DOB04/15/2026Ftm bldg in a code compliant manner. Observed at exposure 1 and exposure 4 cracks, spalling stucco and corroded window lintels at multiple locations at exposure 2 visible cracks and hairline cracks observed. Remedy: repair and or replace
ECB07/14/2025Failure of permit holder to provide access to the construction site. At time of inspection, construction worker denied me access to the construction site with an active permit. Worker locked both entry doors wh$2K due
DOB01/15/2025Failure to maintain building in code compliant manner. Observed hazardous deteriorating facade conditions at all view exposures cracks/failed stucco at many areas. Remedy: maintain building repair and/or replace
DOB01/15/2025Emergency work order due to unstable side walk shed. Remedy: immediately repair and/or replace existing side walk shed under supervisions of NYC licensed professional
DOB09/24/2024Failure to maintain building in a code compliant manner.note at time o f inspection observed cracked/spalling stucco at several window lintel s and below window sills.observed cracks throughout the parapet wall a t EXP1,2,4.remedy:repair/replace
DOB05/07/2024Failure to maintain building in a code compliant manner. Note:- observed cracked/spalling stucco at several spandrel & lintels on multiple floors & exp #1,2,3 & 4. (north, south & west elevation) remedy: fix and/or repair
DOB01/02/2024Failure to maintain building in code compliant manner.exposure#1,2,&4 crack and spalling stucco at several spandrel and lintels on multiple floor repair and/or replace all cracks and spalling stucco
DOB01/02/2024Emergency work order due to hazrdous conditions on expo#1&4 conditions such as crack and spalling stucco at several spandrels and at parapet open cracks and bulging,sagging stucco at several lintels.remedy:immed repair and or replace all damaged stucco on facade
ECB10/06/2023At time of inspection observed exterior facades expo # 01 & 04 instate of disrepair conditions with minor cracks, spalling stucco over window lintels on various locations., repair and/or replace$625 due
ECB01/17/2020Failure to maintain bldg in code compliant manner.noted:at facade all exposures-cracks in masonry.rem: repair and/or replace$2K due
ECB11/10/2017Failure to maintain bldg in a code compliant manner.noted:at the time of inspection,observed cracks throughout masonry wall at exposure#3(rear)due to lack of maintenance or repair to this pre-existing condition$-1,500 due
ECB11/09/2017Failure to maintain bldg wall(s)or appurtenances.noted:@exp#3 wall hasverticle crack from 1ST story up to 6TH story.crack approx 2" wide.also,@bldg interior @public halls from 2ND story up to 6TH story,bricks c$-1,500 due
HPD09/12/2017§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX MISSING AT PUBLIC HALL, 1st STORY
HPD06/20/2017§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE LOCK AT MAILBOX FOR APARTMENT 4B AT PUBLIC HALL, 1st STORY
HPD06/20/2017§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED AT PUBLIC HALL, 1st STORY
HPD06/20/2017§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR MISSING AT PUBLIC HALL, 1st STORY
HPD06/20/2017§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX MISSING AT PUBLIC HALL, 1st STORY
HPD06/20/2017§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AT PUBLIC HALL, 1st STORY
HPD06/20/2017§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING, EAST AND NORTH WALLS AT FIRE STAIRS, 1st STORY
HPD06/20/2017§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT FIRE STAIRS, 3rd STORY
HPD06/20/2017§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT FIRE STAIRS, 1st STORY
HPD06/20/2017§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING AT BOILER ROOM DOOR AND AT PUBLIC HALL, 1st STORY
HPD06/20/2017§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING, EAST AND NORTH WALLS AT FIRE STAIRS, 1st STORY
HPD06/20/2017§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT FIRE STAIRS, 2nd STORY
HPD06/20/2017§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND EAST WALL AT FIRE STAIRS, 2nd STORY
HPD06/20/2017§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AND EAST WALL AT FIRE STAIRS, 2nd STORY
HPD06/20/2017§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AND EAST WALL AT FIRE STAIRS, 3rd STORY
HPD06/20/2017§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND EAST WALL AT FIRE STAIRS, 3rd STORY
HPD06/20/2017§ 27-2053 ADM CODE POST SIGN ON WALL OF ENTRANCE STORY BEARING NAME, ADDRESS INCLUDING APARTMENT NUMBER IF ANY, AND TELEPHONE NUMBER OF SUPERINTENDENT, JANITOR OR HOUSEKEEPER. AT PUBLIC HALL, 1st STORY
HPD01/20/2009SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 6A, 6th STORY, 4th APARTMENT FROM WEST AT NORTH
HPD01/20/2009SECTION 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK THROUGH THE CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 6A, 6th STORY, 4th APARTMENT FROM WEST AT NORTH
HPD05/21/2008SECTION 27-2005 ADM CODE FIRE ESCAPE DEFECTIVE. ADJUST THE DROPLADDER SO THAT IT WILL SLIDE EASILY IN THE GUIDE RODS AT WEST FIRE ESCAPE , 1st STORY
HPD08/05/2005SECTION 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF RUBBISH AT PUBLIC HALL, 1st STORY
HPD01/25/2005SECTION 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE GLASS PANE WINDOW W2 IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 2E, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD06/16/2004SECTION 27-2018 ADM CODE ABATE THE NUISANCE CONSISTING OF VERMIN roaches IN THE ENTIRE APARTMENT LOCATED AT APT 6E, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD06/16/2004SECTION 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 6E, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD05/04/2004Section 27-2018 ADM code abate the nuisance consisting of rodents , rats at basement
HPD12/15/2003SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE FOYER LOCATED AT APT 6D, 6th STORY, 1st APARTMENT FROM WEST AT NORTH
ECB11/20/2018Failure to comply with the commissioners order contained in summons/violation#353263456K issued on 11/10/17 and to file a certificate of correction pursuant to 28-201.1 and 1RCNY 102-01.comply with commissionerNothing owed — awaiting certificate of correction
Likely answered · the city's own records show a filing, but DOB's feed still lists these as active
DOB12/17/2021Failure to perform category 5 inspectionAnswered on the city's records: a Category 5 elevator report was filed since (Dec 17, 2021)
Old · issued 3+ years ago and still listed by DOB; nothing on the city's records either way
DOB09/27/2023Failure to maintain building exterior walls facade.observed multiple l locations with cracked/spalling stucco on exposure#1 north elevation &exposure#4 west elevation.remedy: maintain building exterior wall and facade.take approved safety measures where requiredIssued 2023; DOB's record still lists it as active
DOB02/07/2018Failure to certify correction on immediately hazardous (class 1) ECB violationIssued 2018; DOB's record still lists it as active2 identical filings
DOB11/14/2017Ftm.south brick masonry wall has significant cracks from cellar to roof.emerg shoring wrk has begun pursuant to DOB order#111317FEU10801A d to shore&brace wall.remedy:own retain pe eng'r eval struct&prep plan &obtain perm for perm repair or part replacement of brick wall.engage DOB cont'r beg wrk no later 12/18/17.wrk substant comp by 1/26/18Issued 2017; DOB's record still lists it as active
DOB11/13/2017Ftm bldg.south brick masonry wall has significant crack from cellar to roof.brick masonry can be removed by hand at upper flrs.remedy:immed engage pe eng'r® cont'r to prov int shoring&bracing to south wall estab monitoring prog for movement of bldg.sidewalk shed to protect e.96THST side.file perm w/48HRS of commencing wrkIssued 2017; DOB's record still lists it as active