ECB04/30/2026OBSERVE IN LAUNDRY ROOM ON FIRST FLOOR LACK OF SPRINKLER COVERAGE PER BC 28-301.1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED PER BC 903.2; 27-$3K due
HPD04/30/2026(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
HPD11/17/2025§27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID REGISTRATION STATEMENT IS FILED.
ECB03/12/2024I OBSERVED ON THE 2ND AND 3RD FLOOR ELECTRICAL CLOSETS THE INSTALLATION OF DATA WIRING AND EQUIPMENT. AS PER EC 110.25 NO EQUIPMENT OTHER THAN ELECTRICAL DISTRIBUTION. PHOTOS TAKEN; EC 110.25, COMPLY WITH EC CO$2K due
ECB03/12/2024I OBSERVED ON THE ROOF THE FLEXIBLE CORD SUPPLYING POWER TO THE LIGHTS IMPROPERLY TERMINATED WITHOUT A STRAIN-RELIEF CONNECTOR. THIS ALSO ALLOWS FOR WATER PENETRATION OF THE FIXTURE., COMPLY WITH EC$2K due
ECB04/12/2023I OBSERVED ON THE ROOF THE IMPROPER TERMINATION OF THE FLEXIBLE CORDS SUPPLYING POWER TO THE LIGHTS, NO STRAIN RELIEF CONNECTORS IN USE AND THE CONNECTORS IN USE ALLOW FOR WATER PENETRATION. PHOTOS TAKEN., COMP$800 due
DOB01/13/1997V-DOB VIOLATION - ACTIVE
ECB04/30/2026CLASS 1 CEASE USE: IN-CAR STOP SWITCH INOPERATIVE. REPAIR OR REPLACE IN-CAR STOP SWITCH AND VERIFY PROPER FUNCTION. TEST TO ENSURE POSITIVE STOP OF CAR WHEN ACTIVATED. MAINTAIN IN SAFE WORKING CONDITION. EMAILHearing held — result not yet published$1K proposed
ECB04/30/2026CLASS 2: BRAKE MAINTENANCE TAG NOT CURRENT. CATEGORY 1 TEST TAG NOT CURRENT. HOIST CABLES SHOW SIGNS OF ROGUE. REMEDY: REMEDY: UPDATE AND MAINTAIN CURRENT BRAKE MAINTENANCE TAG AND CATEGORY 1 TEST TAG IN ACCORDHearing held — result not yet published$625 proposed
ECB05/08/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED PER BC 903.2; 27-954. OBSERVED INADEQUATE SPRINKLER COVERAGE FOR GAS POWER DRYERS. LOCATED ON 1ST FNothing owed — awaiting certificate of correction
ECB03/12/2024I OBSERVED ON THE FIRST FLOOR THE GAS-FIRED SYSTEMS LOCATED IN THE MECHANICAL ROOM WITH NO REMOTE SHUT-DOWN AS REQUIRED BY MC 1006.8.1 PHOTOS TAKEN.; MC 1006.8.1, COMPLY WITH CODE; SUPPLY A REMOTE SHUT-DOWNNothing owed — awaiting certificate of correction
ECB09/07/2023WHEN ON A DHS SWEEP INSPECTION, UPON INSPECTION, CEASE USE VIOLATION WAS ISSUED, FOR THE FOLLOWING ITEMS 1/ IN CAR STOP SWITCH DEFECTIVE,NOT WORKING, 2/ LOWER LANDING DOOR BREAKING CONTACT WHEN PULL ON, 3/ DISCNothing owed — awaiting certificate of correction
ECB04/12/2023I OBSERVED ON THE FIRST FLOOR A MECHANICAL ROOM WITHOUT A REMOTE SHUTDOWN FOR THE FUEL BURNING SYSTEMS. AS PER MC 1006.8.1 A REMOTE SHUTDOWN MUST BE PROVIDED AT THE IMMEDIATE POINT EGRESS. PHOTOS TAKEN.; MC 100Nothing owed — awaiting certificate of correction
ECB04/12/2023I OBSERVED ON FLOORS 2 AND 3 THE INSTALLATION OF DATA NETWORK EQUIPMENT AND WIRING IN THE ELECTRICAL CLOSET, NO EQUIPMENT OTHER THAN ELECTRICAL DISTRIBUTION EQUIPMENT SHALL BE INSTALLED IN ELECTRICAL CLOSETS. PNothing owed — awaiting certificate of correction