ECB11/21/2024OBSERVED NON SELF CLOSING DOORS THROUGHOUT BUILDING. INCASE OF EMERGENCY THIS IS A FIRE OR EVACUATION HAZARD., REPAIR/REPLACE DOORNothing owed — awaiting certificate of correction
ECB11/21/2024OBSERVED GAS LEAF BLOWERS BEING STORED IN ROOM ADJACENT FROM THE BOILER ROOM. NO GAS FIRED EQUIPMENT SHALL BE STORED INSIDE OF BUILDING., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB11/19/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED CEILING CHIPPED AND FALLING OFF CEILING. THIS IS A OVERHEAD HAZARD. LOCATED IN AUDITORIUM/ LUNCHROOM., REPAIR AND/REPLACENothing owed — awaiting certificate of correction
ECB07/26/2024UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS AS STATED IN ECB# 39077703P ISSUED ON 01/11/2023 AND FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01 FOR FAILURE TO GROUND ELECNothing owed — awaiting certificate of correction
ECB07/26/2024I OBSERVED IN THE MAIN ELECTRICAL ROOM THE SERVICE DISCONNECT SWITCH IMPROPER FUSING. THE SWITCH HAS (2) 300 AMP FUSES AND (1) 400 AMP FUSE. ALL FUSES IN A DISCONNECT SHALL BE COORDINATED., PROVIDE PROTECTION ANothing owed — awaiting certificate of correction
ECB07/26/2024FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS AS STATED IN ECB# 39077701L ISSUED ON 01/11/2023 FOR IMPROPER FUSING OF ELECTRICAL CONDUCTORS AND FILE A CERTIFICATE OF CORRECTION AS PURSUANT TO 28-201.1 AND 1RCNYNothing owed — awaiting certificate of correction
ECB05/17/2024UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS AS STATED IN ECB # 39077698J ISSUED ON 01/11/2023 AND FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01. FAILURE TO SAFEGUARD PERNothing owed — awaiting certificate of correction
ECB05/17/2024UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS AS STATED IN ECB # 39077703P ISSUED ON 01/11/2023 AND FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01. FAILURE TO SAFEGUARD PERNothing owed — awaiting certificate of correction
ECB03/07/2024UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS AS STATED IN ECB # 39077701L ISSUED ON 01/11/2023 AND FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01. FAILURE TO SAFEGUARD PERNothing owed — awaiting certificate of correction
ECB01/02/2024UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39077703P ISSUED ON 01/13/23 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01., COMPLYNothing owed — awaiting certificate of correction
ECB01/02/2024UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39077701L ISSUED ON 08/03/23 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01., COMPLYNothing owed — awaiting certificate of correction
ECB01/02/2024UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39077698J ISSUED ON 01/11/23 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01., COMPLYNothing owed — awaiting certificate of correction
ECB11/15/2023I OBSERVED IN THE MAIN ELECTRICAL ROOM THE INSTALLATION OF (2) 300 AMP FUSES AND (1) 400 AMP FUSE. THIS IS NOT PERMITTED ALL FUSING OF CONDUCTORS SHALL BE THE SAME RATING. PHOTOS TAKEN., PROVIDE PROTECTION AGAINothing owed — awaiting certificate of correction
ECB11/15/2023I OBSERVED IN THE MAIN ELECTRICAL ROOM THE INSTALLATION OF THE GROUND BAR FOR THE SERVICE DISCONNECTS WITH NO MAIN CONDUCTOR FROM THE WATER MAIN. A SUPPLEMENTAL GROUND ROD IS PROVIDING THE PRIMARY GROUND., PROVNothing owed — awaiting certificate of correction
