DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB01/13/1997V-DOB VIOLATION - ACTIVE
DOB06/09/1994V-DOB VIOLATION - ACTIVE
DOB04/23/1993V-DOB VIOLATION - ACTIVE
ECB06/26/2026REISSUE#35721304R EXIT DOOR NOT SELF-CLOSING.NOTED:EXTERIOR EXIT DOORSDO NOT SELF-CLOSE WHEN TESTED ON 1ST FLR AT EXIT 8,11,6,5,12,2,3 AND 16.REM:REPAIR/REPLACE DOOR.Nothing owed — awaiting certificate of correction
ECB06/26/2026REISSUE#35721091M FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:INSIDE TEMP BLDG P.S.20 ON 1ST FLR ALL EMG LIGHT WENothing owed — awaiting certificate of correction
ECB06/26/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.USE OF PROHIBITED AND/OR HARDWARE PER BC 1008.1.8;27-371(J).NOTED:ON THE 4TH FLR RM#'S406,409,405 ALL HAVE KICK-STOPS INSTALLED AT THE BOTTOM OF CLASSROOM DNothing owed — awaiting certificate of correction
ECB06/26/2026EMERGENCY SIGNS AT ELEVATOR CALL STATIONS MISSING,DEFECTIVE OR NON-COMPLIANT WITH SECTION REQUIREMENTS.NOTED:ON THE 1ST FLR AT ELEVATOR#2 CALL STATION,EVACUATION PLAN SIGN WAS NOT POSTED.REM:INSTALL AND/OR REPANothing owed — awaiting certificate of correction
ECB06/26/2026REISSUE#35721306K FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT EXP#3 IN REAR COURTYARD,BRICKS IN WALKWAY HAVE BECOME LOOSECREATING TRIPPING HAZARD.REM:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB06/26/2026EXIT DOORS NOT SELF-CLOSING.NOTED:AT P.S.20 TEMP BLDG EXTERIOR EXIT DOORS AT EXIT 1 AND EXIT 2 DO NOT SELF-CLOSE PROPERLY WHEN TESTED.REM:REPAIR/REPLACE DOOR.Nothing owed — awaiting certificate of correction
ECB06/26/2026REISSUE#35721305Z FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:INTERIOR FPSC DOORS DO NOT SELF-CLOSE PROPERLY AT 2ND FLR-STAIRCASE A AND E.1ST FLR-STAIRCASE A,C,D AND E.CLASSROOM DOORS DO NOT SELNothing owed — awaiting certificate of correction
ECB06/26/2026REISSUE#35721090K FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:CLASSROOM DOORS DO NOT SELF-CLOSE WHEN TESTED AT 1ST FLR RM#'SANNEX 1,ANNEX 3,ANNEX 4,ANNEX 6,ANNEX 10,ANNEX 7,ANNEX 9,ANNEX 8.FPSCNothing owed — awaiting certificate of correction
ECB09/02/2025REISSUE #35692476N DATE OF ISSUE: 10-10-2024. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT ANNEX LUNCH ROOM ENTRANCE 6, 7, 8, 9, 10 DOORS ARE NOT CLOSINNothing owed — awaiting certificate of correction
ECB09/02/2025REISSUE #35692475L DATE OF ISSUE: 10-10-2024. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED FOR DEFECTIVE HARDWARE OR DOOR CLOSURE . DOORS ARE NOT CLOSING PNothing owed — awaiting certificate of correction
ECB09/02/2025REISSUE #35685074P DATE OF ISSUE: 10-10-2024. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT EXP #3 IN REAR COURTYARD AND BRICKS WALKWAY HAS LOOSE AND LIFNothing owed — awaiting certificate of correction
ECB09/02/2025REISSUE #35685069K DATE OF ISSUE: 10-10-2024. EXIT DOOR NOT SELF-CLOSING PROPERLY AT THE TIME OF INSPECTION. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT 3RD FLOOR NEAR RM #327 2 CORRIDORS EXIT DOOR, ROOM NONothing owed — awaiting certificate of correction
ECB07/28/2025REISSUE #35692478R DATE OF ISSUE: 10-10-2024. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGESAND PUBLIC CORRIDORS PER BC 1006.1; 27-381. AT THE TIME OF INSPECTIONNothing owed — awaiting certificate of correction
