DOB08/28/2026FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. AT TIME OF INSPECTION OBSERVED AT EXP# 1,2,3 & 4 CRACKED AND SPALLING, OPEN MORTAR JOINTS IN TERRA COTTA AT MULCIPLE LOCATIONS. REMEDY: REMOVE AND/OR REPAIR DAMGED FACADE
ECB07/28/2026AT TIME OF INSPECTION, OBSERVED THE REQUIRED SIDEWALK SHED PARAPET INFORMATION PANEL WAS NOT PROVIDED ON THE SIDEWALK SHED, CONTRARY TO BC 3301.9.2. INSTALL THE REQUIRED SIDEWALK SHED PARAPET INFORMATION PANEL.$1K due
ECB01/28/2026FAILURE TO COMPLY/OBEY A VACATE FROM COMMISSIONER ORDER. NOTED: PROPERTY HAS A VACATE ORDER AT EXP 2(N. ELEV) AS PER VACATE ORDER #13936347 AND DOB VIO 101623SR30211XN. THE PARKING LOT DESCRIBED ON THE VACATE O$25K due
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
ECB04/16/2025JOBSITE FENCE NOT CONSTRUCTED/MAINTAINED PURSUANT TO SUBSECTION. AS NOTED: AT THE TIME OF INSPECTION PLYWOOD FENCING WAS FALLING APART. REMEDY: COMPLY WITH CODE.$5K due
ECB04/16/2025TEMPORARY CONSTRUCTION EQUIPMENT ON SITE EXPIRED PERMIT. NOTE: AT THE TIME OF INSPECTION THERE WERE NO FENCE PERMIT. REMEDY: RENEW PERMIT.$6K due
DOB04/16/2025FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON EXP #1, 2,,&4: - CRAKCS & SPALLING OPEN MORTAR JOINTS IN TERRA COTTA @ MULTIPLE FLOORS & LOCATIONS, DAMAGE MORTAR JOINTS IN BRICKS AT SEVERAL FLOORS AND LOCATIONS. REMEDY: REPLACE AN/OR REPAIR DAMAGE FACADE
ECB04/16/2025TEMPORARY CONSTRUCTION EQUIPMENT ON SITE, EXPIRED PERMIT. AS NOTED: ATTIME OF INSPECTION PIPE SCAFFOLDING PERMIT WERE EXPIRED. REMEDY: RENEWPERMIT.$6K due
DOB04/16/2025EMERGENCY WORK ORDER DUE TO PLYWOOD CONSTRUCTION FENCING IS DAMAGED AND FALLING APART. SECTIONS ARE NOT SECURED AND HAVE FALLEN ON SIDEWALK. REMEDY: IMMEDIATELY REPAIR CONSTRUCTION FENCING UNDER THE SUPERVISION OF A LICENSED PROFESSIONAL
DOB09/23/2024VIOLATION ISSUED-FAILURE TO FILE 2023 EXTERNAL LOW PRESSURE INSPECTION
DOB06/23/2024FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2023)
DOB05/17/2024FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED AT EXPOSURE 1, EXPOSURE 2 AND EXPOSURE 4 CRACK/SPALLED TERRA COTTA AT MULTIPLE LOCATIONS AND DAMAGED MARTOR JOINTS. REMEDY: MAINTAIN BUILDING REPAIR AND OR REPLACE
DOB01/19/2024.EMERGENCY WORK ORDER DUE TO HAZARDOUS FACADE CONDITION OBSERVED AT TIME OF INSPECT.OF INSPECTION.OWNER MUST IMMEDIATELY PROVIDE ADEQUATE SAFETY MEASURES ALL EXPO#1,2,&4 TO PROTECT THE PUB.EXPO#1,2&4 CRACKS SPALLING IN TERRA COTTA.AT SEVERAL LOC. & MULTI.FLRSOWNER WASPROV.A P/E TO SUPERV.REPAIR&PROV.REPORT TO DOB ASAP.REPAIR ALL DAMAGE FACADE
DOB01/19/2024FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER AT TIME OF INSPECT.OBSERVED EXPO#1,2&4 CRACKS,SPALLING IN TERRA COTTA AT SEVERAL LOC.AND ON MULTIPLE FLOORS.BROKEN WINEOW PANES ON EXPOSURE#4.THESE HAZ CONDITION NEED IMMED.ATTENTION TO AVOID HARM ANY ONE.REMEDY:REPAIR DAMAGE FSCSDE AS PER CODE PROVIDE ADEQUATE PROTECTION
