DOB08/25/2026FTM. OBSERVED AT EXP 1 WEST ELEVATION: CRACK EYEBROW ON 7TH FL-; CRACKS IN PLASTER ON 7TH FL-CRACKS ON WATERTABLE ON 7TH FL. EXP 2 EROSION/SPALLING BRICKS AT MULTIPLE LOCATIONS EXP 3, EAST ELEVATIONS CRACKS IN 8TH FL. PLASTER; CRACKS IN 8TH FL WATERTABLE/SILL
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB04/16/2025FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED AT EXPOSURE 1 WEST ELEVATION CRACK/DAMAGED STONE @ ROOF CORNICE AND AT 7 FLOOR. EXPOSURE 2 MULTIPLE SPALLING. EXPOSURE 3 CRACK STONE AND DAMAGED JOINTS AT 7TH FLOOR. REMEDY: REPAIR AND/OR REPLACE
ECB11/04/2024EXPIRED SIDEWALK SHED PERMIT. NOTE: AT TIME OF INSPECTION, SIDEWALK SHED PERMIT EXPIRED AND NO PERMIT POSTED ON DATABASE. REMEDY: RENEW PERMIT.$6K due
DOB10/23/2024FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. EXPOSURE 1 WEST ELEVATION DAMAGED TERRA COTTA @ ROOF CORNICE & SPALLING BRICKS, BROKEN GLASS PANEL @ 1ST FL & ENTRY DOOR. EXPOSURE 3 SPALLING MASONRY& WINDOW SILL. EXPOSURE 2 SPALLING BRICKS. REMEDY: MAINTAIN BUILDING REPAIR AND/OR REPLACE
DOB09/23/2024VIOLATION ISSUED-FAILURE TO FILE 2023 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB04/25/2023VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
DOB02/22/2022FAILED TO FILE FISP CYCLE 9A TECHNICAL REPORT BY 02/21/2022
DOB11/18/2021V-DOB VIOLATION - ACTIVE
DOB11/02/2019FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
ECB10/28/2019FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35354327H ISSUED ON 11-27-2018 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01(D)(2) AN ACCEPTIBLE CE$6K due
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB08/02/2019FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB05/20/2019FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB05/02/2019FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB11/28/2018FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
ECB11/27/2018TEMPORARY CONSTRUCTION EQUIPMENT ON SITE EXPIRED PERMIT.NOTE;OBSERVED SIDEWALK SHED IS IN PLACE WITH EXPIRED PERMIT #340349901 ON 05-15-18.REM:RENEW PERMIT.$630 due
ECB11/27/2018INFORMATION PANEL.NOTE;OBSERVED SIDEWALK SHED IS IN PLACE WITHOUT AN INFORMATION PANEL ON IT.REM;COMPLY WITH CODE.$6K due
ECB09/07/2018FAILURE TO MAINTAIN BLDG EXTERIOR FALLS FACADES AND APPURTENANCES. WEST ELEVATION EXP1: BROKEN GLASS AT ENTRANCE DOOR, CRACK GLASS AT EXIT DOOR, BROKEN WINDOW GLASS AT 2ND FLOOR WINDOW, MISSING DECORATIVE$12K due
DOB05/31/2018FAILED TO FILE FISP CYCLE 8A TECHNICAL REPORT BY 02/21/2017
ECB05/18/2018FAILURE TO SUBMIT ACCEPTABLE 8TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL #809562. RMDY: SUBMIT REQUIRED TECHNICAL REPORT.$6K due
ECB03/27/2018FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: ILLUMINATION FOR EXITS, EXIT DISCHARGE AND PUBLIC CORRIDORS PER BC 1006.1:28-381 OBSERVED AT PUBLIC CORRIDORS ON 1ST FLOOR AND EXIT DISCHARGE PATH FROM THE$625 due
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB03/31/2014VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2012 INSPECTION/TEST
DOB03/31/2014VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2012 INSPECTION/TEST
DOB01/31/2013FAILED TO FILE FISP CYCLE 7A TECHNICAL REPORT BY 02/21/2012
DOB12/13/2011VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2010 INSPECTION/TEST