ECB08/04/2023-EMERGENCY EXIT ROOF DOORS DO NOT SELF-CLOSE LOCATED ON ROOF, BOTH STAIRCASES/BULDHEADS. EMERGENCY EXIT DOOR AND DOOR #5, FIRE PROOF SELF-CLOSING DOES NOT SHUT AND LATCH LOCATED IN CORRIDOR OF STAIRCASE A., REPNothing owed — awaiting certificate of correction
ECB01/25/2023I OBSERVED IN THE MAIN DISCONNECT SWITCHES THE ELECTRICAL ROOM THE IMPROPER TERMINATION OF THE CONDUCTORS .FOR THE TERMINATION OF TWO CONDUCTORS UNDER A SINGLE LUG IT SHALL BE OF THE TYPE DESIGNED FOR SUCH INSTNothing owed — awaiting certificate of correction
ECB01/25/2023I OBSERVED IN THE MAIN ELECTRICAL ROOM THE INSTALLATION OF (2) 300 AMP FUSES AND (1) 400 AMP FUSES. THIS NOT PERMITTED ALL FUSING OF CONDUCTORS ARE TO BE OF THE SAME RATING. PHOTOS TAKEN., PROVIDE PROTECTION AGNothing owed — awaiting certificate of correction
ECB01/25/2023OBSERVED: AT SECOND FLOOR CORRIDOR, FIRE PROOF WALLS, SEVERAL CRACKS NEAR RMS, 214/215/212/206/202/201. ALSO, AT CELLAR LEVEL, CORRIDOR NEAR MAINTENCE RM AND ELECTRICAL ROOM., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB01/25/2023OBSERVED: AT GROUND LEVEL, MAINT ENTRANCE STARIR (RIGHT SIDE) & RAMP (LEFT SIDE) MISSING HANDRAILS, REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB01/25/2023OBSERVED: FIRE PROOF SELF-CLOSING DOOR AT SECOND FL, SMOKE DOOR NEAR RM 213 & FIRST FL, EXIT DOORS # 3,4,2, LIBRARY (OBSTRUCTION EXIT WAY) & CAFETERIA (3 DOORS) ALSO, CAFETERIA/ EXIT DOOR ARE MISSING PUSH BARS.Nothing owed — awaiting certificate of correction
ECB01/25/2023I OBSERVED ON ROOFTOP A THE USE OF FLEXIBLE RUBBER CORD THROUGH THE CONCRETE WALL AND IMPROPERLY SPLICED WITH EXPOSED AND ENERGIZED WIRING SUPPLYING POWER TO THE DOWN LIGHT. AS EC 400.8 FLEXIBLE CORDS ARE NOT PNothing owed — awaiting certificate of correction
ECB01/25/2023I OBSERVED IN THE ELECTRICAL SERVICE ROOM THE INSTALLATION OF A GROUND BAR FOR THE SERVICE DISCONNECTS WITH NO MAIN GROUND ELECTRODE CONDUCTOR FROM THE WATER MAIN. A SUPPLEMENTAL GROUND ROD IS SUPPLYING THE PRINothing owed — awaiting certificate of correction
ECB01/25/2023I OBSERVED ON THE ROOFTOP "A" SIDE 8(#S 5-6-8-9-10-11-13-14) DEFECTIVE/INOPERABLE EXHAUST FANS. PHOTOS TAKEN, COMPLY WITH EC; REPAIR/OR REPLACE DEFECTIVE EQUIPMENT.Nothing owed — awaiting certificate of correction
ECB06/08/2022REPAIR CLAMP USED TO STOP LEAK-CORROSION ON VALVE BOILER NO. 2-PIPING UNCAPPED AT MIXING VALVE AND PIPING CAPPED W/WASTE FITTING-ELECTRICAL CONNECTION BOX FOR FIRE SWITCH W/O A COVER-NO SHUT-OFF VALVE FUEL OILNothing owed — awaiting certificate of correction
ECB06/07/2022FIRE PROOF SELF-CLOSING DOOR AT 3RD FL, SMOKE DOOR STAIR A, SMOKE DOOR NEAR RM 313, AT SECOND FL, SMOKE DOOR NEAR RM 213 & FIRST FL, EXIT DOORS # 3,4,2 & CAFETERIA (3 DOORS) ALSO, CAFETERIA/ EXIT DOOR ARE MISSINothing owed — awaiting certificate of correction
ECB12/13/2021NOTED: OBSERVED FIRE PROOF SELF CLOSING DOORS AT ALL FLOORS IN STAIRWELL "A" AND "B" ARE RACKED, AND DAMAGED DOOR CLOSER HARDWARE AND ARE EXCESSIVELY RUBBING ON THE FLOORS NOT ALLOWING THE DOORS TO SELF CLOSE.,Nothing owed — awaiting certificate of correction
