HPD05/13/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ROOF COVERING MATERIAL
HPD05/13/2026§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 5R, 5th STORY, 1st APARTMENT FROM NORTH AT EAST
HPD05/13/2026§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT 5R, 5th STORY, 1st APARTMENT FROM NORTH AT EAST
HPD11/25/2025§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 6C, 6th STORY, 1st APARTMENT FROM NORTH AT EAST
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
ECB06/26/2025AT TIME OF INSPECTON I OBSERVED SIDEWALK SHED INSTALLED ON EXPOSURE # 1 WITHOUT SIGNS OR PROJECT INFORMATION PANEL ON THE SHED PARAPET, TO DISPLAY THE NAME AND THE CONTACT INFORMATION OF THE OWNER OR THE GENER$6K due
HPD05/07/2025§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT GAS RANGE IN THE KITCHEN LOCATED AT APT 2A, 3rd STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD05/07/2025§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE COUNTER BALANCE LOWER SASH WINDOW AT EAST WALL IN THE BATHROOM LOCATED AT APT 2A, 3rd STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD01/21/2025§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT RANGE FOR COOKING IN THE KITCHEN LOCATED AT APT 5B, 5th STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD01/21/2025§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT ALL WALLS IN THE ENTIRE APARTMENT LOCATED AT APT 5B, 5th STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD01/21/2025§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT ALL CEILINGS IN THE ENTIRE APARTMENT LOCATED AT APT 5B, 5th STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD12/13/2024§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT COVE ON WALL IN THE 1st LIVING ROOM FROM NORTH AT WEST LOCATED AT APT 6C, 6th STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD11/15/2024§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE NAILED SHUT UPPER AND LOWER WINDOW SASHES IN THE BATHROOM LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD07/23/2024§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT STOVE IN THE KITCHEN LOCATED AT APT 6A, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH
HPD03/22/2024§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT THE GAS RANGE IN THE KITCHEN LOCATED AT APT 6C, 6th STORY, 2nd APARTMENT FROM SOUTH AT WEST
ECB03/14/2024RESTORE TO SERVICE IMMEDIATLY.$6K due
DOB03/06/2024FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB02/22/2024FAILED TO FILE FISP CYCLE 9C TECHNICAL REPORT BY 2/21/2024
ECB02/01/2024FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8C REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FACADES REPORT REQUIRED BY 28-302.5 FOR CONTROL #802854.AGG2 HISTORY OF NONCOMPLIANCE ON 370221$6K due
HPD01/31/2024§27-2153 ADM CODE THE PREMISES HAS BEEN SELECTED TO PARTICIPATE IN THE ALTERNATIVE ENFORCEMENT PROGRAM WHICH MAY RESULT IN BUILDING-WIDE INSPECTIONS, FEES, AND EXTENSIVE REPAIR WORK TO CORRECT VIOLATIONS AND UNDERLYING CONDITIONS. CHARGES FOR REPAIR WORK DONE PURSUANT TO THIS ORDER, IF NOT PAID, WILL BECOME LIENS ON THE PROPERTY
ECB12/13/2023FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION PER 1RCNY 11$6K due
ECB10/16/2023R T S . THE ELEVATOR IN THE BUILDING OUT OF SERVICE , UP ON INSPECTION THE DEVICE IS FIND TO BE OUT OF SERVICE , REPAIR AND RESTORE TO SERVICE IMMEDIATELY$12K due
ECB08/14/2023R T S. THE ELEVATOR IN BUILDING OUT OF SERVICE , UP ON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE . REPAIR AND RESTORE TO SERVICE IMMEDIATELY.$6K due
