE CELLAR LEVEL IN GAS METER ROOM NO FRESH AIR VENTILATION NEED TO PROVIDED FRESH AIR VENT.REMEDY:REPAIR OR REPLACE.Nothing owed — awaiting certificate of correction
ECB10/07/2019(C/U 5A10); 50B10 (5,A,10) DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLE. THIS IS A SAFETY DEVICE TO ENSURE PASSENGERS SAFETY. (50,B,10) GENERATOR DEFECTIVE VIBRATING AND RUMBLING NOISENothing owed — awaiting certificate of correction
ECB09/20/2019I OBSERVED IN THE CELLAR TEMPORARY WIRING NOT SUPPORTED PROPERLY, OPEN SPLICES ON THE CONDUCTORS, EXPOSED ENERGIZED CONDUCTORS SUBJECT TO UNINTENTIONAL CONTACT, TEMPORARY LIGHTS WITH DEFECTIVE CAGES, COMPLY WITNothing owed — awaiting certificate of correction
ECB09/20/2019I OBSERVED IN GAT METER ROOM ON THE CELLAR LEVEL NO FRESH AIR VENTILATION FOR THE GAS METER., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB09/20/2019I OBSERVED ON EVERY FLOOR A NEW 42 CIRCUIT PANEL, AND 4FT X 4FT JUNCTION BOXES, I OBSERVED 10 4 INCH ELECTRICAL CONDUIT RUNNING FROM THE 1ST FLOOR TO THE TOP FLOOR. I OBSERVED IN THE 1ST FLOOR STAIRWELL 2FT XNothing owed — awaiting certificate of correction
ECB09/17/2019FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT TIME OFINSPECTION I OBSERVED AT CELLAR IN GAS METER ROOM NO FRSH AIR VENT,NEED TO PROVIDE VENTILATION IN GAS METER ROOM AND COMPLY WITH SUMMON.REMENothing owed — awaiting certificate of correction
ECB09/10/2019(CEASE USE)5A10-DOOR ZONE RESTRICTOR NOT WORKING PLUNGES TAMPERED WITHTHIS IS A SAFETY DEVICE TO ENSURE PASSENGERS SAFETY.REPAIR RESTRICTOR AND CONTACT NYCDOB FOR REINSPECTION.Nothing owed — awaiting certificate of correction
ECB05/09/2019EXPOSED WIRING AT COMBUSTION AIR FAN. HOLES ON CEILING AND WALLS. OIL PUMP SET MISSING BELT GUARD. SAFETY RELIEF DISCHARGE PIPES NEED PROPER SUPPORT.Nothing owed — awaiting certificate of correction
ECB05/05/2019FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUM/VIO #35386429P ISSUED ON 02/22/19 &/OR TO FILE A C OF C PURSUANT TO 28-201.1 & 1RCNY 102-01. NO C OF C ON FILE. REMEDY: COMPLY WITH COMMISSIONER'Nothing owed — awaiting certificate of correction
ECB02/22/2019FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT TIME OF INSPECTION I OBSERVED NO FRESH AIR VENT AT CELLAR IN GAS METER RM NEED TO COMLY WITH SUMONS AND PROVIDE FRESH AIR VENTILATION IN GAS METNothing owed — awaiting certificate of correction
ECB12/28/2018FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLAINT MANNER. NOTED: NO VENT/FRESH AIR INTAKE PROVIDED AT CELLAR GAS METER ROOM. REM: COMPLY WITH SUMMONS. PROVIDE FRESH AIR INTAKE/VENT.Nothing owed — awaiting certificate of correction
ECB11/09/2018FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER NOTED: NO FRESH AIR INTAKE/VENT PROVIDED FOR GAS METER ROOM AT CELLAR LEVEL. RMDY: COMPLY WITH SUMMONS. PROVIDED FRESH AIR INTAKE.Nothing owed — awaiting certificate of correction
ECB08/06/2018FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM. NOTE: AT CELLAR IN GAS METER ROOM, NO FRESH AIR VENT/INTAKE DRAWN FROM OUTSIDE.Nothing owed — awaiting certificate of correction
ECB06/26/2018FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT CELLAR IN GAS METER ROOM NO FRESH AIR VENT/INTAKE DRAWN FROM OUTSIDE.REM:REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB04/28/2018FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION 35324888K ISSUED ON 3/14/18 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01. FAILURE TO MAINTAIN BUILDINGNothing owed — awaiting certificate of correction
ECB03/14/2018FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTED:@GAS METER ROOM @BSMT LEVEL NO FRESH AIR VENT DRAWN FROM OUTSIDE.REM:COMPLY W/CODE./INSTALL VENT.Nothing owed — awaiting certificate of correction
ECB03/14/2018FAILURE TO MAINTAIN BUIDLING IN CODE-COMPLIANT MANNER.ILLUMINATION FOREXITS,EXIT DISCHARGES,AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:EXISTING EMERGENCY LIGHTS NEXT TO ROOM 1802,1502,1408,203 KITCHEN ANDNothing owed — awaiting certificate of correction
ECB03/14/2018OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BUILDING DEPT RECORDS.NOTED:OBSERVED FLOORS TWO(2)THROUGH SIX(6)HAVE BEEN CONVERTED INTO OFFICES,CONTRARY TO CERTIFICATE OF OCCUPANCY #65791Nothing owed — awaiting certificate of correction
ECB02/02/2018FAILURE TO COMPLY W/COMM'S OREDER CONTAINED IN SUMM/VIOL#35297606M ISSUED ON 11/24/17 AND TO FILE A COFC PURSUANT TO 28-201.1 AND 1RCNY 102-01.AT GAS METER RM,THERE WAS ILLEGAL STORAGE OF COMBUSTIBLE MATERIALSNothing owed — awaiting certificate of correction