ECB12/13/2021I OBSERVED IN THE MAIN ELECTRICAL ROOM, AN EXCESSIVE AMOUNT OF WATER LEAKING FROM ABOVE ONTO THE MAIN ELECTRICAL EQUIPMENT. EQUIPMENT IS CURRENTLY BEING DETERIORATED, AND THE WATER POOLING CAN LEAD TO A SHOCK HNothing owed — awaiting certificate of correction
ECB10/15/2021FOUND FITZGIBBON BOILER ACTIVE WITH DEFECTS. COMBUSTION AIR FAN SAIL SWITCH DEFECTIVE. CORRECT ALL VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORRECTION.Nothing owed — awaiting certificate of correction
ECB08/27/2021AN UNLAWFUL ACT.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.FAILURE TO CORRECT AND CERTIFY SUMMONS#35253004K ISSUED ON 4/12/2017,FORFAILURE TO GROUND THE ELECTRICAL SERVICE IN THE BASEMENT.ALSO SUMMONS#Nothing owed — awaiting certificate of correction
ECB10/04/2019NOTED: OPERATING A PLACE OF ASSEMBLY AT 1ST FLOOR CAFETERIA/GYM, WITHOUT A VALID CERTIFICATE TO OPERATE, TABLES AND CHAIRS ARRANGED FOR SEATING 93 PERSONS., OBTAIN PLACE OF ASSEMBLY CERTIFICATE OF OPERATIONNothing owed — awaiting certificate of correction
ECB10/04/2019I OBSERVED IN THE ELECTRICAL SERVICE ROOM THE INSTALLATION OF A GROUND BAR FOR THE SERVICE DISCONNECTS WITH NO MAIN GROUNDING ELECTRODE CONDUCTOR FROM THE WATER MAIN. A SUPPLEMENTAL GROUND ROD CONDUCTOR IS SUPPNothing owed — awaiting certificate of correction
ECB10/04/2019I OBSERVED IN THE ELECTRICAL ROOM, SERVICE SWITCHES WITH IMPROPER FUSING , , PROVIDE PROTECTION AGAINST OVERCURRENT; INSTALL FUSES UNIFORMLY.Nothing owed — awaiting certificate of correction
ECB10/04/2019I OBSERVED IN THE ELECTRICAL EQUIPMENT ROOM THE INSTALLATION OF TWO SERVICE SWITCHES WITH CONDUITS AND WIRING TO SUPPLY POWER TO THE KITCHEN AND A SECOND UNSPECIFIED LOCATION. THE CONNECTIONS TO PROVIDE POWER ANothing owed — awaiting certificate of correction
ECB10/04/2019NOTED: EXIT DOORS AT 3RD AND 2ND FLOOR STAIRWAY A, AND 1ST FLOOR STAIRWAY B, DO NOT SELF CLOSE, DOORS ARE RUBBING ON THE FLOOR. , REPAIR/REPLACE DOORNothing owed — awaiting certificate of correction
ECB05/09/2019PIPING ON FEED WATER LEAK-SMOKE ALARM DEFECTIVE-BACKFLOW DRAIN NOT CONNECTED-SURFACE BLOW DOWN DRAIN NOT PIPED-BODY DRAINS NOT INSTALLED ON SAFETY VALVES-FLAME GLASS MISSING-LOW WATER CUTOFF VALVE DEFECTIVE; CONothing owed — awaiting certificate of correction
ECB04/17/2019WORK WITHOUT A PERMIT. OBSERVED IN CELLAR PLUMBING WORK DONE TO REMOVE TWO TEMPORARY AVL PIPES LINE FROM TWO BOILERS WITHOUT A PERMIT. REM: OBTAIN ALL REQUIRED PERMITS.Nothing owed — awaiting certificate of correction
ECB08/21/2018B254,42,50A-50F 50A-NEED SUMP PUMP TO BE REPAIRED OR REPLACED; 50B- SMOKE ALARM NOT WORKING; 50C-FRESH AIR FAN NOT WORKING AND MISSING SAIL SWITCH; 50D- NO OPEN BALL VALVES; 50E-MISSING ADDER AND PLATFORMNothing owed — awaiting certificate of correction
ECB04/02/2018FAILURE TO MAINTAIN BLDG IN CODE COMPIANT MANNER. OBSERVED ON 4218 AT ABOVE ADDRESS ACTIVE LEAK ON WATER PIPING IN WATER/SPRINKLER ROOM. RMDY: REPAIR AND/OR REPLACE. PHOTOS TAKEN.............................Nothing owed — awaiting certificate of correction
ECB02/02/2018UNLAWFUL ACTS. FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. IN AUGUST 21, 2017, 28, 17, APRIL 12, 2017. FOUR ELECTRICAL VIOLATIONS WAS ISSUED TO THE RESPONDENT. THE RESPONDENT FAILED TO COMPLY WITH (NYCNothing owed — awaiting certificate of correction