DOB10/16/2023UNLAWFUL ACTS FAILURE TO COMPLY WITH COMMISSIONERS ORDER VIOL#052322CL VIOL#052322CLL01AK 5/23/22 STATES SAFETY MEASURES TO BE PUT IN PL.DUE DEFECT.COND.VIOL.080522CLL0201RF,112222CLL0201RF,031323CSR30201CC & 060323CSR0203DJ ALLDATED 08/05/22,11/22/22,03/13/23 06/05/23 RESPECT STATE DEFECT COND.AS OF 10/16/23 NOT REPAIRED.REMEDY:COMPLY W/ORDER
DOB10/16/2023FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER:OBSERVED CRACKED STONE WORK IN MULTIPLE LOCATIONS ON EXPOSURE#1,2&4 BROKEN WIND OW ON EXPOSURE 4 AND LARGE VERTICLE CRACK ON EXPOSURE#1 REMEDY: FIX AND OR REPLACE
DOB10/16/2023PARTIAL VACATE ORDER OBSERVED SEVERLY CRACKED AND SPALLED STONE WORK I N MULTPLE LOCATIONS ON EXPOSURE#2 NORTH ELEVATION AS WELL AS A LARGE VERTICLE CRACK.THERE IS NO SIDEWALK SHED OR CONTROLLED ACCESS ZONE IN THIS AREA AND THE GATE TO PARKING LOT IS OPEN TO PUBLIC.REMEDY: VACATE PARKING LOT
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB06/05/2023FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER.OBSERVED CRACK CRACKS ON EXPOSURE 1,2 AND 4 REMEDY:REPAIR AND/OR REPLACE
DOB04/25/2023VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
DOB04/22/2023FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2022)
DOB03/13/2023FAILURE TO MAINTAIN BLDGE IN A CODE COMPLIANT MANNER OBSERVED CRACK/SP SPALLED TERRA COTTA STONE WORK,DAMAGED MORTAR JOINTS&BROKEN WINDOW ON EXP#1SO.ELE.OBSER.CRACKED/SPALLED TERRACOTTA STONEWORK,UNKNOWN OBJECT ONWATERTABLE&SUPPORTED SCAFFOLDING NETTING UNSECURE EXP#2W.ELE.SPALLED CRACKED TERRACOTTA STONEWORK ON EXP#3 N.ELE.PROV.SAFETY MEASURES
DOB11/22/2022FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.AS NOTED:AT TIME OF INSPECTION BUILDING HAS CRACKS AND STEP CRACKS ON EXPOSURE#1,2&4 ON SEVERAL FLOORS,EXPOSURE#4SOUTH BROKEN WINDOW PANES OVER SIDE ENTRANCE DOOR.REMEDY:REPAIR DAMAGED FACADE PER CODE
DOB08/21/2022FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2021)
DOB08/11/2022PROVIDE APPROX. 100FT OF SIDEWALK SHED TO EXPOSURES 2NORTH ELEVATION (PARTKING LOT) & EXPOSURE#4 SOUTH ELEVATION (LAFAYETTE AVENUE) RESPECT IVELY. PROVIDE 100 FEET OF NETTING OR SIDEWALK SHED OVERHANG TO EXP#1 (CLERMONT AVENUE) SIDEWALK SHED TOWARDS THE BUILDING
DOB08/05/2022FTM EXTERIORR BLDG WALLS AND APPURTENANCES. AT TIME OF INSPECTION OBSERVED ON EXP 1,2,& 4 HAZARDOUS CONDITIONS SUCH AS CRACKES, STEP CRAKCS SPALLING IN MASONRY WORK AT VARIOUS FLOORS ALSO BROKEN WINDOW PANES AT SEVERAL FLOORS.INADEQUATE SAFETY MEASURES ON EXP1. REMEDY: IMMED PROV SIDEWALK SHED ON EXP4,2 & EXTEND SIDEWALK SHED TO FACADE
DOB05/23/2022EMERGENCY WORK ORDER DUE TO SAGGING CORNICE, SPALLED AND SEVERLY CRACKED MASONRY UNITS ON ALL EXPOSURES. ALSO DUE TO THE FACT THAT SHED INSTALLED ON FRONT EXP IS INADEQUATE. THERE WAS A WIDE GAP BETWEEN THE SHED AND EXP AND SHED HAS NO NETTING AROUND IT TO KEEP/BLOCK FALLEN OBJECTS. REMEDY:IMMED PROVIDE APPROVED SAFET MEASURES & CONTROL ACCESS