HPD07/29/2023§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT RANGE IN THE KITCHEN LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD07/29/2023§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SPRING BALANCE AT UPPER AND LOWER WINDOW SASHES IN THE BATHROOM LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD05/19/2023§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT RANGE IN THE KITCHEN LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD05/17/2023§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT GAS RANGE IN THE KITCHEN LOCATED AT APT 4B, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH
HPD05/08/2023§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT RANGE IN THE KITCHEN LOCATED AT APT 6C, 7th STORY, 1st APARTMENT FROM WEST AT NORTH
ECB05/08/202397/X/17 RESTORE TO SERVICE FOR PROPER INSPECTION BY DOB.$6K due
HPD04/29/2023§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT RANGE IN THE KITCHEN LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST
ECB03/20/2023CLASS 1 9,97/X/17 RESTORE TO SERVICE FOR PROPER INSPECTION BY DOB.$6K due
ECB03/14/2023AT TIME OF INSPECTION OBSERVED SPALLING BRICK INTERIOR SIDE OF ROOF PARAPET, COPPING MISSING ON PARAPET TOP, PARAPET RAILING DAMAGED AND MINOR CRACKS ON EXTERIOR SIDE. ALSO OBSERVED 2- DAMAGED WINDOWS & BOARDED$6K due
ECB02/16/2023CLASS 1: UPON INSPECTION FOUND DEVICE TO BE OUT OF SERVICE. RESTORE TO SERVICE REPAIR IMMEDIATELY AS PER 1RCNY 11-02. REINSPECTION REQUIRED CONTACT NYCDOB AT EIR@BUILDINGS.NYC.GOV.$12K due
ECB02/10/2023ELEVATOR OUT OF SERVICE.... UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE CREATING A HAZARDOUS CONDITION PER 1RCNY 11-02. RESTORE SERVICE IMMEDIATELY AND NOTIFY NYC D.O.B. BY EMAILING EIR@BUILDINGS.$6K due
HPD02/03/2023§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ALL WALLS AND THE CEILING IN THE 2nd ROOM FROM NORTH LOCATED AT APT 5A, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH
ECB01/10/2023CLASS 1: RESTORE TO SERVICE REPAIR IMMEDIATELY & CALL NYCDOB FOR INSPECTION. FIRE SERVICE MISSING. INSTALL AS AS MANDATED BY CODE A-17.1 SECTION 3.10.12 OF THE 2014 NYCBC K3.$6K due
DOB12/02/2022VIO22-50158
ECB08/04/20222/X10 OUT SIDE COMM INOPERATIVE REPAIR,98/BB/7 CAT FIVE EXPIRED 7/2016 PROVIDE FILE FOR TEST BY DOB. 8/V/1 CAR FLOOR TO LANDING SILL NOT LEVEL ADJUST, 57/BB/7 FIRE EXTINGUISHER EXPIRED PROVIDE.$3K due
HPD06/15/2022HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST
DOB05/11/2022FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
ECB04/28/2022REPAIR PHONE, PROVIDE KEYS TO MOTOR ROOM$3K due
DOB04/13/2022FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
ECB02/24/2022PHONE NOT WORKING, ELEVATOR NOT LEVELING PROPERLY AT THE TOP FLOOR$3K due
ECB02/11/2022V/F CLASS 1, RESTORE TO SERVICE FOR PROPER INSPECTION BY D/O/B.$6K due
ECB01/12/2022FAILURE TO MAINTAIN IN CODE COMPLIANT MANNER.UPON INSPECTION,OBSERVED SOME UNITS 1A,1B,1D,3D,4D,5D ALL OF THE UNITS NEEDS FULL INTERNAL RENOVATION.DUE TO SEVERAL HOLES AND DAMAGED AREA IN SEVERAL PLACES ON PLYW$6K due
ECB11/24/2021FAILURE TO FILE ACCEPTABLE AMENDED CYCLE8C REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FACADES REPORT REQUIRED BY28-302.5 FOR CONTROL#802854.FILE ACCEPTABLE REPORT$6K due
ECB10/05/2021FOUND OUTSIDE COMMUICATION (PHONE) IN CAR IS NOT WORKING. REPAIR. CAT5 TAG IN THE ELEVATOR MACHINE ROOM EXPIRED. PERFORM CAT5 TEST AND PROVIDE CAT5 TAG IN THE ELEVATOR MACHINE ROOM. BRAKE TAG IN THE ELEVATOR MA$3K due
DOB12/09/2020FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
ECB09/17/2020NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY : FILE APPLICATION, INSTALL DLM$1K due
DOB03/30/2020V-DOB VIOLATION - ACTIVE
DOB05/20/2019FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB01/18/2019V-DOB VIOLATION - ACTIVE
