HPD05/01/2026(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
HPD03/18/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BELL BUZZER FROM BUILDING FRONT TO EAST WALL IN THE FOYER LOCATED AT APT 3R, 3rd STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD03/18/2026§ 27-2029 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FOR THE APARTMENT IN THE ENTIRE APARTMENT LOCATED AT APT 3R, 3rd STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD03/18/2026§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED AT PUBLIC HALL AT BOILER ROOM, 1st STORY
HPD03/17/2026§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ' EAST WALL, CEILING IN THE KITCHEN LOCATED AT APT 2R, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD03/17/2026§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE BATHROOM , THE 1st ROOM FROM EAST, THE 4th ROOM FROM EAST LOCATED AT APT 2R, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD03/17/2026§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE EAST WALL, CEILING IN THE KITCHEN LOCATED AT APT 2R, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD03/17/2026§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE ELECTRICAL CEILING LIGHT FIXTURE IN THE 1st ROOM FROM EAST LOCATED AT APT 2R, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD03/17/2026§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 2R, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD03/17/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SPRING BALANCE AT LOWER SASH WINDOW AT EAST 1 IN THE 1st ROOM FROM EAST LOCATED AT APT 2R, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD03/17/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LOWER LSASH COUNTER BALANCE SPRING, FIRST WINDOW FROM NORTH AT EAST IN THE 1st ROOM FROM EAST LOCATED AT APT 2R, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD03/17/2026§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) NORTH WALL, SOUTH WALL, WEST WALL, 1st WINDOW FRAME FROM SOUTH AT WEST WALL IN THE KITCHEN LOCATED AT APT 2R, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD03/17/2026§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD-PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE AND EITHER TESTED INCONCLUSIVE FOR LEAD CONTENT AT 0.5MG/CM2 OR TESTED POSITIVE FOR LEAD CONTENT ON A METAL OR CERAMIC SUBSTRATE AS SET FORTH IN (28 RCNY §11-07(b)) USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(b)(2). 1st DUMB WAITER FROM EAST AT SOUTH WALL IN THE KITCHEN LOCATED AT APT 2R, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD03/17/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL LIGHT FIXTURE AT CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT 2R, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD03/17/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BELL BUZZER FROM BUILDING FRONT TO NORTH WALL, IN THE FOYER LOCATED AT APT 2R, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD03/16/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SPRING BALANCES AT LOWER WINDOW SASG AT FIRE ESCAPE WINDOW IN THE KITCHEN LOCATED AT APT 4R, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD03/16/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE AT BUILDING FRONT LEADING TO THE WEST WALL IN THE FOYER LOCATED AT APT 4R, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD03/16/2026§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 4R, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD03/16/2026§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 4R, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD03/12/2026§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM BOILER ROOM DOOR LOCKED AT CELLAR AT BOILER ROOM
HPD12/22/2025§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER SASH WINDOW IN THE KITCHEN LOCATED AT APT 4R, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD12/22/2025§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ FT AT CEILING IN THE KITCHEN LOCATED AT APT 4R, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST ORIGINAL VIOLATION 18523619 ISSUED 22-DEC-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b).
HPD12/22/2025§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 4R, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD12/22/2025§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 4R, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD12/22/2025§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BELL BUZZER FROM BUILDING ENTRANCE TO APARTMENT AT EAST WALL IN THE FOYER LOCATED AT APT 4R, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD12/22/2025§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE KITCHEN LOCATED AT APT 4R, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD12/22/2025§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM LOCKED DOOR AT BASEMENT AT BOILER ROOM
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
HPD06/06/2025(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
ECB05/12/2025WEILMCLAIN STEAM BOILER HAS POOR FLAME FROM OIL BURNER+SPILL SWITCH IS INCORRECT+CHIMNEY DOOR INOPERABLE+WASTE OIL IN BOILER ROOM+STORAGE@OIL TANK+MISSING ANTISYPHON VALVE;CORRECT VIOLATION+SUBMIT CERTIFICATE O$1K due
DOB09/23/2024VIOLATION ISSUED-FAILURE TO FILE 2023 EXTERNAL LOW PRESSURE INSPECTION
HPD09/13/2024§ 27-2056.4 ADM CODE- CORRECT FAILURE TO NOTIFY OCCUPANTS AND/OR TO INVESTIGATE LEAD-BASED PAINT HAZARDS.