DOB04/01/2022FAILURE TO MAINTAIN-EXTERIOR BUILDING FACADE & APPURTENANCES BUILDING HAS DEFECTIVE STONE MASONRY ON ALL EXPOSURES,STEP CRACKING ON BRICKS AND STORE WORK,BROKEN WINDOW,SPALLING STONES MAINTAIN EXTERIOR BUILDING FACADE, PROVIDE APPROVED SAFETY MEASURES REPAIR DAMAGED FACADE AS PER IRCNY 103.04
DOB02/22/2022FAILED TO FILE FISP CYCLE 9A TECHNICAL REPORT BY 02/21/2022
DOB08/05/2021FAILURE TO COMPLY WITH COMMISSIONER'S ORDER 313364(053021CLLFA01RF) ISSUED ON 05/30/2020. AS OF 08/05/2021 OWNER HAS NOT COMPLIED WITH IMMEDIATE CURE ORDER. REMEDY: IMMED COMPLY WITH CODE AND COMMISSIONER'S ORDERS
DOB06/21/2021FTM EXTERIOR BLDG FACADE AND APPURTENANCES. AT TIME OF INSPECTION OBSERVED DETERIORATED JOINTS A STONE SPALLING STONE, CRACK, LOOSE STONE, MISSING WINDOW AND DEFECTS AT DECORATIVE STONE. REMEDY: MAINTAIN EXTERIOR BLDG FACADE AND APPURTENANCES AS PER 1 RCNY 103-04
DOB06/20/2021FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2020)
DOB06/29/2020FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2019)
DOB05/30/2020FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES.WEST AND SOUTH ELEVATIONS DISPLAY SUBSTANTIALLY CRACK STONE WORK AT THE BASE OF WINDOWS AND COLUMNS CREATING A HAZARD FOR PEDESTRIANS REMEDY:MAINTAIN EXTERIOR FACADE.TAKE/PROVIDE SAFETY MEASURES(SIDEWALK SHED)MAKE REPAIRS AS PER 1 RNCY 103-04
DOB04/05/2019VIOLATION ISSUED TO ELEVATOR - FAILURE TO FILE CATEGORY 1 2017 INSPECTION/TEST
DOB04/05/2019VIOLATION ISSUED TO ELEVATOR - FAILURE TO FILE CATEGORY 1 2017 INSPECTION/TEST
DOB03/18/2019FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2018)
DOB08/08/2018V-DOB VIOLATION - ACTIVE
DOB08/08/2018V-DOB VIOLATION - ACTIVE
DOB03/27/2018FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2017)
DOB06/30/2017V-DOB VIOLATION - ACTIVE
DOB06/30/2017V-DOB VIOLATION - ACTIVE
DOB02/16/2017FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 IN 2016
DOB07/19/2016V-DOB VIOLATION - ACTIVE
DOB07/19/2016V-DOB VIOLATION - ACTIVE
DOB10/22/2008V-DOB VIOLATION - ACTIVE
ECB04/20/2026FAILURE TO FILE ACCEPTABLE CYCLE 9A AND 10A REPORT INDICATING CORRECTION OF UNSAFE CONDITION DESCRIBED IN INITIAL FACADES REPORT REQUIRED BY28-302.5 FOR CONTROL #1016993. REMEDY: FILE ACCEPTABLE REPORT.Hearing held — result not yet published$1K proposed
ECB04/16/202527-MISC; 28-MISC; BC-MISC. UNSECURED DEBRIS NETTING ON SUPPORTED SCAFFOLDING. AS NOTED: AT THE TIME OF INSPECTION I OBSERVED NETTING FLYING LOOSELY ON SCAFFOLDING. REMEDY: COMPLY WITH CODE, SECURE DEBRIS NETTINHearing held — result not yet published$1K proposed
ECB12/17/2024FAILURE TO OBEY A VACATE ORDER FROM THE COMMISSIONER PER 28-207.4. NOTE: AT TIME OF INSPECTION OBSERVED VACATE ORDER FOR PARKING LOT ONCE ATTHE SITE OBSERVED 2 CARS PARKED IN PARKING LOT OBSERVED OPEN LOCK TO ENothing owed — awaiting certificate of correction
ECB12/17/2024JOB SITE FENCE NOT CONSTRUCTED OR MAINTAINED PURSUANT TO SUBSECTION. NOTE: AT TIME OF INSPECTION UNSECURED CONSTRUCTION FENCE LEANING TOWARDS THE SIDEWALK SHED AND BECOMING PINNED. OBJECTS SUCH AS CONSTRUCTIONNothing owed — awaiting certificate of correction