ECB08/28/2017FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNE:NO FIRE STOPPING PER BC 712.3:27-345. NOTED: AT CELLAR IN GAS METER ROOM,OPENINGS AROUND PLUMBING ELIMINATING FIRE STOPPING.REMEDY:PROVIDE/MAINTAIN FIRE STOPNothing owed — awaiting certificate of correction
ECB08/28/2017FAIL TO PROVIDE EFFECTIVE ELECTRICAL CONTINUITY FOR METAL RACEWAYS/ ENCLOSURES/CABLE ARMOR.OBSERVED SEALTITE IN KITCHEN DISCONNECTED FROM FIXED APPLIANCE WAITH WIRING EXPOSED.REMEDY:COMPLY WITH CODE/PROVIDENothing owed — awaiting certificate of correction
ECB08/28/2017FAIL TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.RC:INSTALLATION/MAINTENANCE OF PLUMBING MATERIALS/EQUIPMENT PER P.C. 102.3;27-902. OBSERVED ON 8/28/17 AT ABOVE ADDRESS JIM CAPS INSTALLED IN BASEMENT OUTSIDENothing owed — awaiting certificate of correction
ECB08/28/2017110.4 CONDUCTORS NOT PROPERLY INSTALLED /TERMINATED . OBSERVED PRIOR CONDITION NOT RECTIFIED AS PER PREVIOUS ECB #35253006Y. TWO CONDUCTORS TERMINATED UNDER A SINGLE LUG TERMINAL NOT DESIGNED FOR INSTALLATIONNothing owed — awaiting certificate of correction
ECB08/28/2017OPERATION OF A PLACE OF ASSEMBLY WITHOUT A CURRENT CERTIFICATE OF OPERATION.NOTED: NO CURRENT CERTIFICATE OF OPERATION FOR 1ST STORY CAFETERIA WITH MAXIMUM OCCUPANCY SIGN FOR 365 PERSON.REMEDY:OBTAIN A PLACENothing owed — awaiting certificate of correction
ECB08/21/2017UNLAWFUL ACTS.FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER.IN APRIL 12,2017, JUNE 26,2017.THREE ELECTRICAL VIOS WAS ISSUE TO THE RESPONDENT.THE RESPONDENT FAILED TO COMPLY W/(NYC) ELECTRICAL CODE #250.4,110Nothing owed — awaiting certificate of correction
ECB06/26/2017AN UNLAWFUL ACT. FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER. FAILED TO CORRECT & CERTIFY ECB#35253004K RECEIVED ON 3-12-17 FOR BROKEN OR MISSING THE MAIN HOUSE AROUNDING WIRE WHICH WAS CONNECTED TO THENothing owed — awaiting certificate of correction
ECB04/12/2017EC110.14A. CONDITIONS NOT PROPERLY INSTALLED/TERMINATED. I OBSERVED @ TIME OF INSP. THE OUTDOOR A.C. SERVICE SWITCHES WITH 2 CONDUCTORS SERVICE UNDER A SINGLE TERMINAL LUG, BSMT SERVICE SWITCHES WITH 2 CONDUCTONothing owed — awaiting certificate of correction
ECB04/12/2017FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. RE: INSTALLATION/MAINTENANCE OF PLUMBING MATERIALS/EQUIPMENT PER PC 102.3;27-302. OBSERVED ON 4/12/17 @ ABOVE ADDRESS JIM CAPS & ALSO IN ELECTRIC METER ROOM.Nothing owed — awaiting certificate of correction
ECB04/12/2017FAILURE TO GROUND ELECTRICAL SYSTEM. AT THE TIME OF INSP. I OBSERVED THE MAIN BLDG GROUND WAS CUT OFF FROM THE BLDG WATER MAIN PIPE. THIS ISAN IMMEDIATE HAZARD TO PERSON & PROPERTY AS IT DOESN'T ALLOW INCIDENTANothing owed — awaiting certificate of correction
ECB08/08/2016OPERATION OF A PLACE OF ASSEMBLY W/O A CURRENT CERTIFICATE OF OPERAT TION(PACO) NOTED: NO CURRENT CERTIFICATE OF OPERATION FOR 1ST FLOOR CAFETERIA WITH MAXIMUM OCCUPANCY SIGN POSTED FOR 365 PERSONS.PREVIOUSNothing owed — awaiting certificate of correction
ECB02/19/2016OPERATION OF PLACE OF ASSEMBLY W/O A CURRENT CERTIFICATE OF OPERATION.NOTED: OPERATING 1ST FLR CAFETERIA W/MAXIMUM OCCUPANCY 365 PERSONS W/OCURRET CERTIFICATE OF OPERAITONS.RMDY: OBTAIN A PLACE OF ASSEMBLY CERTNothing owed — awaiting certificate of correction