ECB07/20/2026CLASS 2 ITEMS: NO EMERGENCY COMMUNICATION DEVICE/TELEPHONE PROVIDED IN ELEVATOR CAR, IN VIOLATION OF ASME A17.1-2013 2.27.1.1 AND 8.6.1.2.1 BRAKE MAINTENANCE TAG IS EXPIRED, INDICATING REQUIRED PERIODIC MAINTEN$625 due
HPD06/16/2026§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH SET AT DOOR AT LAUNDRY ROOM, 3rd STORY
ECB05/04/2026CLASS 2 ITEMS: . EMERGENCY TWO-WAY COMMUNICATION SYSTEM IS INOPERATIVE AND DOES NOT PROVIDE COMMUNICATION WITH AN AUTHORIZED PARTY, IN VIOLATION OF ASME A17.1-2013 2.27.1.1 CAR VENTILATION FAN IS INOPERATIVE AN$310 due
ECB04/16/2026CLASS 2 ITEMS: IN-CAR COMMUNICATION INOPERATIVE. AS PER (ASME A17.1 2.27.1.1.3). CLEAN ENTIRE MACHINE ROOM. AS PER (ASME A17.1 8.6.4.1). CLEAN ENTIRE PIT AREA. AS PER (ASME A17.1 8.6.4.1). PROVIDE UPDATED MAINT$310 due
ECB03/17/2026CLASS 2 ITEMS: IN-CAR COMMUNICATION INOPERATIVE. PROVIDE AN UPDATED MAINTENANCE LOG. REMOVE USED PARTS AND DRUMS / BUCKETS FROM MACHINE ROOM. CLEAN THE ENTIRE PIT AREA.$310 due
ECB02/11/2026CLASS 1 RTS: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE ONLY DEVICE IN THIS BUILDING IS FOUND TO BE OUT OF SERVICE, CREATING$1K due
ECB01/29/2026DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE, CALL OR EMAILTHE D.O.B. EIR@BUILDINGS.NYC.GOV. ELEVATOR DIVISION AT (212) 393-2144 FOR A RE$1K due
ECB12/30/2025REPLACE WORN GIBS WHERE NEEDED. SECURE GIBS WHERE NEEDED. INOPERATIVE CAR PHONE. MISSING IN CASE OF FIRE SIGNS. MISSING CAT ONE TAG. MAINTENANCE LOG NOT UP TO DATE. REMOVE ALL NON ELEVATOR EQUIPMENT FROM MACHIN$625 due
HPD11/30/2025§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 5L, 5th STORY, 2nd APARTMENT FROM NORTH AT EAST
DOB11/22/2023FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
ECB07/06/2023OBSERVED ON THE FIFTH FLOOR IN THE LAUNDRY ROOM HAVING AN OPEN VENT ,GAS LINE NOT BEING SUPPORTED ,HAVING OPEN END GAS LINE AND A FUTURE ON THE GAS LINE. WHICH CONTRARY TO FGC SECTION 408.2, REPAIR AND/REPLACE$1K due
DOB07/06/2023COMMISSIONERS REQUEST FOR IMMEDIATE CORRECTIVE ACTION I OBSERVED OPEN VENT AND OPEN GAS LINE IN LAUNDRY ROOM OBSERVED CONDITION(S) DOES NOT COMPLY WITH SECTION 28-301.1 OF THE B102 AND PRESENTS AN IMMINENT RISK TO PUBLIC SAFETY. CORRECT THE SITUATION WITHIN 48 HOURS