ECB10/10/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT ANNEX: LUNCHROOM ENTRANCE, 6, 7, 8, 9, 10 DOORS ARE NOT CLOSING PROPERLY. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB10/10/2024REISSUE #35676505N. EXIT DOOR NOT SELF-CLOSING. NOTED: AT 3 FLOOR SMOKE STAIR C, 2FL.(5) STAIR A, E, 1FL.(5) STAIR A, C, D, E. EXITS 8, 10, 12 DOORS ARE NOT CLOSING PROPERLY 2, 3, 5, 15. REMEDY: REPAIR/REPLACENothing owed — awaiting certificate of correction
ECB10/10/2024REISSUE #35676249N. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT EXP. 3 IN REAR COURTYARD, AND BRICKS WALKWAY HAS LOOSE AND LIFTED BRICKS CAUSING TRIP HAZARDS. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB10/10/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED: AT 1 FLOOR BOX #8-8, A-10, A-11, BY CLASSROO, 3, 5, 8, 10 AND BYNothing owed — awaiting certificate of correction
ECB10/10/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT 4 FLOOR, 404, LIBRARY ENTRANCE, 3FL. 325, MENS AND WOMANS BATHROOM BY STAIRC, 2FL. CORRIDOR BY 213, 215, 220, 245, 1FL. 123, 124, 143 AND 147 DOONothing owed — awaiting certificate of correction
ECB07/26/2023EXIT DOOR NOT SELF-CLOSING. NOTED: AT CAFETERIA, EXIT #12, BOTH DOOR, EXIT#10, BOTH DOOR, EXIT#8, ONE DOOR DO NOT CLOSE PROPERLY. REMEDY: REPAIR/REPLACE DOOR.Nothing owed — awaiting certificate of correction
ECB07/26/2023REISSUE #35657991N FAILURE TO MAINTAIN BUILDING BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT EXP. #3 IN REARYARD, BRICK WALKWAY HAS LOOSE, MISSING, AND LIFTED BRICKS CAUSING A TRIPPING HAZARD. REMEDY: MAKE NECNothing owed — awaiting certificate of correction
ECB05/24/2022REISSUE35331085M-FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:REARYD WALKWAY HAS LOOSE,LIFTED BRICKS CAUSING TRIPPING HAZARD COMPLY W/CODENothing owed — awaiting certificate of correction
ECB07/23/2021FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTE AT EXPOSURE#3 REAR YARD IN THE COURTYARD THE BRICK AND CONCRETE SEATS ARE IN DISREPAIR WITH CRACKS AND BROKEN BRICKS ALSO MISSING MORTAR THROUGHOUT.REMNothing owed — awaiting certificate of correction
ECB07/23/2021REISSUE:35498506X.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTE AT EXPOSURE#3 REAR YARD(COURTYARD AND PLAY GROUND)THROUGHOUT THE ENTIRE AREA THE BRICK WALKWAY HAS BRICK THAT HAVE LIFTED CAUSING A TNothing owed — awaiting certificate of correction
ECB06/03/2020REISSUE#35423242P FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTE: DURING INSPECTION OBSERVED AT EXP#3/REAR(COURTYARD/PLAY GROUND)THROUGHOUT ENTIRE BRICK WALKWAY THERE ARE SEVERAL BRICKS THAT ARE LOOSE,Nothing owed — awaiting certificate of correction
ECB06/26/2019RE-ISSUE #35331085M.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTE:OBSERVED AT EXP#3,BRICK WALKWAY IS LOOSE AND LIFTED CAUSING ATRIPPING HAZARD.REM:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB05/03/201913X10.68M07,100M07,12M07,100D10. 13X-REPAIR LIGHTING IN STOP SWITCH, 68M-PROVIDE ON SITE; 100M-0PROVIDE MANUAL LOWERING DEVICE; 12M-PROVIDELIGHTING OVER DEVICE AREA; 100D-REPAIR PINCH DANGER BELOW TOP FLOORNothing owed — awaiting certificate of correction
ECB05/07/2018FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTE IN REAR YARD EXP#3 BRICK WALKWAY HAS LOOSE AND LIFTED BRICKS CAUSING A TRIPPING HAZARD. RMDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB06/10/2010THE AUDITORIUM IS BEING OPERATED AS A PLACE OF ASSEMBLY W/O A CURRENT CERTIFICATE OF OPERATION. NOTED: AT TIME OF INSPECTION OBSERVED APPROX OVER 500 SEATS W/O PROPER PERMITS. REMEDY: OBTAIN A PLACE OF ASSEMBLYNothing owed — awaiting certificate of correction