ECB02/09/2022UNLAWFUL ACTS.FAIL TO COMPLY WITH AN ORDER OF COMMISSIONER.FAIL TO CORRECT AND CERTIFY ECB#35343154P-NO GFCI PROVIDED OUTDOOR ECB#35343155R-FIXABLE METAL CONDUIT MORE THAN 6 FT ECB#35343150H-FAILURE TO GROUND,N$12K due
ECB12/21/2021UNLAWFUL ACTS.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.FAILURE TO CORRECT AND CERTIFY SUMMONS ECB#35343950H;ECB#35343154P AND ECB#35343156Z.UNAPPROVED,UNSAFE,UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS$12K due
ECB09/23/2021FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER SUMMONS 35343150H AND 35343155R STILL REMAINS, COMPLY WITH COMMISSIONER'S ORDER; COMPLY WITH CODE$12K due
ECB11/06/2021UNLAWFUL ACTS. FAILURE TO COMPLY W/ AN ORDER OF THE COMMISSIONER. FAILURE TO CORRECT AND CERTIFY SUMMONS#35343150H NO WATER MAIN GROUND,SUMMONS#35343151J GEC IS NOT OF PROPER SIZE,SUMMONS#35343154P OUTDOORS ANDNothing owed — awaiting certificate of correction
ECB05/21/2019FAILURE TO COMPLY W/ COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35343248X ISSUED ON 8/6/18,AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28.201.1 AND 1RCNY 102-01(D)(2). AN ACCEPTABLE CERTIFICATENothing owed — awaiting certificate of correction
ECB10/05/2018FAIL TO PROVIDE/MAINTAIN SUFFICIENT ACCESS/WORKSPACE ABOUT ELECTRICAL EQUIPMENT.MIN CLEARANCE IS NOT PROVIDED IN FRONT OF ELECTRICAL PANELS IN KITCHEN ELECT AREA.REM:PROVIDE/MAINTAIN ACCESS/WORK SPACENothing owed — awaiting certificate of correction
ECB10/05/2018350.12.3.AMENDMENT.FLEXIBLE METAL CONDUIT FEEDING OUTDOOR AC UNIT BEHIND BAK IS MORE THAN 6FT.REM:COMPLY WITH EC CODE.MUST FILE AN ELECTRICAL APPLICATIONNothing owed — awaiting certificate of correction
ECB10/05/2018UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE.EMT USED OUTDOOR TO SUPPLY POWER TO WOMEN LOCKER ROOM.REM:COMPLY WITH EC CODE MUST FILE AN ELECTRICAL APNothing owed — awaiting certificate of correction
ECB10/05/2018TABLE 250.66.GROUNDING CONDUCTOR AT 400 SER SW IS NOT OF PROPER SIZE #8 BARE SOLID CONDUCTOR USE FOR SER ENTRNACE CONDUCTOR 500 INCH GROUNDING CONDUCTOR IS NOT AS PER TABLE.REM:COMPLY WITH EC CODE MUST FILE ANNothing owed — awaiting certificate of correction
ECB10/05/2018FAILURE TO GROUND ELECTRICAL SYSTEM.NO WATER MAIN GROUND IS PROVIDED AT WATER MAIN FOR YOU A SENSWIS.REM:PROVIDE GROUNDING.MUST FILE AN ELECTRICAL APPLICATIONNothing owed — awaiting certificate of correction
ECB10/05/2018210.8.B.GFCI IS NOT PROVIDED FOR OUTLETS OUTDOOR AND OUTDOOR BAKS ENTIRE GROUNDS OUTDOOR AREA,REC AREA,WOMEN LOCKER ROOM,SHEDS.REM:COMPLY WITH EC CODE MUST FILE AN ELECTRICAL APPLICATIONNothing owed — awaiting certificate of correction
ECB10/05/2018UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS,MATERIALS,DEVICE APPLIANCES OR WIRING IN USE,FLEXIBLE CORD USED AS PERMANENT WIRING OUTDOOR FLEXIBLE CORD USED AS PERMANENT WIRING OUTDOOR FEEDING FASNothing owed — awaiting certificate of correction
ECB08/06/2018UNAPPROVED/UNSAFE/UNSUITABLE/ELECTRICAL EQUIPMENTS,APPARATUS,MATERIALS,DEVICES,APPARATUS OR WIRING IN USE.EXTERNSION CORDS & FIXTURE/ZIP CORDS USED AS PERMENANT WIRING THROUGHOUT.REM:COMPLY W/EC CODE/OBTAIN PERNothing owed — awaiting certificate of correction
ECB07/24/2018GFC503.4.1.MISC VIOLATIONS USE OF APPROVED MAINTAIN.ON THE ABOVE MENTIONED DATE I OBSERVED PVC PIPING BEING USED TO VENT 2 HOT WATER HEATERSAT THIS PROPERTY WHICH IS NOT PERMITTED AS PER THE CODE.REM:COMPLY WINothing owed — awaiting certificate of correction
ECB07/24/2018WORK WITHOUT A PERMIT.AT THE TIME OF MY INSPECTION I OBSERVED THE INSTALLATION OF MOBILE BATHROOM AT THE REAR OF THE ESTABLISHMENT I ALSO OBSERVED THAT THESE BATHROOMS HAD PVC PIPING USED FOR THE WASTE LINES INothing owed — awaiting certificate of correction
ECB07/24/2018FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER.FAILURE TO COMPLY WITH LAW FOR DRAINAGE SYSTEM PER 702.1;27-911;THE ABOVE MENTION DATE I OBSERVED THE USE OF PVC PIPING USED THROUGHOUT PREMISES.THE PIPINNothing owed — awaiting certificate of correction