DOB06/23/2024FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2023)
DOB05/29/2024FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
ECB02/13/2024(05-A-10) CEASE USE ITEM. DOOR ZONE RESTRICTOR HAS BEEN TAMPERED WITH/ DISABLED AND RENDERED INOPERATIVE. THIS IS A SAFETY DEVICE TO ENSURE ELEVATOR PASSENGERS' SAFETY. REPAIR RESTRICTOR AND CONTACT NYCDOB AT E$1K due
DOB10/04/2023FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB04/22/2023FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2022)
DOB02/22/2023FAILED TO FILE FISP CYCLE 9B TECHNICAL REPORT BY 2/21/2023
ECB12/08/2022FOUND ROCKMILLS MODEL MP125 OIL FIRED STEAM BOILER SERIAL#91124 CEASED USE DUE TO HAZARDOUS CONDITION.EVIDENCE OF TUBES LEAKING AND CHAMBER FULL OF WATER DO NOT OPERATE BOILER UNTIL HAZARDOUS CONDITIONS ARE IMM$1K due
DOB08/21/2022FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2021)
DOB12/09/2021V-DOB VIOLATION - ACTIVE
DOB06/20/2021FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2020)
HPD08/26/2020§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK ABOVE CEILING IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 6U, 6th STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD08/26/2020§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 6U, 6th STORY, 2nd APARTMENT FROM SOUTH AT WEST
DOB06/29/2020FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2019)
DOB03/16/2020V-DOB VIOLATION - ACTIVE
DOB03/16/2020V-DOB VIOLATION - ACTIVE
DOB11/08/2019VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
DOB11/08/2019VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB04/05/2019VIOLATION ISSUED TO ELEVATOR - FAILURE TO FILE CATEGORY 1 2017 INSPECTION/TEST
DOB03/18/2019FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 IN 2018
DOB08/09/2018FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
ECB05/09/20185X10)CEASE USE ITEM. DOOR ZONE RESTRICTOR HAS BEEN TAMPERED WITH/DISABLED AND RENDERED INOPERATIVE. THIS IS A SAFETY DEVICE TO ENSURE ELEVATOR PASSENGERS SAFETY. REPAIR RESTRICTOR AND CONTACT NYCDOB AT EIR@BUIL$726 due
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
DOB02/02/2016FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB11/02/2015FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB08/02/2015FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB05/02/2015FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB05/30/2014VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
DOB05/30/2014VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
DOB01/29/2014FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB10/28/2013FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB10/28/2013FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB10/09/2013FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
HPD04/22/2009§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING & NORTH WALL IN THE BATHROOM LOCATED AT APT 5A, 5th STORY, 1st APARTMENT FROM NORTH AT EAST
HPD04/22/2009§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF CONCEALED WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 5A, 5th STORY, 1st APARTMENT FROM NORTH AT EAST
ECB12/08/2022BOLTS MISSING ON BOILER DOORS,2-LOW WATER CUT OFFS ON 1-TAPPING,SAIL SWITCH TIED BACK NOT WORKINGNothing owed — awaiting certificate of correction
ECB12/08/2022BOLTS & DOGS MISSING ON BOILER DOORS,SMOKE ALARM NOT WORKING,2-LOW WATER CUT OFFS ON 1- TAPPING,SAIL SWITCH FOR COMBUSTION AIR FAN TIED BACK NOT WORKINGNothing owed — awaiting certificate of correction
ECB11/26/2021IN CAR ALARM BELL INOPERATIVE , REPAIR / OPERATOR COVER MISSING , PROVIDE / WATER IN PIT , REMOVENothing owed — awaiting certificate of correction
ECB03/19/2019REMOVAL OF SAFETY MEASURE, SUCH AS SIDEWALK SHED'S W/O DEPT APPROVAL. NOTE: AT THE TIME OF INSPECTION BUILDING FACADE WAS STILL DESIGNATED AS UNSAFE, THE AMENDED FACADE REPORT RECEIVED ON 03-12-2019.HAD NOTNothing owed — awaiting certificate of correction
ECB01/28/2019FAILURE TO SUBMIT A REQUIRED CYCLE 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL #811354. RMDY: SUBMIT REQUIRED TECHNICAL REPORT.Nothing owed — awaiting certificate of correction
ECB09/20/2016FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS.AT THE TIME OF MY INSPECTION @12:10PM I OBSERVED ON THE MAIN FLOOR IN THE LAUNDRY ROOM THAT THNothing owed — awaiting certificate of correction
ECB09/20/2016FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS.AT THE TIME OF MY INSPECTION@12:10PM I OBSERVED ON THE MAIN FLOOR IN THE LAUNDRY ROOMS COMMERNothing owed — awaiting certificate of correction
ECB10/31/2013WORK W/O PERMIT WORK NOTED: AT CELLAR ON GROUND LEVEL WEST WING,CLOSEST TO 38 AVENUE.CREATED A CLASS"A"APT WITH FULL 3PC BATHROOM (TOILET,SINK,TUB)INSTALLED WATER AND WASTE LINES,INSTALLED RESIDENTIAL SINK INNothing owed — awaiting certificate of correction
ECB10/31/2013RESIDENCE ALTERED FOR OCCUPANCY AS A DWELLING FOR MORE THAN THE LEGAL LY APPROVED NUMBER OF FAMILIES.NOTED: COFO#102137 INDICATES ONE (1) SUPT'S APT ON GROUND (CELLAR) LEVEL. PRESENTLY THERE IS TWO(2), ONE LENothing owed — awaiting certificate of correction
ECB08/08/2013FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED. AT THE TIME OF INSPECTIO I OBSERVED ONE GAS RANGE IN USE IN THE SUPER'S CELLAR APT W/O PERFORMING GAS TEST. PERMIT #420808497 OBTAINED AND HAD GAS PIPINGNothing owed — awaiting certificate of correction
ECB08/08/2013GAS BEING SUPPLIED TO BLDG W/O INSPECTION AND CERTIFICATION BY DOB AT THE TIME OF INSPECTION I OBSERVED 1 RANGE IN USE IN THE SUPER'S CELLARAPT. INSPECTIONS MUST BE DONE TO GET GAS AUTHORIZATION. PIPING ROUGHNothing owed — awaiting certificate of correction
ECB07/08/2013USE OR INSTALLATION OF PLUMBING MATERIALS OR EQUIPMENT WHICH DO NOT COMPLY WITH RS-16.AT TIME OF INSPECTION I OBSERVED 2 SPEED QUEEN DRYERS INSTALLED WITH FLEXIBLE GPS CONNECTORS.SOLID PIPING MUST BE USED WHENothing owed — awaiting certificate of correction
ECB07/08/2013FAILURE TO PROVIDE A SYSTEM OF AUTOMATIC SPRINKELRS WHERE REQUIRED/2 DRYERS 2 MORE AT THE TIME OF INSPECTION I OBSERVED 2 SPEED QUEEN DRYERS IN USE IN THE CELLAR LAUNDRY ROOM W/O AN AUTOMATIC SPRINKLER SYSTEMNothing owed — awaiting certificate of correction