DOB07/30/2026FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED THE FOLLOWING CONDITIONS AT EXPOSURE 1 AND 4 CRACKS, DEFLATED LINTELS AND DAMAGED JOINTS. REMEDY: REPAIR AND/OR REPLACE
ECB07/27/2026PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATIONS. NOTED AT THE TIME OF INSPECTION I OBSERVED DEFECTIVE/INADEQUATE AND DAMAGED/ROTTED MUDSILLS AT MULTIPLE LOCATIONS WHICH ARE NOT IN COMPLIANCE WITH NYC AD$2K due
ECB04/02/2026FOUND A BEST 5E250 BOILER HEATING BOTH BUILDING 3535&3555 LEAKING WATER FROM INSIDE THE BOILER CHAMBER/AIR PROOFING SWICTH NOT WORKING PROPERLY/OIL PUMP MISSING BELT GUARD/ CORRECT ALL VIOLATING CONDITION/SUBMI$6K due
ECB04/02/2026AT TIME OF COMPLAINT INSPECTION I FOUND THE WATER BOOSTER PUMP MAKING A LOUD NOISE IN BUILDING 3555 KINGS COLLEGE PL CELLAR, MAINTAIN BOILER; CORRECT ALL VIOLATING CONDITION/ SUBMIT A CERTIFICATE OF CORRECTION$1K due
ECB03/02/2026CEASE USE ISSUED FOR, DLM A SAFETY DEVICE NOT WORKING. REMEDY; REPAIR THEN AND CONTACT NYCDOB, FOR RESTORE TO SERVICE, RE-INSPECTION,$6K due
ECB11/07/2025UPON REINSPECTION, THE DEVICE IS FOUND TO BE OUT OF ORDER, BY THE COMMISSIONER ORDER, REMEDY REPAIR CEASE USE ITEMS, THEN CONTACT NYCDOB FOR A RE-INSPECTION .$3K due
HPD10/22/2025§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT BATHTUB IN THE BATHROOM LOCATED AT APT 1F, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD10/22/2025§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE SOUTH WALL IN THE BATHROOM LOCATED AT APT 1F, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD10/22/2025§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT SINK IN THE KITCHEN LOCATED AT APT 1F, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD10/22/2025§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK THE CEILING IN THE BATHROOM LOCATED AT APT 1F, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD10/22/2025§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 1F, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD06/10/2025§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE EAST WALL IN THE KITCHEN LOCATED AT APT 5D, 5th STORY, 4th APARTMENT FROM NORTH AT EAST
HPD06/10/2025§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK PENETRATING AT EAST WALL IN THE KITCHEN LOCATED AT APT 5D, 5th STORY, 4th APARTMENT FROM NORTH AT EAST
HPD03/25/2024§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING AT PUBLIC HALL, 1st STORY
HPD03/25/2024§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED AT PUBLIC HALL, 1st STORY
HPD03/25/2024§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR MISSING AT PUBLIC HALL, 1st STORY
HPD03/25/2024§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY
HPD03/25/2024§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX MISSING AT PUBLIC HALL, 1st STORY
HPD03/25/2024§ 27-2053 ADM CODE POST SIGN ON WALL OF ENTRANCE STORY BEARING NAME, ADDRESS INCLUDING APARTMENT NUMBER IF ANY, AND TELEPHONE NUMBER OF SUPERINTENDENT, JANITOR OR HOUSEKEEPER. AT PUBLIC HALL, 1st STORY
HPD03/25/2024§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD. AT PUBLIC HALL, 1st STORY
HPD03/25/2024§ 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING.
ECB02/15/2024FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8A AND 9A REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITAIL FACADES REPORT REQUIRED BY 28-302.5 FOR CONTROL #908218. REMEDY: FILE ACCEPTABLE REPORT.$6K due
ECB02/15/2024FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8A AND 9A REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FACADES REPORT REQUIRED BY 28-302.5 FOR CONTROL #908219. REMEDY: FILE ACCEPTABLE REPORT.$6K due
DOB11/01/2023FAILURE TO CORRECT SWARMP CONDITIONS
DOB08/11/2023CYCLE 9A UNSAFE REPORT FILED
DOB04/22/2023FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2022)
DOB12/21/2022EMER WORK ORDR TO PROV SAFTY MSURES.SDEWALK SHED TO SCURE PUBSFTY @ EXP1 EAST ELEVTION&EXPO34 NRTH ELEVTION TO PRTCT PUB SFTY UNSFE FILING #908219-9A-001 DATED 8/31/2020
ECB12/16/2022FAILURE TO SUBMIT ACCEPTABLE REQUIRED CYCLE8A,9A REPORT OF CRITICAL EXAM DOCUMENTING CONDITION OF EXTERIOR WALL&APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL908219.AGG1:PRIOR NOV 37021180J UNDER 28-302.4.SUBMI$10K due
ECB12/16/2022FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 8A AND 9A REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITIONS OF EXTERIOR WALL AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL#908218.AGG1:PRIOR NOV 37021178K$10K due
DOB11/21/2022FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2021)
ECB09/13/2022FAILURE TO PROVIDE SAFETY MEASURES TO PROTECT PUBLIC SAFETY FROM DOCUMENTED UNSAFE FACADE.NOTE:QEWI SUBMITTED UNSAFE NOTIFICATION #908219 DATED 8/31/22 HOWEVER AS OF TODAY 9/13/22 SAFETY MEASURES STILL MISSING$25K due
ECB09/13/2022FAILURE TO PROVIDE SAFETY MEASURES TO PROTECT PUBLIC SAFETY FROM DOCUMENTED UNSAFE FACADE.NOTE:QEWI SUBMITTED UNSAFE NOTIFICATION #908218 DATED ON 98/31/2022 BUT AS OF TODAY 9/13/22 SAFETY MEASURES STILL MISSIN$10K due
DOB02/22/2022FAILED TO FILE FISP CYCLE 9A TECHNICAL REPORT BY 02/21/2022
ECB07/09/2021FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 8A REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL#808219.AGG1 PRIOR NOV 37011295K UNDER 2$10K due
DOB06/02/2021FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
ECB04/01/2021FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 8A REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL#808218.AGG1 PRIOR NOV 37011296M UNDER 2$10K due
DOB02/17/2019FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
ECB09/25/2018FAILURE TO SUBMIT ACCEPTABLE 8TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL#808218. REMEDY: SUBMIT REQUIRED TECHNICAL REPORT$1K due
ECB09/25/2018FAILURE TO SUBMIT ACCEPTABLE 8TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL#808219. REMEDY: SUBMIT REQUIRED TECHNICAL REPORT$6K due
DOB05/31/2018FAILED TO FILE FISP CYCLE 8A TECHNICAL REPORT BY 02/21/2017
DOB05/01/2014FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
ECB05/11/2026RTS CLASS 1: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITIONHearing held — result not yet published$1K proposed
ECB04/20/2026FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8A AND 9A REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FACADES REPORT REQUIRED BY 28-302.5 FOR CONTROL #908219. AGG1: PRIOR NOV 37026421Y UNDERHearing held — result not yet published$3K proposed
ECB04/20/2026FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8A AND 9A REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FACADES REPORT REQUIRED BY 28-302.5 FOR CONTROL #908218. AGG1: PRIOR NOV 37026435P UNDERHearing held — result not yet published$3K proposed