DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
ECB04/01/2026REISSUE#35692454M FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:THERE ARE SEVERAL EXTERIOR EXIT DOORS THAT ARE ROTTED,RUSTED, AND SEVERLY DETERIORATED,LARGE HOLES AT DOOR BOTTOMS ALLOW RODENTS,WATNothing owed — awaiting certificate of correction
ECB03/31/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THERE ARE SEVERAL WINDOWS SCATTERED THROUGH OUT THE SCHOOL THAT ARE BROKEN OR DAMAGED AND DO NOT OPERATER CORRECTLY. SOME SCREWED AND INOPERABLE. RENothing owed — awaiting certificate of correction
ECB03/31/2026RE-ISSUE #35692452Z. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THERE IS DAMAGE TO THE WALLS AND CEILINGS OF BULKHEADS FROM THE WATER LEAKING THROUGH ROOF ABOVE. REMEDY: REPAIR/REPLACE.Nothing owed — awaiting certificate of correction
ECB03/31/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THERE WERE SEVERAL ROOMS SCATTERED THROUGH OUT THE SCHOOL THAT HAVE COMBUSTIBLE MATERIALS HANGING, CREATING A FIRE HAZARD. OBSERVED ELECTRICAL STRINNothing owed — awaiting certificate of correction
ECB03/31/2026RE-ISSUE #35692451R. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THERE IS WATER PENETRATION WITH EVERY RAIN AT STAIRWAY #AAT EACH LEVEL. THE CHANGE IS SERIOUS AT THE WINDOWS AT ALL LEVELS. REMNothing owed — awaiting certificate of correction
ECB05/06/2025RE-ISSUE #35672294Y. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THE WINDOWS AT STAIRWAY #A AT ALL LEVELS ALLOW WATER PENETRATION WHEN/EVER IT RAINS. ONGOING FOR YEARS, DAMAGE CONTINUES. REMEDNothing owed — awaiting certificate of correction
ECB05/06/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THERE ARE SEVERAL EXIT DOORS THROUGHOUT THE ECHOOL THAT NEED TO BE REPLACED. THEY ARE SERIOUSLY RUSTED, ROTTED AND DETERIORATING AT DOOR BOTTOMS ANDNothing owed — awaiting certificate of correction
ECB05/06/2025RE-ISSUE #35672295X. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THERE ARE SEVERAL DOORS SCATTERED THROUGHOUT THE SCHOOL AT EXITS, THAT ARE SERIOUSLY RUSTED, ROTTED AND DETERIORATING, INCLUDINNothing owed — awaiting certificate of correction
ECB05/06/2025RE-ISSUE #35672293M. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: WALLS AND CEILINGS AT BULKHEAD LOCATIONS SHOW SIGNS OF WATER DAMAGE FROM THE ROOF LEAKS ABOVE THESE AREAS. REMEDY: REPAIR/REPLANothing owed — awaiting certificate of correction
ECB03/14/2024REISSUE#35665334 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNERNOTED:THERE ARE SEVERAL DOORS THROUGHOUT THE SCHOOL THAT ARE RUSTED,ROTTED AND SERIOUSLY DETERIORATING.THESE DOORS NEED TO BE REPLACED.REM:RNothing owed — awaiting certificate of correction
ECB03/14/2024REISSUE#35665335X FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:THE WINDOWS AT STAIRWAY#A AT ALL LEVELS ALLOW WATER PENETRATION WHEN LIT RAINS.REM:REPAIR/REPLACE-FIX LEAKS AT WINDOWS.Nothing owed — awaiting certificate of correction
ECB03/14/2024REISSUE#35665336H FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.WATER PENETRATION THRU ROOF AT BULKHEAD LOCATIONS.WALLS AND CEILINGSAT BULKHEADS SHOW OBVIOUS SIGNS OF THE LEAKS.REM:REPAIR/REPLACE ROOFINNothing owed — awaiting certificate of correction
ECB01/30/2023REISSUE #35636505R.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT EXIST 2 & 7 & OTHER EXITS DOORS & FRAMES RUSTED & ROTTED.LARGE HOLES FROM CONDITION AT BOTTOM OF DOORS THAT ALLOW RODENTS TO GETNothing owed — awaiting certificate of correction
ECB01/30/2023REISSUE #35636506Z FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:ONGOING PROBLEM OF LEAKS IN ROOF CONTINUES.BULKHEADS SHOW OBVIOUS PROOF OF LEAKS BY WATER.REMEDY:REPAIR/REPLACE/FIX LEAKS IN ROOFNothing owed — awaiting certificate of correction
ECB01/30/2023REISSUE #35636504P FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:WINDOWS ON ALL LEVEL AT STAIRWAY A ALLOW RAINWATER TO PENETRATE INTO BUILDING.WINDOWS HAVE BEEN LEAKING FOR YEARS & NEED TO BE FIXENothing owed — awaiting certificate of correction
ECB02/07/2022REISSUE#35555848Y.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED AT TOI THE WINDOWS AT STAIRCASE A LEAK WHEN IT'S RAINING FROM UPPER FLOORS TO GROUND FLOOR.REMEDY:REPAIR/REPLACE FIX LEAKS.Nothing owed — awaiting certificate of correction