ECB12/17/2024EXPIRED SIDEWALK SHED PERMIT. NOTE: AT TIME OF INSPECTION, OBSERVED SIDEWALK SHED IN PLACE. NOTE: B00794637-1R-SH WAS EXPIRED ON 12-01-2024.NO VALID PERMIT ON BIS OR DOB NOW. REMEDY: RENEW PERMIT.Nothing owed — awaiting certificate of correction
ECB12/17/2024TEMPORARY CONSTRUCTION EQUIPMENT ON SITE: EXPIRED PERMIT FOR CONSTRUCTION FENCE/NO PERMIT PULLED FOR THE CONSTRUCTION FENCE THAT WAS INSTALLED AROUND THE PROPERTY. REMEDY: RENEW PERMIT. GET PERMIT.Nothing owed — awaiting certificate of correction
ECB05/17/2024TEMPORARY CONSTRUCTION EQUIPMENT ON SITE: EXPIRED PERMIT. PEMRIT #B00357782-11-SF EXPIRED ON 02/24/2024 NO PERMIT POSED ON DATABASE. REMEDY:RENEW PERMIT.Nothing owed — awaiting certificate of correction
ECB05/17/2024JOB SITE FENCE NOT CONSTRUCTED OR MAINTAINED PURSUANT TO SUBSECTION. NOTE AT TIME OF ISNPECTION OBSERVED AT EXPOSURE 1 SECTION OF FENCE MISSING AND IS LEANING AGAINST THE BUILDING. LEAVING AN OPENING AND REASONNothing owed — awaiting certificate of correction
ECB01/30/2024JOB SITE FENCE NOT CONSTRUCTED OR MAINTAINED PURSUANT TO SUBSECTION. AS NOTED: AT TIME OF INSPECTION I OBSERVED ON EXPOSURE #1 WEST ELEVATION PANELS MISSING/SECTIONS OF FENCE BROKEN OFF AND LEANING ON THE BUILDNothing owed — awaiting certificate of correction
ECB12/09/2022FAILURE TO SUBMIT ACCEPTABLE REQUIRED CYCLE 9A REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL & APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL #916993.REMEDY:SUBMIT ACCEPTABLE REQUIRED TENothing owed — awaiting certificate of correction
ECB10/14/2022FAILURE TO PROVIDE ADEQUATE SAFETY MEASURES SUCH AS NETTING,SHED,ETC WHERE REQUIRED TO PROTECT & SECURE PUBLIC SAFETY FROM DOCUMENTED UNSAFE FACADE AS PER 1RCNY 103.04 NOTE:AS PER PREVIOUS VIOLATION #35663893LNothing owed — awaiting certificate of correction
ECB04/01/2022FAILURE TO PROVIDE SIDEWALK SHED WHERE REQUIRED.AS NOTED BUILDING HAS DEFECTIVE MASONRY FACADE ON ALL EXPOSURE AND NO PROTECTION IS PROVIDE ON EXPOSURE 2 AND 4 WHICH SPALLED STONES CRACKED BRICKS AND STORE WORKNothing owed — awaiting certificate of correction
ECB01/26/2022PEDESTRIAN PROTECTION NOT MEET CODE.SIDEWALK SHED.AT TIME OF INSPECTION IN RESPONSE TO COMPLIANT UNIT TIGHTS SURROUNDING 317 CLERMONT AVE,I OBSERVED PEDESTRIAN PROTECTION SIDEWALK SHED IN PLACE UNDERSIDE OF SIDNothing owed — awaiting certificate of correction
ECB01/18/201897X10 THE ELEVATOR IN BLDG OUT OF SERVICE.UPON INSPECTION THE DEVICE IS FOUND TOB E OUT OF SERVICE. RESTORE TO SERVICE IMMEDIATELY.Nothing owed — awaiting certificate of correction
ECB08/09/2014FAIL TO MAINTAIN BLDG WALL & APPURTENANCES.NOTED:@THE EAST CORNER OF THE SOUTH ELEVATION FROM THE ROOF DOWN TO THE 4FLR LEVEL DEFECTIVE MASONRY CONSISTING OF A VERTICAL CRACK.ALSO NOTED TERRA-COTTA DEFECTIVE ONNothing owed — awaiting certificate of correction