DOB01/13/2016FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
HPD11/29/2010§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ELECTRICAL LIGHT SWITCH COVER AT NORTH WALL IN THE BATHROOM LOCATED AT APT 1D, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
DOB11/30/2007V-DOB VIOLATION - ACTIVE
HPD11/16/1987§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT WALLS CEILINGS AND WOODWORK 3 STY FRONT WEST APT 3B THROUGHOUT. LOCATED AT APT 3B
HPD12/19/1985D26-10.01 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR WALL AT SOUTH 3RD STY REAR EAST APT 3D CENTER ROOM. LOCATED AT APT 3D
HPD12/19/1985D26-10.01 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WALL TILE AT 3RD STY REAR EAST APT 3D BATHROOM. LOCATED AT APT 3D
ECB04/20/2026FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8C AND 9C REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FACADES REPORT REQUIRED BY 28-302.5 FOR CONTROL #902854. REMEDY: FILE ACCEPTABLE REPORT.Hearing held — result not yet published$1K proposed
ECB05/17/2023OBSERVED IN BASEMENT IN BOILER ROOM INSTALLED NEW WATER LINES FOR TWO NEW ELECTRIC HOT WATER HEATERS ALL WORK COMPLETED NO PERMITS, OBTAIN PERMITNothing owed — awaiting certificate of correction
ECB03/27/2023OBSERVED ON THE GROUND FLOOR OUTSIDE OF BOILER ROOM HAVING NO PERMIT ON RECORD FOR THE UNUSED GAS PIPING OUTLET. WORK WAS DONE %100, OBTAIN PERMIT; MUST BE CAPPED, VALVED, AND ON AN APPROVED APPLICATION PER NYCNothing owed — awaiting certificate of correction
ECB07/20/20163307.9 FAILED TO REMOVE SIDEWALK SHED UPON JOB COMPLETION.NOTED:@TIME OF INSPECTION FACADE REPAIR WORK UNDER APP#122224299 WAS COMPLETED &SIGNED OFF 7/11/16 SIDEWALK SHED WASN'T REMOVED.REM:COMPLY W.CODE.Nothing owed — awaiting certificate of correction
ECB07/20/2016SIDEWALK SHED PARAPET SIGN NOT IN COMPLIANCE W.SECTION.NOTED:@TIME OF INSPECTIION SIGN FOR SIDEWLAK SHED @EXP#1 DOESN'T CONTAIN BLDG ADDRESSOF THE SITE.&THE STATEMENT FOR MORE INFO VISIT WWW.NYC.GOV/BUILDINGS FNothing owed — awaiting certificate of correction
ECB07/20/20163307.6.5.3 FAILURE TO MAINTAIN SIDEWALKS SHED.NOTED:@TIME OF INSPECTION SEVERAL CROSS BRACES FOR SIDEWALK SHED ARE DETACHED.SHARP EDGES(BOLTS ON VERTICAL POSTS)ARE NOT PROTECTED.REM:MAINTAIN SIDEWALK SHED IN ORNothing owed — awaiting certificate of correction
ECB07/20/2016PEDESTRIAN PROTECTION DOESN'T MEET CODE SPECS.NOTED:@TIME OF INSPECTION SIDEWALK SHED @EXP#1 DOESN'T EXTEND 5FT PAST THE BLDG ON THE RIGHT HAND SIDE.SIDEWALK SHED CROSS BRACES BLOCKING FIRE ESCAPE LADDER.REM:CONothing owed — awaiting certificate of correction
ECB10/22/2015WORK W/O A PERMIT: ILLEGAL WORK NOTED: ERECTED NEW PARTITIONS, NEW ELECTRIC LINES,WATER,WASTE LINES IN APTS #5D; 3D; #3B AND REMOVAL OF PARTITITONS IN BASEMENT REAR APT WORK APPROX 70% COMPLETED W/O FIRST OBTAINothing owed — awaiting certificate of correction
ECB10/22/2015FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT BSMT LEVEL REAR APT WITH REMOVED PARTITIONS,AND WALLS OPENINGS ACCUMULATED CONSTRUCTION DEBRIS FROM OTHER APTS STORED ON HIGH. PILE THROUGHOUTNothing owed — awaiting certificate of correction
ECB02/19/2015WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS &/OR APPROVEDAMENDMENTS. NOTE: SIDEWALK SHED HAS BEEN ERECTED AT FRONT OF THE BLDG UNDER PERMIT #140270659-01-EQ-SH. 1)THERE ARE 3 LINES OF SWS COLUMNSNothing owed — awaiting certificate of correction
ECB02/04/2011B154,51,15,44A,48A,B,50,50A,B,C,D,E,F,G,H,I. 51- 53 (PPM) CARBON MONOXIDE IN BOILER ROOM. 50- 3 PRESSURE CONTROLS ON 1/2 PIPE TO BOILER. 50A- LWCO PIPE CORRODED. 50B- SUMP PUMP DEFECTIVE. 50C- CONDENSATE PUMPNothing owed — awaiting certificate of correction