HPD09/13/2024§ 27-2056.7 ADM CODE: CORRECT FAILURE TO PROVIDE TO THE DEPARTMENT WITHIN 45 DAYS OF DEMAND ALL RECORDS REQUIRED TO BE MAINTAINED BY OWNER PURSUANT TO LOCAL LAW 1 OF 2004 RELATED TO LEAD-BASED PAINT NOTICES, INSPECTIONS AND REMEDIATION/ABATEMENT ACTIVITIES.
HPD06/10/2024§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED
HPD06/10/2024§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF BABY CARRIAGE FREE STANDING ON THE FLOOR , AT PUBLIC HALL, 1st STORY
HPD06/10/2024§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HELMET ,STORAGE BOX, FREE STANDING ON THE FLOOR, AT PUBLIC HALL, 3rd STORY
HPD06/10/2024§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD. AT PUBLIC HALL, 1st STORY
HPD06/10/2024§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF KIDS SCOOTER OVERLAPPED ON RADIATOR, ON THE FLOOR, AT PUBLIC HALL, 2nd STORY
HPD06/10/2024§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE CEILING LIGHT FIXTURE, IN THE MIDDLE SECTIONS, AT PUBLIC HALL, 3rd STORY
HPD04/03/2024(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
HPD03/20/2023(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
HPD02/22/2022(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
HPD04/06/2021(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
HPD04/16/2014SECTION 27-2040 ADM CODE PROVIDE ADEQUATE LIGHTING AT OR NEAR THE OUTSIDE OF THE FRONT ENTRANCEWAY OF THE BUILDING AND KEEP SAME BURNING FROM SUNSET EVERY DAY TO SUNRISE ON THE DAY FOLLOWING A MINIMUM OF 100 WATTS OF INCANDESCENT LIGHT REQUIRED. (LIGHT FIXTURE PRESENT)
HPD03/10/2013SECTION 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 1; WG TO REPLACE = 0; WG TO REPAIR = 2; IN THE ENTIRE APARTMENT LOCATED AT APT 4L, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
HPD02/11/2013SECTION 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY ?11-06(B)(2) EAST WALL IN THE PRIVATE HALLWAY LOCATED AT APT 4L, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
HPD02/11/2013SECTION 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY ?11-06(B)(2) NORTH WALL, EAST WALL, WEST WALL IN THE 3rd ROOM FROM NORTH LOCATED AT APT 4L, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
HPD02/11/2013SECTION 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY ?11-06(B)(2) NORTH WALL, WEST WALL IN THE 5th BATHROOM FROM NORTH LOCATED AT APT 4L, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
HPD02/11/2013SECTION 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY ?11-06(B)(2) WEST WALL IN THE 6th KITCHEN FROM NORTH LOCATED AT APT 4L, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
DOB01/19/2007V-DOB VIOLATION - ACTIVE
DOB09/16/1997V-DOB VIOLATION - ACTIVE
DOB02/10/1997V-DOB VIOLATION - ACTIVE
DOB08/29/1995V-DOB VIOLATION - ACTIVE
HPD06/02/1995SECTION 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE SHEET ROCK CEILING BATHROOM 3 STY APT 3L ER1. , SECTION '' ''
HPD06/02/1995SECTION 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF CONCEALED LEAK CEILING BATHROOM 3 STY APT 3L ER1. , SECTION '' ''
DOB06/01/1994V-DOB VIOLATION - ACTIVE
DOB08/16/1993V-DOB VIOLATION - ACTIVE
DOB06/01/1993V-DOB VIOLATION - ACTIVE
HPD06/25/1991SECTION 27-2013 ADM CODE REMOVE OR COVER IN A MANNER APPROVED BY THE DEPARTMENT THE PEELING LEAD PAINT CEILING 2ND ROOM FROM FRONT 3 STY EAST APT 3L ER1 1771508. , SECTION '' ''
HPD06/25/1991SECTION 27-2013 ADM CODE REMOVE OR COVER IN A MANNER APPROVED BY THE DEPARTMENT THE PEELING LEAD PAINT CEILING AND DOORS FRONT ROOM HERNANDEZ 965 9752 3 STY EAST APT 3L ER1 1771508. , SECTION '' ''