DOB03/31/2008V-DOB VIOLATION - ACTIVE
DOB07/01/1997V-DOB VIOLATION - ACTIVE
DOB04/17/1995V-DOB VIOLATION - ACTIVE
ECB04/16/2025EXPIRED SIDEWALK SHED PERMIT. NOTE: AT THE TIME OF INSPECTION OBSERVEDPERMIT EXPIRED AND NO PERMIT POSTED ON DATABASE. REMEDY: RENEW PERMIT.Nothing owed — awaiting certificate of correction
ECB10/23/2024PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATION: OBSERVED DAMAGED/ROTTED MUDSILL AT EXPOSURE 1 FLATBUSH AVENUE. REMEDY: COMPLY TO CODE SPECIFICATION.Nothing owed — awaiting certificate of correction
ECB12/09/2022FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 7A,8A AND 9A REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL#909562.AGG2 HISTORY OF NONCOMNothing owed — awaiting certificate of correction
ECB07/08/2020FAILURE TO MAINTAIN EXTERIOR BLDG FACADE & APPURTENANCES.NOTE:OBSERVEDCRACKED & DEFECTIVE BRICKWORK & TERRA COTTA STONE WORK ON THE UPPER 2 LEVELS OF EXPOSURES 1 & 3,WEST & EAST ELEVATIONS.REMEDY:MAINTAIN EXTERNothing owed — awaiting certificate of correction
ECB05/20/2020FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 7A & 8A REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL & APPURTENANCESREQUIRED BY 28-302.4 FOR CONTROL #809562.AGG2 HISTORY OF NONCOMPLIANCENothing owed — awaiting certificate of correction
ECB03/27/2018FAILURE TO MAINTAIN IN CODE COMPLIANT MANNER OBSERVED AT 1ST FLOOR CORRIDOR A PILE OF JUNK STORED BY CELLAR FLOOR'S STAIRCASE EXCESSIVE DEBRIS, WOODEN CONSTRUCTION MATERIALS STORED IN THE EGRESS PATH, CREATINGNothing owed — awaiting certificate of correction
ECB12/20/2016FAILURE TO SUBMIT ACCEPTABLE 7TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS & APPURTENANCES REQUIRED BY 28-302.4. AGG2 HISTORY OF NONCOMPLIANCE ON 36023254X(AGG1),36019111R.Nothing owed — awaiting certificate of correction
ECB01/12/2016FAILURE TO FILE AN ACCEPTABLE TECHNICAL REPORT IN COMPLIANCE W/CODE PROVISIONS: PERIODIC INSPECTION OF EXERIOR WALLS AND APURTENANCES AS RE QUIRED BY ARTICLE 28.302 AND THE DOB RULES AND REGULATIONS.RMDY:FILE TNothing owed — awaiting certificate of correction
ECB06/12/2014FAILUER TO FILE AN ACCEPTABLE CYCLE 7 TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS: PERIODIC INSPECTION OF EXTERIOR WALLS & APPURTENANCES AS REQUIRED BY ARTICLE 28-302 & THE DEPT OF BLDGS RULES & REGULATNothing owed — awaiting certificate of correction
ECB06/07/2010FAILURE TO FILE AN ARCHITECT/ENGINEER REPORT CERTIFYING EXIT/DIRECTIONAL SIGNS ARE CONNECTED TO EMERGENCY POWER SOURCE/STORAGE BATTERY EQUIPMENT. REMEDY:FILE ARCHITECT/ENGINEER REPORT.Nothing owed — awaiting certificate of correction
ECB12/19/1998FAILURE TO SUBMIT A FOURTH ROUND TECHNICAL REPORT: PERIODIC INSPECTIONOF EXTERIOR WALLS AND APPURTENANCES AS REQUIRED BY LOCAL LAW 10 OF 1980 AND THE DEPARTMENT OF BUILDINGS RULES AND REGULATIONS. REMEDY:Nothing owed — awaiting certificate of correction
ECB09/08/1998FAILURE TO SUBMIT A FOURTH ROUND TECHNICAL REPORT: PERIODIC INSPECTIONOF EXTERIOR WALLS AND APPURTENANCES AS REQUIRED BY LOCAL LAW 10 OF 1980 AND THE DEPARTMENT OF BUILDINGS RULES AND REGULATIONS.REMEDY:FILENothing owed — awaiting certificate of correction
Office with commercial, 7-19 stories · 6,438 sf lot · 6.86 FAR built · Flood zone X