ECB02/02/2018FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.AT GAS METER RM(2 LOCATION)IN BSMT,NO FRESH AIR VENT DRAWN FROM OUTSIDE.REM:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB11/24/2017FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT TIME OF INSPECTION, NO FRESH AIR VENT IN GAS METER ROOM.Nothing owed — awaiting certificate of correction
ECB11/24/2017FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT TIME OF INSPECTION THE GAS METER ROOM WAS CLUTTERED WITH COMBUSTIBLE MATERIALS. INCLUDING BUT NOT LIMITED TO FLAMMABLE STORAGE CABINET, PAINTS, CNothing owed — awaiting certificate of correction
ECB10/27/201797R5)PROPERLY FILE WITH DEPT OF BUILDING FOR DISMANTED AND PERFORM INSPECTION WITH THIS DEPT.Nothing owed — awaiting certificate of correction
ECB08/29/2017FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON 08/29/17 AT ABOVE ADDRESS EXCESSIVE STORAGE IN GAS METER ROOM. REMEDY: REPAIR AND OR REPLACE.Nothing owed — awaiting certificate of correction
ECB08/29/2017FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT CELLAR IN VARIOUS LOCATIONS AT CEILING WATER PENETRATING CAUSING SHEET ROCK AT CEILING TO BUCKLE,CRAKCK AND CRUMBLE.REMEDY:REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB08/29/2017FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON 8/29/17 AT ABOVE ADDRESS NO FRESH AIR VENTILATION IN THE GAS METER ROOM LOCATED IN THE BASEMENT.REMEDY:REPAIR AND OR REPLACENothing owed — awaiting certificate of correction
ECB08/29/2017401.1 GAS PIPING NOT LABELED.OBSERVED ON 8/29/17 AT ABOVE ADDRESS CERTAIN SECTIONS ON THE GAS PIPING NOT LABELED.COMPLY IWTH SUMMONS.Nothing owed — awaiting certificate of correction
ECB04/20/2017C/U-59L11,59U15,68B7. MACHINE BRAKE LININGS ARE DETERIORAED TO THE POINT OF USELESSNESS. NO ANNUAL BRAKE TAG, NO ENTRY OF DATE OF ANNUAL BRAKE MAINENANCE IN LOG.Nothing owed — awaiting certificate of correction
ECB02/24/2016EXIT DOOR NOT SELF-CLISING.THE FOLLOWING DOORS NOT SELF-CLOSING:EXIT DOORS ADJACENT TO ELEVATOR DOORS AT ALL FLOOR LEVELS,EXIT DOOR STAIR "BB" 1ST FLR REAR EXIT DOOR AND EXIT DOOR "B15".RMDY: REPAIR/REPLC DOONothing owed — awaiting certificate of correction
ECB02/24/201627-766 - FAILURE TO PROVIDE FRESH AIR IN GAS METER ROOM AS PER RS 16/P 155.4 AND TPPN 106/1995. REISSUED ECBC 35120338L. RMDY: PROVIDE PERMANENT FRESH AIR INTAKE.Nothing owed — awaiting certificate of correction
ECB02/24/2016FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3, 27-345. NOTED: NO FIRE STOPPING AT PIEP(S) PENETRATIONAREAS AT ENTIRE CELLAR. REISSUED ECB #35094757J RMDY:PROVIDE/MAINTAINNothing owed — awaiting certificate of correction
ECB02/24/2016OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BUILDING DEPT RECORDS. COFO 65794 INDICATES LEGAL APTS AND HOTEL ROOMSON EACH STORY. ILLEGAL OCCUPANCY NOTED: 2ND THROUGH 6TH FLOORS ARE NOWNothing owed — awaiting certificate of correction
ECB02/22/2016FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. DEFECTS NOTED:WATERDAMAGE TO CEILING AT ROOM #1509,ROOM #1`406,ROOM #817 AND ROOM#1217.Nothing owed — awaiting certificate of correction
ECB10/14/2015FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN NOV #35094758Z ISSUED ON 6/4/14 & TO FILE A C OF C PURSUANT TO 28-201.1,28-204.4 & 1RCNY 102-01. REMEDY: COMPLY W/COMM'S ORDER &/OR FILE A C OF C.Nothing owed — awaiting certificate of correction
ECB08/18/2015FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN NOV #35120340K ISSUED ON 3/09/15 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1,28-204.4 AND 1RCNY 102-01.Nothing owed — awaiting certificate of correction
ECB08/18/2015FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN NOV #35094758L ISSUED ON 6/04/14 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1,28-204.4 AND 1RCNY 102-01.WORK WITHOUT A PERMIT. REMOVANothing owed — awaiting certificate of correction
ECB08/10/2015/97R05/ 97R05-WORK WITHOUT PERMIT. DEVICE# 1P12693 WAS DISMANTLED WITHOUT A PERMIT BEING OBTAINED & APPLICATION BEING FILED REMEDY FILE APPLICATION & OBTAIN PERMIT FOR WORK OF DISMANTLE OF DEVICE 1P12693 SCHEDUNothing owed — awaiting certificate of correction
ECB06/27/2015FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINING IN NOTICE OF VIOLATION # 35094758L ISSUED ON 06/04/14. FOR WORK WITHOUT A PERMIT REMOVAL OF GAS LINES FROM 6TH FLOOR TO 2ND FLOOR. REMEDY: COMPLY WITHNothing owed — awaiting certificate of correction