ECB02/07/2022REISSUE#35555847M AND 35555844R AND 849X.FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER.OBSERVED AT TOI AT EXITS 2 AND 7 AND VARIOUS OTHER LOCATIONS.DOORS AND DOOR BUCKS ARE RUSTED AND ROTTED AND NOT WNothing owed — awaiting certificate of correction
ECB02/07/2022REISSUE#35555843P.FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER.OBSERVED AT TOI THE ROOF LEAKS AT SEVERAL LOCATIONS.THIS PROBLEM IS MOST EVIDENT AT ALL 3 BULKHEAD LOCATIONS CAUSING DAMAGE AT BULKHEADSNothing owed — awaiting certificate of correction
ECB04/19/2021FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES NOTE@STAIRCASER WINDOWS LEAK WHEN RAINING FROM TOP FL TO GROUND FL.MAINTAIN BLDG EXTERIOR WALLS.Nothing owed — awaiting certificate of correction
ECB04/19/2021FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER NOTE@EXITS2&7 DOOR BUCK IS RUSTED OUT@BOTTOM OF MIDDLE MULLON.REPAIR &/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB04/19/2021REISSUE35502143P FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER NOTE@BULKHEAD B&C WATER DAMAGE TO WALLS&STAIRS.REPAIR&/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB04/19/2021REISSUE35502146K FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER NOTE@ROOF LEVEL BULKHEAD C&A WATER PENETRATION@BOTTOM OF BULKHEAD CAUSING DAMAGE TO INTERIOR WALLS.REPAIR &/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB07/06/2020REISSUE ECB #35459549Y FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER AT BULKHEAD AND STAIRCASE #B&C WATER FAMAGE AND STRING IN NEED OF REPAIR ,PROBLEM CONTINUED AND GETS WORSE WITH EACH HEAVY RAIN REPAINothing owed — awaiting certificate of correction
ECB07/06/2020REISSUE 35452238P FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANENR NOTE ROOF LEVEL WATER PENETRTAION AT BULKHED (C) AT BOTTOM OF BULKHEAD ON EAST AND SOUTH SIDE ALSO ROOF MATERIALS IN POOR SHAPE WITH VARIONothing owed — awaiting certificate of correction
ECB03/05/2020WORK AFTER HOURS W/O A VARIANCE PERMIT CONTRARY TO 28-105.12.5. NOTE:AT THE TIME OF INSPECTION IT WAS OBSERVED TEMPORARY ELECTRIC WORK BEINGPERFORMED ON THE OUTSIDE OF THE ABOVE ADDRESS. VARIANCE PERMIT#5008765Nothing owed — awaiting certificate of correction
ECB12/06/2019FAILURE TO MAINTAIN. NOTED:AT TIME OF INSPECTION,AT BULKHEAD AND STAIRCASE#B&#C WATER DAMAGE AND STAINING IN NEED OF REPAIR. PROBLEM CONTINUED AND GETS WORSE W/ EACH HEAVY RAIN. REMEDY:REPAIR/REPLACE. FIX THE LNothing owed — awaiting certificate of correction
ECB10/23/2019FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED AT BULKHEAD C & STAIRCASE B&C WATER PENETRATION TAKES PLACE WHEN HEAVY RAINS ARE ACTIVE.SIGNS OF WATER ARE OBVIOUS EVEN WHEN DRY.REMEDY:REPAIR/REPLACENothing owed — awaiting certificate of correction
ECB09/03/2019FAILURE T MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTE AT ROOF LEVEL WATER PENETRATION AT BULKHEAD C AT BOTTON OF BULKHEAD ON EAST AND SOUTH SIDE ALSO ROOF MATERIAL IN POOR SHAPE WITH VARIOUS AREAS ROTTON ANNothing owed — awaiting certificate of correction
ECB09/03/2019REISSUED #35386193L FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTE AT ROOF LEVEL BULKHEAD C WATER PENETRATION INSTAIRASE B& C ALSO BULKHEAD B WATER PENETRATION AT WINDOW ON 3RD FLOOR REPAIR AND OR RNothing owed — awaiting certificate of correction
ECB07/12/2018REISSUE #35271118H FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.WATER PENETRATION AT VARIOUS LOCATIONS AT STAIRCASE B & C FROM BULKHEAD TO GAS METER ROOM. DAMAGE TO WINDOW LINTEL AT 3RD FLOOR BELOW BULKHENothing owed — awaiting certificate of correction
ECB06/21/2017REISSUE#35216964P FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNERS. NOTED: STAIRCASE'A'LANDING'S BETWEEN 2ND & 3RD FL THE WINDOW LINTEL IS CORRODED & RUSTED SIGNS OF WATER PENETRATION AT STAIRCASE'B'&'C'Nothing owed — awaiting certificate of correction
ECB10/28/2016REISSUE #35093569H FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT STAIRCASE (A) AT LANDINGS 1ND, 3RD FLOOR WINDOWS, TOP WINDOW SILLS SPALLING AND DAMAGE FROM INSIDE. ALSO, AT BULKHEAD STAIRCNothing owed — awaiting certificate of correction
ECB03/31/2014FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: INTERIOR. AT STAIRWAY A AT LANDINGS 2ND & 3RD FLOOR WINDOWS, TOP WINDOW SILLS SPALLING & DAMAGED FROM INSIDE. REMEDY: REPAIR TOP WINDOW SILLS INTEIROR.Nothing owed — awaiting certificate of correction